Bryant 310AAV instruction manual Cleaning Heat Exchanger, Igniter Position-Side View

Page 46

310AAV

NOTE: If thermostat terminals are jumpered at the time blower access door switch is closed, blower will run for 90 sec before beginning a heating or cooling cycle.

c.Perform component self-test as shown at the bottom of the SERVICE label, located on the front of blower access door.

d.Verify blower is rotating in the correct direction

16.If furnace is operating properly, RELEASE BLOWER ACCESS DOOR SWITCH. Remove any jumpers or re- connect any disconnected thermostat leads. Replace blower access door.

17.Downflow or horizontal furnaces with vent pipe through furnace only:

a.Install and connect short piece of vent pipe inside fur- nace to existing vent.

b.Connect vent connector to vent elbow.

18.Reinstall casing door.

19.Turn on gas supply and cycle furnace through one com- plete heating and cooling cycle. Verify the furnace temper- ature rise as shown in Adjustments Section. Adjust tem- perature rise as shown in Adjustments Section. If outdoor temperature is below 70_F, (21_C) turn off circuit breaker to outdoor unit before running furnace in the cooling cycle. Turn outdoor circuit breaker on after completing cooling cycle.

CLEANING HEAT EXCHANGER

The following steps should be performed by a qualified service agency:

NOTE: If the heat exchangers get a heavy accumulation of soot and carbon, they should be replaced rather than trying to clean them thoroughly. A heavy build-up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, incorrect size or damaged manifold orifice( s), improper gas, or a restricted heat exchanger. Action must be taken to correct the problem.

If it becomes necessary to clean the heat exchangers because of dust or corrosion, proceed as follows:

1.Turn OFF gas and electrical power to furnace.

2.Remove outer access door.

3.Disconnect vent connector from furnace vent elbow.

4.For downflow or horizontal furnace having an internal vent pipe, remove internal vent pipe within the casing.

5.Disconnect wires to the following components. Mark wires to aid in reconnection of (be careful when discon- necting wires from switches because damage may occur):

a.Draft safeguard switch.

b.Inducer motor.

c.Pressure switch(es).

d.Limit overtemperature switch.

e.Gas valve.

f.Hot surface igniter.

g.Flame-sensing electrode.

h.Flame rollout switches.

i.Remove NOx baffles on low NOx models.

6.Remove screws that fasten the collector box assembly to the cell panel. Be careful not to damage the collector box.

Inducer assembly and elbow need not be removed from collector box.

7.Disconnect gas line from gas manifold.

8.Remove the 5 screws that attach the burner assembly to the cell panel. The gas valve and individual burners need not be removed from support assembly.

NOTE: Be very careful when removing burner assembly to avoid breaking igniter. See Fig. 46 and 47 for correct igniter location.

9.Using field-provided 25-caliber rifle cleaning brush, 36-in. (914 mm) long, 1/4 in. (6 mm) diameter steel spring cable, a variable speed, reversible electric drill, and vacuum cleaner, clean cells as follows:

a.Remove metal screw fitting from wire brush to allow insertion into cable.

b.Insert the twisted wire end of brush into end of spring cable, and crimp tight with crimping tool or crimp by striking with ball-peen hammer. TIGHTNESS IS VERY IMPORTANT.

NOTE: The materials needed in item 9 can usually be purchased at local hardware stores.

(1)Attach variable-speed, reversible drill to the end of spring cable (end opposite brush).

(2)Insert brush end of cable into the outlet opening of cell and slowly rotate with drill. DO NOT force cable. Gradually insert cable into upper pass of cell. (See Fig. 48.)

(3)Work cable in and out of cell 3 or 4 times to obtain sufficient cleaning. DO NOT pull cable with great force. Reverse drill and gradually work cable out.

A05025

Fig. 46 ---Igniter Position-Side View

46

Image 46
Contents 310AAV/JAV Furnace Reliability Hazard Safety ConsiderationsCUT Hazard Inlet Width Size 20/060155Introduction SafetyCodes and Standards Electrostatic Discharge ESD Precautions Procedure LocationMultipoise Orientations Fire and Explosion HazardFire Hazard AIR for Combustion VentilationPersonal Injury AND/OR Property Damage Hazard Location Relative to Cooling EquipmentCarbon Monoxide Poisoning Hazard Outdoor Combustion Air MethodOther than FAN-ASSISTED Total Bottom Return Air Inlet InstallationUpflow Installation Side Return Air InletDownflow Installation Leveling Legs Leveling Legs If DesiredRoll-Out Protection Suspended Furnace SupportPlatform Furnace Support Filter Arrangement Carbon Monoxide and Poisoning HazardGeneral Requirements Opening Dimensions In. mmAIR Ducts Ductwork Acoustical Treatment Supply Air ConnectionsFurnace RETURN---AIR Speed Air Delivery CFM with FilterSize Inlet ⎯ Air Delivery CFM with Filter FurnaceHorizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions Maximum Capacity of Pipe Return Air ConnectionsGAS Piping Fire or Explosion Hazard Furnace Overheat HazardBurner and Manifold Electrical Connections Electrical Shock HazardFurnace MAY not Operate WiringElectrical Shock and Fire Hazard BOX RelocationBX Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXElectrical Data Furnace Control Venting AccessoriesGeneral Venting Requirements Masonry Chimney Requirements Chimney Inspection Chart Burn Hazard Appliance Application RequirementsAdditional Venting Requirements Sidewall VentingInternal Area of Chimney Vent HeightUpflow Application-Vent Elbow Up Diameter Height Orientation Input BTUH/HRDownflow Application-Vent Elbow Up then Left Horizontal Right Application-Vent Elbow Right Adjustments START-UP, ADJUSTMENT, and Safety CheckStart-Up Procedures GeneralFurnace Damage Hazard Never Assume Orifice SIZE. Always Check and VerifySpeed Selection Furnace Overheating HazardWiring Diagram Gas Control Valve Orifice Hole Check Safety Controls ChecklistFilter Size Information In. / mm Gas Rate cu ft./hrSeconds for Size of Test Dial Revolution Specific Gravity of Natural GAS Altitude Range BTU/CU FTSpecific Gravity of Natural GAS Altitude Range Heat Value AT Altitude Specific Gravity of Natural GAS AltitudeService and Maintenance Procedures IntroductionCleaning AND/OR Replacing AIR Filter Care and MaintenanceCarbon Monoxide Poisoning and Fire Hazard Blower Motor and Wheel Electrical Shock Hazard Media cabinet filter proceduresUnit Damage Hazard Cleaning Heat Exchanger Igniter Position-Side ViewSequence of Operation HeatingCooling Mode Wiring DiagramsTroubleshooting Continuous Blower ModeTroubleshooting Guide Chimneyin KitAdapter VentBlocked usedswitch Accessory List Description Part NumberParts Replacement Information Guide
Related manuals
Manual 45 pages 34.04 Kb

310AAV specifications

The Bryant 310AAV and 310JAV are high-efficiency air conditioning and heating systems designed for residential and light commercial applications. These models embody Bryant's commitment to delivering reliable comfort solutions while prioritizing energy efficiency and performance.

One of the standout features of the Bryant 310AAV and 310JAV is their impressive Seasonal Energy Efficiency Ratio (SEER) ratings. The higher the SEER, the more efficient the unit is in using electricity to cool your space. The Bryant 310AAV boasts a SEER rating of up to 16, while the 310JAV offers a slightly lower rating. This efficiency translates into cost savings on monthly energy bills while ensuring indoor comfort throughout the year.

Both models utilize advanced technologies, including two-stage heating and cooling capabilities. This means that the systems can adjust their operation based on the heating or cooling needs of a space, providing optimal temperature control while reducing energy waste. The two-stage operation also contributes to quieter operation levels, making these units suitable for residential settings where noise is a concern.

The 310AAV and 310JAV are equipped with variable-speed compressors, which further enhance their efficiency and comfort levels. The variable-speed technology allows the system to operate at different speeds, ensuring consistent temperature management and reducing the frequency of on-and-off cycling. This leads to steadier indoor temperatures and improved humidity control.

In addition to their performance features, Bryant places a strong emphasis on durability and dependability. The units are constructed with high-quality materials that are designed to withstand various environmental conditions. Features such as a weather-resistant cabinet and an efficient coil design help protect the units from wear and tear, ensuring long-lasting performance.

The implementation of environmentally friendly refrigerant options is another characteristic that demonstrates Bryant's commitment to sustainability. Both the 310AAV and 310JAV utilize R-410A refrigerant, which has a lower environmental impact compared to older refrigerants, aligning with modern standards for eco-friendly HVAC systems.

Overall, the Bryant 310AAV and 310JAV represent a blend of efficiency, advanced technology, and durability. With their attractive SEER ratings, two-stage operation, variable-speed capabilities, and commitment to sustainability, these models stand out as excellent choices for homeowners and businesses looking to enhance their heating and cooling solutions while keeping energy consumption in check. Whether for residential comfort or light commercial use, these Bryant units promise reliability and performance for years to come.