Bryant 310AAV Furnace Damage Hazard, Never Assume Orifice SIZE. Always Check and Verify

Page 33

!CAUTION

FURNACE DAMAGE HAZARD

Failure to follow this caution may result in reduced furnace life.

DO NOT redrill orifices. Improper drilling (burrs, out-of round holes, etc.) can cause excessive burner noise and misdirection of burner flames. This can result in flame impingement of heat exchangers, causing failures. (See Fig. 43.)

Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft. (610 M). Furnace input rate must be within +/-2 percent of furnace rating plate input.

1.Determine the correct gas input rate.

The input rating for altitudes above 2,000 ft. (610 M) must be reduced by 4 percent for each 1,000 ft. (305 M) above sea level. For installations below 2000 ft., refer to the unit rating plate. For installations above 2000 ft. (610 M), mul- tiply the input on the rating plate by the derate multiplier in Table 11 for the correct input rate.

2.Determine the correct orifice and manifold pressure adjust- ment. There are two different orifice and manifold adjust- ment tables. All models in all positions, except Low NOx models in downflow or horizontal positions, use Table 15 (22,000 Btuh/Burner).

Low NOx models in the downflow or horizontal positions must use Table 16 (21,000 Btuh/Burner). See input listed on rating plate.

a.Obtain average yearly gas heat value (at installed alti- tude) from local gas supplier.

b.Obtain average yearly gas specific gravity from local gas supplier.

c.Find installation altitude in Table 15 or 16.

d.Find closest natural gas heat value and specific gravity in Table 15 or 16.

e.Follow heat value and specific gravity lines to point of intersection to find orifice size and manifold pressure settings for proper operation.

f.Check and verify burner orifice size in furnace.

NEVER ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY.

g.Replace orifice with correct size if required by Table 15 or 16. Use only factory-supplied orifices. See EXAMPLE 2.

EXAMPLE 2: (0-2000 ft. (0-610 M) altitude)

For 22,000 Btuh per burner application use Table 15. Heating value = 1000 Btuh/cu ft.

Specific gravity = 0.62 Therefore: Orifice No. 43* Manifold pressure: 3.7-In. W.C.

*Furnace is shipped with No. 43 orifices. In this example all main burner orifices are the correct size and do not need to be changed to obtain proper input rate.

3.Adjust manifold pressure to obtain correct input rate.

a.Turn gas valve ON/OFF switch to OFF.

b.Remove manifold pressure tap plug from gas valve. (See Fig. 42.)

c.Connect a water column manometer or similar device to manifold pressure tap.

d.Turn gas valve ON/OFF switch to ON.

e.Manually close blower door switch.

f.Set thermostat to call for heat.

g.Jumper R and W thermostat connections on furnace control board to start furnace.

h.Remove regulator seal cap and turn regulator adjusting screw counterclockwise (out) to decrease input rate of clockwise (in) to increase input rate.

i.Install regulator seal cap.

j.Leave manometer or similar device connected and proceed to Step 4.

NOTE: DO NOT set manifold pressure less than 3.2-In. W.C. or more than 3.8-In. W.C. for natural gas at sea level. If manifold pressure is outside this range, change main burner orifices or refer Table 15 or 16.

NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics.

4. Verify natural gas input rate by clocking meter.

NOTE: Gas valve regulator adjustment cap must be in place for proper input to be clocked.

a.Turn off all other gas appliances and pilots served by the meter.

b.Run furnace for 3 minutes in heating operation.

c.Measure time (in sec) for gas meter to complete 1 re- volution and note reading. The 2 or 5 cubic feet dial provides a more accurate measurement of gas flow.

d.Refer to Table 13 for cubic ft. of gas per hr.

e.Multiply gas rate (cu ft./hr) by heating value (Btu/cu ft.) to obtain input.

If clocked rate does not match required input from Step 1, increase manifold pressure to increase input or decrease manifold pressure to decrease input. Repeat steps b through e until correct input is achieved. Reinstall regulator seal cap on gas valve.

5.Set temperature rise. The furnace must operate within the temperature rise ranges specified on the furnace rating plate. Do not exceed temperature rise range specified on unit rating plate. Determine the temperature rise as fol- lows:

NOTE: Blower access door must be installed when taking temperature rise reading. Leaving blower access door off will result in incorrect temperature measurements.

a.Place thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see radiant heat from heat exchangers. Radiant heat affects temperature rise readings. This practice is par- ticularly important with straight-run ducts.

b.When thermometer readings stabilize, subtract return- air temperature from supply-air temperature to determ- ine air temperature rise.

NOTE: Blower access door must be installed for proper temperature rise measurement.

NOTE: If the temperature rise is outside this range, first check:

SGas input for heating operation. S Derate for altitude if applicable.

SReturn and supply ducts for excessive restrictions caus- ing static pressures greater than 0.50-In. W.C.

SDirty filter.

310AAV

33

Image 33
Contents 310AAV/JAV Safety Considerations Furnace Reliability HazardCUT Hazard 20/060155 Inlet Width SizeSafety IntroductionCodes and Standards Location Electrostatic Discharge ESD Precautions ProcedureFire and Explosion Hazard Multipoise OrientationsPersonal Injury AND/OR Property Damage Hazard AIR for Combustion VentilationFire Hazard Location Relative to Cooling EquipmentOutdoor Combustion Air Method Carbon Monoxide Poisoning HazardOther than FAN-ASSISTED Total Upflow Installation InstallationBottom Return Air Inlet Side Return Air InletLeveling Legs Leveling Legs If Desired Downflow InstallationPlatform Furnace Support Suspended Furnace SupportRoll-Out Protection Filter Arrangement Carbon Monoxide and Poisoning HazardAIR Ducts Opening Dimensions In. mmGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsAir Delivery CFM with Filter Furnace RETURN---AIR SpeedSize Inlet Furnace ⎯ Air Delivery CFM with FilterHorizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions GAS Piping Fire or Explosion Hazard Return Air ConnectionsMaximum Capacity of Pipe Furnace Overheat HazardElectrical Connections Electrical Shock Hazard Burner and ManifoldElectrical Shock and Fire Hazard WiringFurnace MAY not Operate BOX RelocationPower Cord Installation in Furnace J-BOX BX Cable Installation in Furnace J-BOXElectrical Data Furnace Control Accessories VentingGeneral Venting Requirements Masonry Chimney Requirements Chimney Inspection Chart Additional Venting Requirements Appliance Application RequirementsBurn Hazard Sidewall VentingVent Height Internal Area of ChimneyDiameter Height Orientation Input BTUH/HR Upflow Application-Vent Elbow UpDownflow Application-Vent Elbow Up then Left Horizontal Right Application-Vent Elbow Right Start-Up Procedures START-UP, ADJUSTMENT, and Safety CheckAdjustments GeneralNever Assume Orifice SIZE. Always Check and Verify Furnace Damage HazardFurnace Overheating Hazard Speed SelectionWiring Diagram Gas Control Valve Orifice Hole Checklist Check Safety ControlsGas Rate cu ft./hr Filter Size Information In. / mmSeconds for Size of Test Dial Revolution BTU/CU FT Specific Gravity of Natural GAS Altitude RangeSpecific Gravity of Natural GAS Altitude Range Heat Value AT Altitude Altitude Specific Gravity of Natural GASIntroduction Service and Maintenance ProceduresCare and Maintenance Cleaning AND/OR Replacing AIR FilterCarbon Monoxide Poisoning and Fire Hazard Media cabinet filter procedures Blower Motor and Wheel Electrical Shock HazardUnit Damage Hazard Igniter Position-Side View Cleaning Heat ExchangerHeating Sequence of OperationTroubleshooting Wiring DiagramsCooling Mode Continuous Blower ModeTroubleshooting Guide Chimneyin KitAdapter VentBlocked usedswitch Description Part Number Accessory ListParts Replacement Information Guide
Related manuals
Manual 45 pages 34.04 Kb

310AAV specifications

The Bryant 310AAV and 310JAV are high-efficiency air conditioning and heating systems designed for residential and light commercial applications. These models embody Bryant's commitment to delivering reliable comfort solutions while prioritizing energy efficiency and performance.

One of the standout features of the Bryant 310AAV and 310JAV is their impressive Seasonal Energy Efficiency Ratio (SEER) ratings. The higher the SEER, the more efficient the unit is in using electricity to cool your space. The Bryant 310AAV boasts a SEER rating of up to 16, while the 310JAV offers a slightly lower rating. This efficiency translates into cost savings on monthly energy bills while ensuring indoor comfort throughout the year.

Both models utilize advanced technologies, including two-stage heating and cooling capabilities. This means that the systems can adjust their operation based on the heating or cooling needs of a space, providing optimal temperature control while reducing energy waste. The two-stage operation also contributes to quieter operation levels, making these units suitable for residential settings where noise is a concern.

The 310AAV and 310JAV are equipped with variable-speed compressors, which further enhance their efficiency and comfort levels. The variable-speed technology allows the system to operate at different speeds, ensuring consistent temperature management and reducing the frequency of on-and-off cycling. This leads to steadier indoor temperatures and improved humidity control.

In addition to their performance features, Bryant places a strong emphasis on durability and dependability. The units are constructed with high-quality materials that are designed to withstand various environmental conditions. Features such as a weather-resistant cabinet and an efficient coil design help protect the units from wear and tear, ensuring long-lasting performance.

The implementation of environmentally friendly refrigerant options is another characteristic that demonstrates Bryant's commitment to sustainability. Both the 310AAV and 310JAV utilize R-410A refrigerant, which has a lower environmental impact compared to older refrigerants, aligning with modern standards for eco-friendly HVAC systems.

Overall, the Bryant 310AAV and 310JAV represent a blend of efficiency, advanced technology, and durability. With their attractive SEER ratings, two-stage operation, variable-speed capabilities, and commitment to sustainability, these models stand out as excellent choices for homeowners and businesses looking to enhance their heating and cooling solutions while keeping energy consumption in check. Whether for residential comfort or light commercial use, these Bryant units promise reliability and performance for years to come.