Bryant 310AAV instruction manual Service and Maintenance Procedures, Introduction

Page 43

SERVICE

If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. On RED LED boards do not remove power or blower door before initiating status code recall. After

status code recall is completed component test will occur. LED CODE

STATUS

CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.

CONTINUOUS ON - Control has 24VAC power.

RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.

EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.

11NO PREVIOUS CODE - Stored status code is erased automatically after 72 hours. On

RED LED boards stored status codes can also be erased when power (115 VAC or 24 VAC) to control is interrupted.

12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed) or R-W opens during blower on-delay.

13LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit, draft safeguard, flame rollout, or

blocked vent switch (if used) is open longer than 3 minutes.

- Control will auto reset after three hours.

- Refer to #33.

14IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.

21GAS HEATING LOCKOUT - Control will NOT auto reset.

Check for: - Mis-wired gas valve

-Defective control (valve relay)

22ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de- energized. Inducer will run until fault is cleared. Check for: - Leaky gas valve - Stuck-open gas valve

23PRESSURE SWITCH DID NOT OPEN Check for:

- Obstructed pressure tubing.

- Pressure switch stuck closed.

24SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary voltage (24VAC) wiring.

COMPONENT TEST

To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor fan speed (on AMBER LED boards only) blower motor-heat speed, and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier will not be turned on.

327596-101 REV. B

Fig. 45 ---

31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes,

inducer shuts off for 15 minutes before retry. Check for: - Excessive wind

- Proper vent sizing

- Defective inducer motor

- Low inducer voltage (115VAC)

- Defective pressure switch

- Inadequate combustion air supply

- Disconnected or obstructed pressure tubing

- Low inlet gas pressure (if LGPS used)

- Restricted vent

If it opens during blower on-delay period, blower will come on for the selected blower off-delay.

33LIMIT CIRCUIT FAULT - Indicates a limit, draft safeguard, flame rollout, or blocked vent switch (if used) is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13.

If open less than 3 minutes status code #33 continues to flash until blower shuts off.

Flame rollout switch and BVSS require manual reset. Check for:

- Restricted vent

- Proper vent sizing

- Loose blower wheel.

- Excessive wind

-Dirty filter or restricted duct system.

-Defective blower motor or capacitor. - Defective switch or connections.

-Inadequate combustion air supply (Flame Roll-out Switch open).

34IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Flame sensor must not be grounded

-Oxide buildup on flame sensor (clean with fine steel wool).

-Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).

- Gas valve defective or gas valve turned off - Manual valve shut-off

- Defective Hot Surface Ignitor

- Control ground continuity

 

- Low inlet gas pressure

- Inadequate flame carryover or rough ignition

- Green/Yellow wire MUST be connected to furnace sheet metal

 

45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour

lockout due to;

- Gas valve relay stuck open

- Flame sense circuit failure

- Software check error

Reset power to clear lockout.

Replace control if status code repeats.

A04223

Service Label

310AAV

SERVICE AND MAINTENANCE

PROCEDURES

!WARNING

FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury, death and/or property damage.

The ability to properly perform maintenance on this equipment requires certain knowledge, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual.

!WARNING

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury or death, or property damage.

Before servicing, disconnect all electrical power and install lockout tag to furnace. Verify proper operation after servicing.

!CAUTION

ELECTRICAL OPERATION HAZARD

Failure to follow this caution may result in improper furnace operation.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

!CAUTION

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental pollution.

Remove and recycle all components or materials (i.e. oil, refrigerant, et.) before unit final disposal.

Step 1 Introduction

GENERAL

These instructions are written as if the furnace is installed in an upflow application. An upflow furnace application is where the blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Since this furnace can be installed in any of the 4 positions shown in Fig. 4, you must revise your orientation to component location accordingly.

ELECTRICAL CONTROLS AND WIRING

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position and install a lockout tag. There may be more than one electrical supply to the furnace. Check accessories and cooling unit for additional electrical supplies that must be shut off during furnace servicing. Lockout and tag switch with a suitable warning label. Verify proper operation after servicing.

The electrical ground and polarity for 115-v wiring must be properly maintained. Refer to Fig. 26 for field wiring information and to Fig. 41 for furnace wiring information.

NOTE: If the polarity is not correct, the STATUS LED on the control will flash rapidly and prevent the furnace from heating.

43

Image 43
Contents 310AAV/JAV Furnace Reliability Hazard Safety ConsiderationsCUT Hazard 20/060155 Inlet Width SizeIntroduction SafetyCodes and Standards Location Electrostatic Discharge ESD Precautions ProcedureFire and Explosion Hazard Multipoise OrientationsLocation Relative to Cooling Equipment AIR for Combustion VentilationPersonal Injury AND/OR Property Damage Hazard Fire HazardOutdoor Combustion Air Method Carbon Monoxide Poisoning HazardOther than FAN-ASSISTED Total Side Return Air Inlet InstallationUpflow Installation Bottom Return Air InletLeveling Legs Leveling Legs If Desired Downflow InstallationFilter Arrangement Carbon Monoxide and Poisoning Hazard Suspended Furnace SupportPlatform Furnace Support Roll-Out ProtectionDuctwork Acoustical Treatment Supply Air Connections Opening Dimensions In. mmAIR Ducts General RequirementsFurnace RETURN---AIR Speed Air Delivery CFM with FilterSize Inlet Furnace ⎯ Air Delivery CFM with FilterHorizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions Furnace Overheat Hazard Return Air ConnectionsGAS Piping Fire or Explosion Hazard Maximum Capacity of PipeElectrical Connections Electrical Shock Hazard Burner and ManifoldBOX Relocation WiringElectrical Shock and Fire Hazard Furnace MAY not OperateBX Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXElectrical Data Furnace Control Venting AccessoriesGeneral Venting Requirements Masonry Chimney Requirements Chimney Inspection Chart Sidewall Venting Appliance Application RequirementsAdditional Venting Requirements Burn HazardVent Height Internal Area of ChimneyDiameter Height Orientation Input BTUH/HR Upflow Application-Vent Elbow UpDownflow Application-Vent Elbow Up then Left Horizontal Right Application-Vent Elbow Right General START-UP, ADJUSTMENT, and Safety CheckStart-Up Procedures AdjustmentsNever Assume Orifice SIZE. Always Check and Verify Furnace Damage HazardFurnace Overheating Hazard Speed SelectionWiring Diagram Gas Control Valve Orifice Hole Checklist Check Safety ControlsFilter Size Information In. / mm Gas Rate cu ft./hrSeconds for Size of Test Dial Revolution BTU/CU FT Specific Gravity of Natural GAS Altitude RangeSpecific Gravity of Natural GAS Altitude Range Heat Value AT Altitude Altitude Specific Gravity of Natural GASIntroduction Service and Maintenance ProceduresCleaning AND/OR Replacing AIR Filter Care and MaintenanceCarbon Monoxide Poisoning and Fire Hazard Blower Motor and Wheel Electrical Shock Hazard Media cabinet filter proceduresUnit Damage Hazard Igniter Position-Side View Cleaning Heat ExchangerHeating Sequence of OperationContinuous Blower Mode Wiring DiagramsTroubleshooting Cooling ModeTroubleshooting Guide Chimneyin KitAdapter VentBlocked usedswitch Description Part Number Accessory ListParts Replacement Information Guide
Related manuals
Manual 45 pages 34.04 Kb

310AAV specifications

The Bryant 310AAV and 310JAV are high-efficiency air conditioning and heating systems designed for residential and light commercial applications. These models embody Bryant's commitment to delivering reliable comfort solutions while prioritizing energy efficiency and performance.

One of the standout features of the Bryant 310AAV and 310JAV is their impressive Seasonal Energy Efficiency Ratio (SEER) ratings. The higher the SEER, the more efficient the unit is in using electricity to cool your space. The Bryant 310AAV boasts a SEER rating of up to 16, while the 310JAV offers a slightly lower rating. This efficiency translates into cost savings on monthly energy bills while ensuring indoor comfort throughout the year.

Both models utilize advanced technologies, including two-stage heating and cooling capabilities. This means that the systems can adjust their operation based on the heating or cooling needs of a space, providing optimal temperature control while reducing energy waste. The two-stage operation also contributes to quieter operation levels, making these units suitable for residential settings where noise is a concern.

The 310AAV and 310JAV are equipped with variable-speed compressors, which further enhance their efficiency and comfort levels. The variable-speed technology allows the system to operate at different speeds, ensuring consistent temperature management and reducing the frequency of on-and-off cycling. This leads to steadier indoor temperatures and improved humidity control.

In addition to their performance features, Bryant places a strong emphasis on durability and dependability. The units are constructed with high-quality materials that are designed to withstand various environmental conditions. Features such as a weather-resistant cabinet and an efficient coil design help protect the units from wear and tear, ensuring long-lasting performance.

The implementation of environmentally friendly refrigerant options is another characteristic that demonstrates Bryant's commitment to sustainability. Both the 310AAV and 310JAV utilize R-410A refrigerant, which has a lower environmental impact compared to older refrigerants, aligning with modern standards for eco-friendly HVAC systems.

Overall, the Bryant 310AAV and 310JAV represent a blend of efficiency, advanced technology, and durability. With their attractive SEER ratings, two-stage operation, variable-speed capabilities, and commitment to sustainability, these models stand out as excellent choices for homeowners and businesses looking to enhance their heating and cooling solutions while keeping energy consumption in check. Whether for residential comfort or light commercial use, these Bryant units promise reliability and performance for years to come.