1.If a vent (common or dedicated) becomes blocked, the fur- nace will be shut off by the draft safeguard switch located on the vent elbow.
2.Do not connect this Category I furnace into a
3.Vent connectors serving Category I furnaces shall not be connected into any portion of a mechanical draft system operating under positive pressure.
4.Do not vent this appliance with any solid fuel burning ap- pliance.
5.Category I furnaces must be vented vertically or nearly vertically unless equipped with a listed power venter.
6.Do not vent this appliance into an unlined masonry chim- ney. Refer to Chimney Inspection Chart, Fig. 27.
MASONRY CHIMNEY REQUIREMENTS
NOTE: These furnaces are CSA
If a clay
NOTE: See the NFPA 54 / ANSI
13.2.20regarding alternative venting design and the Exception, which cover installations such as the Chimney Adapter Kits which are listed for use with these furnaces. The Chimney Adapter Kit is listed alternative venting system for these furnaces. See the kit instructions for complete details. See Table 17 for accessory list.
This furnace is permitted to be vented into a clay
1.Vent connector is
2.This furnace is common vented with at least 1 draft hood equipped appliance, and
3.The combined appliance input rating is less than the max- imum capacity given in Table 8 , and
4.The input rating of each space heating appliance is greater than the minimum input rating given in Table 9 for the local 99% Winter Design Temperature. Chimneys having internal areas greater than 38 in2 (24516 mm2) require fur- nace input ratings greater than the input ratings of these furnaces. See footnote at bottom of Table 9, and
5.The authority having jurisdiction approves.
If all of these conditions cannot be met, an alternative venting design shall be used, such as the listed chimney adapter kit with these furnaces, which are listed for use with the kit, a listed
Inspections before the sale and at the time of installation will determine the acceptability of the chimney or the need for repair and/or (re)lining. Refer to the Fig. 27 to perform a chimney inspection. If the inspection of a previously used
a.Shows signs of vent gas condensation, the chimney should be relined in accordance with local codes and the authority having jurisdiction. The chimney should be relined with a listed metal liner,
b.Indicates the chimney exceeds the maximum permiss- ible size in the tables, the chimney should be rebuilt or relined to conform to the requirements of the equip- ment being installed and the authority having jurisdic- tion.
A chimney without a clay tile liner, which is otherwise in good condition, shall be rebuilt to conform to ANSI/NFPA 211 or be lined with a UL listed metal liner or UL listed
If a metal liner or
310AAV
25