Trane TRG-TRC014-EN manual Morning Warm-up/Cool-down Mode

Page 56

period three

System Configurations

notes

Morning Warm-up/Cool-down Mode

Main supply fan operates continuously

Main supply fan controlled to maintain the system static-pressure set point

Outdoor air damper is closed, unless required for preoccupancy purge

Terminal units are either fully open or modulated to maintain their respective “occupied” space thermostat set points

Figure 70

The morning warm-up/cool-downmode typically occurs as a transition from the unoccupied mode to the occupied mode. It establishes the occupied comfort conditions for the building as rapidly as possible, because they were allowed to drift from occupied set point during the unoccupied mode, usually to save energy.

In this mode, the building does not initially require ventilation because it is not occupied, but it may eventually be provided for a preoccupancy purge (diluting the contaminants that accumulated during the unoccupied mode).

During the morning warm-up/cool-down mode, the system is controlled as follows:

nThe AHU fan operates continuously to provide primary air to the spaces for cooling or heating. If separate perimeter heat is installed and heat is demanded, the perimeter heat source operates and the AHU fan remains off.

nThe supply fan is controlled to maintain the static-pressure set point for the system.

nThe outdoor air damper is closed unless ventilation is needed for preoccupancy purge.

nThe terminal units may be fully open, allowing “wild” (uncontrolled) warm- up or cool-down, or they may modulate to achieve the occupied temperature set points for a “controlled” warm-up or cool-down.

Morning warm-up or cool-down mode is ended when the perimeter zone thermostats or a single, representative thermostat reaches its occupied set point. Then the system switches to the occupied mode.

TRG-TRC014-EN

51

Image 56
Contents Air Conditioning Clinic VAV Systems One of the Systems Series Publication of The Trane Company Preface VAV SystemsContents TRG-TRC014-EN What Is Variable Air Volume? Constant-Volume Variable-Temperature SystemConstant Volume-Full Load Constant Volume-Part Load Constant × Supply AirflowConstant Volume-Multiple Spaces FineTerminal Reheat System Variable-Air-Volume VAV System VAV-Full LoadReduced fan energy Reduced refrigeration energy Why VAV? Energy SavingsVAV-Part Load Why VAV? Comfort Dedicated terminal units Dedicated thermostatsSystem Comparison VAVVAV Building Characteristics Variable Thermal Load ProfilesIndependent Space Control Common Return Air PathComponents of a VAV System Components of a VAV SystemVAV Terminal Units VAV Terminal UnitsAir Heating coil Filter Mixing fan Single Duct, Cooling Only Primary air irSpace Heating with a VAV System VAV Reheat Primary airFan-Powered Terminal Units SeriesParallel, Fan-Powered Series, Fan-Powered Parallel Versus Series Fan-Powered Single-Duct VAV Systems Dual-Duct Variable Air Volume to the Space Cool Primary airConstant Air Volume to the Space Single-Fan, Dual-Duct VAV SystemTwo-Fan, Dual-Duct VAV System VAV Terminal Unit Controls VAV Terminal Unit ControlsUpstream Pressure Affects Airflow Pressure-Dependent Control Pressure-Independent ControlPrimary Airflow Measurement Terminal-Unit Control TechnologiesPneumatic Control Electronic Control Direct Digital Control DDC Components of a VAV System Diffusers DiffusersLinear Slot Diffuser EffectCeiling-Diffuser Compatibility Components of a VAV System Supply Duct System Supply Duct SystemStatic regain method Duct DesignEqual friction method Duct Design Recommendations System Configurations Perimeter P Versus InteriorPerimeter Spaces Perimeter SpacesBaseboard Perimeter Heating Overhead Supply Perimeter Heating Heat loss 250 Btu/hr/ft Fan-Powered VAV Dual-Duct VAVInterior Spaces Interior Spaces, Reheat RequiredSmall Buildings Changeover/Bypass VAV SystemOccupied mode Unoccupied mode Morning warm-up/cool-down mode System-Level Control ModesOccupied Mode Unoccupied Mode Morning Warm-up/Cool-down Mode Fan Performance Curve Fan ModulationFan Performance Curve System Resistance Curve System Resistance CurveOperating Point Riding the Fan CurveForward-Curved Centrifugal Fan Fan Modulation Curve Fan Modulation CurveFan Control Loop VAV Fan ModulationFan Modulation Methods Discharge DampersStatic pressure Discharge damper SP loss Inlet Vanes Fan-Speed Control 0 r p mVariable-Pitch Blade Control Fan Modulation Comparisons BI fan with Discharge DampersControlling System Static Pressure Fan Outlet Static-Pressure ControlSupply Duct Static-Pressure Control Sensor located Down supply ductOptimized Static-Pressure Control At fan outletPart-Load Comparison Application Considerations Period fiveSystem-Level Ventilation System-Level VentilationVentilation Reset Freeze Protection for Coils Freeze Protection for CoilsMeasures to Prevent Coil Freeze-Up Part-Load Space Humidity Control Part-Load Space Humidity ControlPart-Load Supply Air Tempering Building Pressure Control Building Pressure ControlDirect Pressurization Control Application Considerations Review Review-Period OneReview-Period Two Review-Period Three Review-Period FourReview-Period Five Trane Air Conditioning ManualReview Quiz Questions for PeriodQuiz TRG-TRC014-EN Answers Glossary Glossary Glossary Trane Company

TRG-TRC014-EN specifications

The Trane TRG-TRC014-EN is a comprehensive technical resource guide that serves as an essential tool for HVAC professionals and engineers looking to enhance their understanding of Trane's commercial HVAC systems. This guide provides an in-depth examination of Trane’s advanced technologies, key features, and design characteristics that position their products as industry leaders in heating, ventilation, and air conditioning.

One of the standout features of the TRG-TRC014-EN is its focus on energy efficiency. Trane continuously works on incorporating cutting-edge technologies that minimize energy consumption while maximizing performance. This includes the use of variable speed compressors and advanced control systems that adapt the HVAC operation according to real-time demand, significantly reducing energy costs for end users.

The guide also highlights Trane’s commitment to sustainable practices. The incorporation of environmentally friendly refrigerants and compliance with regulatory standards ensures that Trane units not only deliver comfort but also contribute to lower environmental impact. The guide provides detailed specifications on these refrigerants, allowing engineers to make informed decisions in line with environmental policies.

Another important aspect of the TRG-TRC014-EN is its technical information regarding system design and application. With comprehensive data on airflow, capacity calculations, and installation techniques, the guide serves as a valuable resource in the design phase of HVAC projects. This ensures that systems are optimized for performance and meet the specific needs of any given commercial space.

Additionally, the TRG-TRC014-EN addresses integration with smart building technologies. Trane units are designed to easily integrate with building management systems (BMS), enabling better monitoring and control of HVAC operations. This compatibility enhances operational efficiency and supports predictive maintenance, reducing downtime and servicing costs.

Moreover, the guide emphasizes Trane’s extensive warranty and service support. Understanding that customer satisfaction extends beyond the sale, Trane provides comprehensive service options that assure users of reliable and prompt support throughout the lifecycle of their HVAC systems.

In conclusion, the Trane TRG-TRC014-EN stands as an essential guide for HVAC professionals seeking to leverage Trane’s innovative technologies and design features. With a strong emphasis on energy efficiency, sustainability, technical accuracy, smart integration, and robust support, this guide underscores Trane's position as a leader in the HVAC industry.