Trane TRG-TRC014-EN manual Part-Load Space Humidity Control

Page 77

period five

Application Considerations

notes

Coils can be protected from freezing in many ways, such as:

nDraining the coils during cold weather

nKeeping the water in motion

nAdding glycol to the water

nUsing face-and-bypass dampers to limit the amount of cold airflow through the coil

nPreheating the outdoor air with either a conventional heating coil or heat recovered from the exhaust air stream

Part-Load Space Humidity Control

part-load space conditions CV system = 75°F, 66% RH

[23.9°C]

VAV system = 75°F, 58% RH

[23.9°C]

 

D

mixed air

A

C

B

 

55°F

60°F

75°F

[12.8°C]

[15.6°C]

[23.9°C]

dry-bulb temperature

humidity ratio

Figure 100

Part-Load Space Humidity Control

VAV systems do a good job of “indirectly” controlling space relative humidity (RH) at full-and part-load conditions. A typical VAV system supplies air at a constant, low dew-point temperature at all load conditions.

In this example, both the constant-volume and variable-volume systems deliver the same quantity and temperature (A = 55°F [12.8°C]) of air to the space at design load conditions. However, at part load the VAV system still supplies 55°F [12.8°C] air to the space. This results in a lower space relative humidity

(B verses D) than the constant-volume system that modulates the coil capacity and supplies warmer (C = 60°F [15.6°C]) air at the same part-load condition. Realize that adding reheat to this constant-volume system will improve its ability to control space relative humidity, but will also cause it to use more energy.

This demonstrates the danger of using primary air temperature reset on VAV systems! Increasing the primary air temperature on a VAV system will save some cooling energy, but will require more fan energy and will result in higher space relative humidity levels. ASHRAE Standard 62–1999 recommends that the space relative humidity not exceed 60%. If temperature reset is used, it should be allowed to be overridden by a space relative-humidity sensor.

72

TRG-TRC014-EN

Image 77
Contents Air Conditioning Clinic VAV Systems One of the Systems Series Publication of The Trane Company VAV Systems PrefaceContents TRG-TRC014-EN Constant-Volume Variable-Temperature System What Is Variable Air Volume?Constant Volume-Full Load Constant × Supply Airflow Constant Volume-Part LoadFine Constant Volume-Multiple SpacesTerminal Reheat System VAV-Full Load Variable-Air-Volume VAV SystemReduced fan energy Reduced refrigeration energy Why VAV? Energy SavingsVAV-Part Load Dedicated terminal units Dedicated thermostats Why VAV? ComfortVAV System ComparisonVariable Thermal Load Profiles VAV Building CharacteristicsCommon Return Air Path Independent Space ControlComponents of a VAV System Components of a VAV SystemVAV Terminal Units VAV Terminal UnitsAir Heating coil Filter Mixing fan Primary air ir Single Duct, Cooling OnlySpace Heating with a VAV System Primary air VAV ReheatSeries Fan-Powered Terminal UnitsParallel, Fan-Powered Series, Fan-Powered Parallel Versus Series Fan-Powered Single-Duct VAV Systems Dual-Duct Cool Primary air Variable Air Volume to the SpaceSingle-Fan, Dual-Duct VAV System Constant Air Volume to the SpaceTwo-Fan, Dual-Duct VAV System VAV Terminal Unit Controls VAV Terminal Unit ControlsUpstream Pressure Affects Airflow Pressure-Independent Control Pressure-Dependent ControlTerminal-Unit Control Technologies Primary Airflow MeasurementPneumatic Control Electronic Control Direct Digital Control DDC Components of a VAV System Diffusers DiffusersEffect Linear Slot DiffuserCeiling-Diffuser Compatibility Components of a VAV System Supply Duct System Supply Duct SystemStatic regain method Duct DesignEqual friction method Duct Design Recommendations Perimeter P Versus Interior System ConfigurationsPerimeter Spaces Perimeter SpacesBaseboard Perimeter Heating Overhead Supply Perimeter Heating Heat loss 250 Btu/hr/ft Dual-Duct VAV Fan-Powered VAVInterior Spaces, Reheat Required Interior SpacesChangeover/Bypass VAV System Small BuildingsSystem-Level Control Modes Occupied mode Unoccupied mode Morning warm-up/cool-down modeOccupied Mode Unoccupied Mode Morning Warm-up/Cool-down Mode Fan Performance Curve Fan ModulationFan Performance Curve System Resistance Curve System Resistance CurveRiding the Fan Curve Operating PointForward-Curved Centrifugal Fan Fan Modulation Curve Fan Modulation CurveVAV Fan Modulation Fan Control LoopDischarge Dampers Fan Modulation MethodsStatic pressure Discharge damper SP loss Inlet Vanes 0 r p m Fan-Speed ControlVariable-Pitch Blade Control BI fan with Discharge Dampers Fan Modulation ComparisonsFan Outlet Static-Pressure Control Controlling System Static PressureSensor located Down supply duct Supply Duct Static-Pressure ControlAt fan outlet Optimized Static-Pressure ControlPart-Load Comparison Period five Application ConsiderationsSystem-Level Ventilation System-Level VentilationVentilation Reset Freeze Protection for Coils Freeze Protection for CoilsMeasures to Prevent Coil Freeze-Up Part-Load Space Humidity Control Part-Load Space Humidity ControlPart-Load Supply Air Tempering Building Pressure Control Building Pressure ControlDirect Pressurization Control Application Considerations Review-Period One ReviewReview-Period Two Review-Period Four Review-Period ThreeTrane Air Conditioning Manual Review-Period FiveReview Questions for Period QuizQuiz TRG-TRC014-EN Answers Glossary Glossary Glossary Trane Company

TRG-TRC014-EN specifications

The Trane TRG-TRC014-EN is a comprehensive technical resource guide that serves as an essential tool for HVAC professionals and engineers looking to enhance their understanding of Trane's commercial HVAC systems. This guide provides an in-depth examination of Trane’s advanced technologies, key features, and design characteristics that position their products as industry leaders in heating, ventilation, and air conditioning.

One of the standout features of the TRG-TRC014-EN is its focus on energy efficiency. Trane continuously works on incorporating cutting-edge technologies that minimize energy consumption while maximizing performance. This includes the use of variable speed compressors and advanced control systems that adapt the HVAC operation according to real-time demand, significantly reducing energy costs for end users.

The guide also highlights Trane’s commitment to sustainable practices. The incorporation of environmentally friendly refrigerants and compliance with regulatory standards ensures that Trane units not only deliver comfort but also contribute to lower environmental impact. The guide provides detailed specifications on these refrigerants, allowing engineers to make informed decisions in line with environmental policies.

Another important aspect of the TRG-TRC014-EN is its technical information regarding system design and application. With comprehensive data on airflow, capacity calculations, and installation techniques, the guide serves as a valuable resource in the design phase of HVAC projects. This ensures that systems are optimized for performance and meet the specific needs of any given commercial space.

Additionally, the TRG-TRC014-EN addresses integration with smart building technologies. Trane units are designed to easily integrate with building management systems (BMS), enabling better monitoring and control of HVAC operations. This compatibility enhances operational efficiency and supports predictive maintenance, reducing downtime and servicing costs.

Moreover, the guide emphasizes Trane’s extensive warranty and service support. Understanding that customer satisfaction extends beyond the sale, Trane provides comprehensive service options that assure users of reliable and prompt support throughout the lifecycle of their HVAC systems.

In conclusion, the Trane TRG-TRC014-EN stands as an essential guide for HVAC professionals seeking to leverage Trane’s innovative technologies and design features. With a strong emphasis on energy efficiency, sustainability, technical accuracy, smart integration, and robust support, this guide underscores Trane's position as a leader in the HVAC industry.