Trane RT-PRC010-EN manual Table ED-6 -Voltage Utilization Range, 48.5 39.0 Motor Hp, Fla, 517-633

Page 85

Electrical Data

Table ED-2— 20-130Tons Electrical Service Sizing Data — Motors

 

 

 

Nominal Voltage

 

 

 

200

230

460

575

 

 

FLA

FLA

FLA

FLA

Nominal Tons

 

Condenser Fan Motors

 

20

 

8.2

8.2

3.6

2.8

25

 

12.3

12.3

5.4

4.2

30

 

12.3

12.3

5.4

4.2

40

 

16.4

16.4

7.2

5.6

50

 

24.6

24.6

10.8

8.4

55

 

24.6

24.6

10.8

8.4

60

 

24.6

24.6

10.8

8.4

70

 

24.6

24.6

10.8

8.4

75

 

24.6

24.6

10.8

8.4

90

 

32.8

32.8

14.4

11.2

105

 

41.0

41.0

18.0

14.0

115

 

41.0

41.0

18.0

14.0

130

 

49.2

49.2

21.6

16.8

Motor Horsepower

 

Supply Fan Motors

 

3

 

11.2

8.8

4.4

3.8

5

 

15.2

13.4

6.6

5.3

71/2

 

22.3

19.6

9.8

7.8

10

 

29.7

26.4

13.2

10.3

15

 

44.4

38.6

19.3

15.4

20

 

58.7

51.0

25.5

20.4

25

 

70.5

61.0

30.5

24.5

30

 

86.5

75.0

37.5

30.0

40

 

112.0

97.0

48.5

39.0

Motor Hp

 

Exhaust Fan Motor

 

11/2

 

5.0

4.4

2.2

1.8

3

 

11.2

8.8

4.4

3.8

5

 

15.2

13.4

6.6

5.3

71/2

 

22.3

19.6

9.8

7.8

10

 

29.7

26.4

13.2

10.3

15

 

44.4

38.6

19.3

15.4

20

 

58.7

51.0

25.5

20.4

25

 

70.5

61.0

30.5

24.5

30

 

86.5

75.0

37.5

30.0

40

 

112.0

97.0

48.5

39.0

Table ED-320-130Tons Electrical Service Sizing Data — Electric Heat Module (Electric Heat Units Only)

 

 

 

 

Voltage

 

 

 

200

230

460

575

Module KW

FLA

FLA

FLA

FLA

30

83.3

72.2

36.1

28.9

50

138.8

120.3

60.1

48.1

70

194.3

168.4

84.2

67.4

90

249.8

216.5

108.3

86.6

110

305.3

264.6

132.3

105.9

130

 

 

 

156.4

125.1

150

 

 

 

180.4

144.3

170

 

 

 

204.5

163.6

190

 

 

 

228.5

182.8

Note: Electric heat FLA are determined at 208, 240, 480 and 600 volts.

Table ED-420-130Tons Electrical Service Sizing Data — Control PowerTransformer — Heating and Cooling Modes

Nominal Tons

(Add) FLA

20-403

50-756

90-1308

Table ED-520-130Tons — Electrical Service Sizing Data —Crankcase Heaters — (Heating Mode on 460/575Volt Only)

Nominal Tons

(Add) FLA

20-30

1

40-60

2

70-105

3

115-130

4

Table ED-6 —Voltage Utilization Range

 

Voltage

Unit Voltage

Utilization Range

200/60/3

180-220

230/60/3

207-253

380/50/3

342-418

415/50/3

373-457

460/60/3

414-506

575/60/3

517-633

RT-PRC010-EN

85

Image 85
Contents 20 75Tons 90 130Tons American Standard Inc IntroductionContents Standard Features Features and BenefitsOptional Features Field Installed AccessoriesInstallation Ease Features SummaryEasy to Service ReliabilitySimplifyingThe Comfort System Integrated Comfort System ICSTracer control points for IntelliPak Rooftops FansWith Inlet GuideVanes Features and Benefits Optimum Building Comfort ControlVariable Frequency Drives VFD Trane 3-DScroll Compressor Proven DesignThroughTesting and ResearchSimple Design with 70% Fewer Parts LowTorqueVariationApplication Considerations Barometric Relief Dampers Percent Exhaust SystemHorizontal Discharge Panel C Dimensions20 75 tons SXHF, SFHF, SLHF, SSHF, SXHF, SFHF, SLHF, Sshf UnitsTable AC-5 SXHG, SLHG, Sshg Z Dimensions Table AC-4 SXHG, SLHG, Sshg Panel a and B Dimensions2508 17.4 Corrosive Atmospheres High Capacity Evaporator CoilVentilation Override Sequences Natural Gas Heating ConsiderationsClearance Requirements Acoustical ConsiderationsDuct Design Figure AC-4 Unit PlacementSelection Procedure Electric Heating System DetermineTotalWinter Heating LoadGas Heating System Natural Gas HotWater HeatingExhaust Fan Motor Sizing Supply Fan Motor SizingAltitude Corrections Selection Procedure H F C Model Number Description1 1 567 Table GD-1- General Data 20-40Tons General Data20Ton 25Ton 30Ton 40Ton RPMFilters Table GD-2 General Data 50-75Tons Low Ambient Option Min. Outside AirTemp 50Ton 55Ton 60Ton 70Ton 75Ton90Ton 105Ton 115Ton 130Ton Table GD-3 General Data 90-130Tons50% 100% Number/Size/Type 22/FC Table GD-5 ARI Correction Multipliers Table GD-4 ARI Performance DataEER Iplv Table PAF-1 Enthalpy of Saturated AIR Performance Adjustment FactorsPerformance 20Ton Data Performance 25Ton Data Performance 30Ton Data 345 452 265 496 183 Performance 40Ton Data561 207 451 399 493 302 537 199 429 389 468 292 431 551Performance 50Ton Data Performance 55Ton Data Performance 60Ton Data Performance 70Ton Data AmbientTemperature FFlow Performance 75Ton Data Performance 90Ton Data Performance 105Ton Data 115, 130Tons PerformanceTable PD-24 Natural Gas Heating Capacities Performance DataTable PD-25- Natural Gas Heating Capacities Table PD-26 Steam Heating Capacities Q/ITD1Table PD-29- 90To 130-Ton Electric Heat AirTemperature Rise Table PD-28 20 to 75-Tons Electric Heat AirTemperature RiseTable PD-30- Electric Heat KW Ranges Table PD-31- HotWater Heating Capacities Q/ITD1 RPM BHP 20, 25TonsPressure 1225 1271 4000 10371364 140910 HP 1200 RPM 80% 1100 RPM 22.22 6000 883 927 968 1007 1043 10781400 RPM Wocfm 40% 1300 RPM 25 HP Inches 1200 RPM 50% 20 HP 6000 890 933 974 1012 1049 Table PD-35 Supply Fan PerformanceWITH Inletvanes 30Ton1357 20.45 Ithout Exhaust Dual 18 X 18 Fans Wocfm Entrance Losses15 HP 1200 RPM Fan Curve Limits 1000 RPM 10 HP30.47 40, 50, 55Tons32.36 40, 50, 55Tons 1161 32.63 Cfm Total Static Pressure Std 250 500 750 000 800 14.86 820Inches w.c 43.85 60, 70, 75Tons60, 70, 75Tons 14000 729 800 RPM 20 HP 70% 15 HP 904 13.34 28000 667 710 750 791 826 10.15 857 27000 646 690 732 773 808 840 10.71 87230000 708 749 787 826 10.13 861 897 12.88 928 14.40 957 15.80 98529000 1375 42.04 1398 43.93 1423 45.91 1445 27000 1363 39.85 1388 41.68 1414 43.54 1437 45.26 14611469 49.80 1491 1515 53.66 30000 1382 43.16 1406 45.18 1428904 13.44 935 14.77 28000 718 756 791 825 10.28 858 27000 695 734 770 805 840891 12.90 922 14.26 952 15.65 29000 741 778 812 845 897 13.19 928 14.59 958 16.05 98732000 1442 49.55 1464 15791496 55.23 1518 57.33 1541 59.53 1565 37000 1494Performance 105,115,130Tons 00 R 1500 1623 76.74 1640 78.951100 100 900 RP26.95 25.3532.56 1233 34.40 1255 36.26 1277 38.17 46000 1138 26.67 30.40 1216 32.05 1240 33.79 1086 23.371641 79.40 1625 76.92 1643 79.30 46000 1624Table PD-44 Component Static Pressure Drops in.W.G Performance 20 -75Tons DataSFHF/G SEHF/G SLHF/G SSHF/G Table PD-45 Component Static Pressure Drops in.W.G Performance 90-130Tons DataSFHF/G SLHF/G SSHF/GTable PD-47 90-130 -Tons Supply Air Fan Drive Selections Table PD-46 20-75 -Tons Supply Air Fan Drive Selections835 39.71 859 BHP RPM885 44.08 910 46.33 934 48.32 Table PD-51 90-130Tons -100% Exhaust Fan Drive Selections Table PD-50 20-75Tons 100% Exhaust Fan Drive SelectionsTable PD-53 90-130 Tons 50% Exhaust Fan Performance Table PD-52 20-75Tons 50% Exhaust Fan Performance18.97 835 19.86 859 20.87 885 22.05 910 23.18 934 24.17 Table PD-54- 50% Exhaust Fan Drive Selections VAV Units ControlsVAV Units Only Reset based on outdoor air temperature Supply Air Setpoint ResetReset based on zone temperature ZoneTemperature Control Unoccupied Zone Heating and CoolingCV Units Only CV UnitsHeating Gas Heating -Two-Stage Gas Heating Modulating Gas Unoccupied ZoneTemperature Control Cooling and HeatingElectric Heating HotWater or Steam HeatingVAV/CV Units Purge sequence D Exhaust sequence CPurge with duct pressure control E Human Interface Panel H.IGeneric Building Automation System odule Gbas Human Interface Panel Main MenuEvaporator Coil Frost Protection Dry BulbTemperature Control of Economizer Occupied/Unoccupied SwitchingNight Setback Sensors Occupied/Unoccupied input on the RTMDual Source Power units 200V Electrical Service SizingElectrical Data Set 2. Rooftop units with Electric Heat178 21.8 143 RLA1 LRA48.5 39.0 Motor Hp Table ED-6 -Voltage Utilization Range48.5 39.0 FLADimensional 20 75Tons Detail B Covers 40, 60, 70 and 75 TON Units Figure DD-1 20-75Ton Cooling Only Unit Dimensions Sahf20 & 25 5-8 15/ 16 24-1 3 5/ 8 1-7 9 10’-1 7 ’-10 15/ 16 2’-0 ’-6 SahfFigure DD-5 90 130Tons Service Clearance Dimensional 90 130TonsSection B-B RT-PRC010-EN Figure DD-6 90 130Ton Roof Curb DimensionsField Installed Sensors DimensionalConstant Integrated Comfort System Sensors CV and VAVTableW-1 -Approximate OperatingWeights Lbs./Kg WeightsSL/SS 14740 15380 15930 16080Options OptionsAgency Approval Ambient ControlMiscellaneous Options Roof Curb Electronic Zone SensorsGeneral Mechanical Specifications90 130Ton Units Supply Fan 20 75Ton UnitsControls Unit ControllerHigh efficiency throwaway option Permanent cleanable wire mesh optionPercent bag filter option Percent cartridge filter optionManual outside air option Outside Air GeneralPercent modulating economizer option Ultra low-leak economizer dampers optionHeating System AccessoriesFile Number PL-RT-S*HF/S*HG-20-130TONS-PRC0010-EN-10-2001 Literature Order NumberSupersedes RT-DS-8 05/98 Stocking Location Inland-LaCrosse

RT-PRC010-EN specifications

The Trane RT-PRC010-EN is a prominent model in the line of Trane's packaged rooftop units, designed to offer efficient heating, cooling, and ventilation for commercial applications. Renowned for its robust performance, this unit integrates advanced technologies and superior engineering to meet diverse environmental needs while ensuring energy efficiency and reliability.

One of the key features of the RT-PRC010-EN is its energy-efficient operation. The unit is equipped with variable-speed fans and scroll compressors, which allow for precise control over temperature and airflow. This adaptability not only enhances comfort but also contributes to significant energy savings. The inclusion of high-efficiency cooling coils further optimizes performance, making it an excellent choice for businesses looking to lower their operational costs.

The RT-PRC010-EN model integrates smart controls that allow for seamless integration into building management systems. These controls facilitate real-time monitoring and diagnostics, enabling facility managers to maintain optimum operational efficiency and promptly address any maintenance needs. This technology minimizes downtime and extends the lifecycle of the unit.

Moreover, the unit’s construction is targeted toward resilience and durability. Built with a corrosion-resistant cabinet and extensive insulation, the RT-PRC010-EN can withstand the rigors of various climates, making it suitable for installation across different geographical locations. Its compact design allows for easy installation on rooftops, maximizing space utilization in commercial buildings.

Another standout characteristic is the unit's versatility in application. The RT-PRC010-EN can be tailored to suit a wide range of commercial settings, including retail establishments, educational institutions, and healthcare facilities. Options for various indoor and outdoor configurations enhance its adaptability to specific operational requirements.

In conclusion, the Trane RT-PRC010-EN stands out as an energy-efficient, reliable, and versatile solution for commercial heating and cooling needs. Its advanced features, smart controls, and robust design make it an ideal choice for businesses looking to enhance comfort while minimizing energy expenditures and ensuring operational reliability. Whether dealing with extreme weather conditions or managing indoor air quality concerns, this rooftop unit provides a comprehensive solution tailored to modern commercial requirements.