Trane RT-PRC010-EN manual Table GD-4 ARI Performance Data, Table GD-5 ARI Correction Multipliers

Page 27

General Data

Table GD-3 — General Data — 90-130Tons Continued

 

90Ton

105Ton

115Ton

130Ton

Filters

 

 

 

 

Panel Filters

 

 

 

 

Number/Size (Inches)

25-24x24x2

25-24x24x2

25-24x24x2

25-24x24x2

Face Area (Ft2)

100.0

100.0

100.0

100.0

Bag Filters

3-12x24x19

3-12x24x19

3-12x24x19

3-12x24x19

Number/Size (Inches)

15-24x24x19

15-24x24x19

15-24x24x19

15-24x24x19

Cartridge Filters

3-12x24x12

3-12x24x12

3-12x24x12

3-12x24x12

 

15-24x24x12

15-24x24x12

15-24x24x12

15-24x24x12

Prefilters (For Bag & Cartridge)

3-20x24x2

3-20x24x2

3-20x24x2

3-20x24x2

Face Area (Ft2)

15-24x24x2

15-24x24x2

15-24x24x2

15-24x24x2

66.0

66.0

66.0

66.0

Standard Unit Min. Outside AirTemperature For Mechanical Cooling

 

 

Without Hot Gas Bypass

45 F

45 F

45 F

45 F

With Hot Gas Bypass

45 F

45 F

45 F

45 F

Notes:

1. For cfm values outside these ranges, refer to RT-EB-104.

2 Refer to Table PD-30 for availability of electric heat kw ranges by voltage.

3.90-130 Ton models are dual circuit.

4.Max cfm for 105 Ton std is 44,000.

5The firing rate of the unit can vary from 33% of the Heater Mbh up to the nameplate rating of the unit.

6.The firing rate of the unit can vary from pilot rate of 125,000 Btuh up to the nameplate rating of the unit.

Table GD-4 — ARI Performance Data 1

ARI Performance Data1

 

 

Capacity

 

 

Tons

Model3

(MBh)

EER

IPLV2

 

SAHFC2040A**A**A*****

220

9.5

12.8

 

SXHFC2040A**A**A*****

220

9.5

12.8

20

SFHFC204LA**A**A*****

220

9.4

12.7

 

SEHFC204*A**A**A*****

220

9.4

12.7

 

SLHFC204LA**A**A*****

220

9.4

12.6

 

SSHFC204LA**A**A*****

220

9.4

12.7

Notes:

1. This information is rated and tested in accordance with ARI Standard 360-93 for large unitary equipment up to 25 tons. These Trane products can be found in the current ARI Directory.

2. IPLV — Integrated Part Load Value

3. This information applies to units whose design sequence (Digit 10) is “A” or later.

Table GD-5 — ARI Correction Multipliers

 

Model

 

Multipliers (%)

 

Option Description

Digit

Designator

Capacity

EER

IPLV2

High Heat — Gas

9

H,J,P

100

100

100

High Heat — Steam

9

H

100

99

98

High Heat — Hot Water

9

H

100

99

99

Wire Mesh Filter

13

B

100

101

101

95% Bag filter

13

D

99

95

91

95% Cartridge Filter

13

E

99

95

92

100% Economizer

16

D

100

99

98

High Capacity Coil

21

G

114

109

107

High Efficiency Motor

21

L

100

101

101

Inlet Guide Vanes

17

3

100

99

99

VFD (60 Hz)

17

6-9

99

98

98

Table GD-6 — Economizer OutdoorAir Damper Leakage (Of Rated Airflow)

 

P Across Dampers (In. WC)

 

0.5 (In.)

1.0 (In.)

Standard “Low Leak”

1.5 %

2.5 %

Optional “Ultra Low Leak”

0.5 %

1.0 %

Note:

1.Above data based on tests completed in accordance with AMCA Standard 575 at AMCA Laboratories.

RT-PRC010-EN

27

Image 27
Contents 20 75Tons 90 130Tons American Standard Inc IntroductionContents Field Installed Accessories Features and BenefitsStandard Features Optional FeaturesReliability Features SummaryInstallation Ease Easy to ServiceIntegrated Comfort System ICS SimplifyingThe Comfort SystemTracer control points for IntelliPak Rooftops Features and Benefits Optimum Building Comfort Control FansWith Inlet GuideVanesVariable Frequency Drives VFD LowTorqueVariation Proven DesignThroughTesting and ResearchTrane 3-DScroll Compressor Simple Design with 70% Fewer PartsApplication Considerations Barometric Relief Dampers Percent Exhaust SystemSXHF, SFHF, SLHF, Sshf Units Panel C DimensionsHorizontal Discharge 20 75 tons SXHF, SFHF, SLHF, SSHF,Table AC-4 SXHG, SLHG, Sshg Panel a and B Dimensions Table AC-5 SXHG, SLHG, Sshg Z Dimensions2508 17.4 Natural Gas Heating Considerations High Capacity Evaporator CoilCorrosive Atmospheres Ventilation Override SequencesClearance Requirements Acoustical ConsiderationsDuct Design Figure AC-4 Unit PlacementSelection Procedure HotWater Heating DetermineTotalWinter Heating LoadElectric Heating System Gas Heating System Natural GasSupply Fan Motor Sizing Exhaust Fan Motor SizingAltitude Corrections Selection Procedure H F C Model Number Description1 1 567 RPM General DataTable GD-1- General Data 20-40Tons 20Ton 25Ton 30Ton 40TonFilters Table GD-2 General Data 50-75Tons Low Ambient Option Min. Outside AirTemp 50Ton 55Ton 60Ton 70Ton 75TonTable GD-3 General Data 90-130Tons 90Ton 105Ton 115Ton 130Ton50% 100% Number/Size/Type 22/FC Table GD-4 ARI Performance Data Table GD-5 ARI Correction MultipliersEER Iplv Table PAF-1 Enthalpy of Saturated AIR Performance Adjustment FactorsPerformance 20Ton Data Performance 25Ton Data Performance 30Ton Data 431 551 Performance 40Ton Data345 452 265 496 183 561 207 451 399 493 302 537 199 429 389 468 292Performance 50Ton Data Performance 55Ton Data Performance 60Ton Data AmbientTemperature F Performance 70Ton DataFlow Performance 75Ton Data Performance 90Ton Data Performance 105Ton Data 115, 130Tons PerformanceTable PD-26 Steam Heating Capacities Q/ITD1 Performance DataTable PD-24 Natural Gas Heating Capacities Table PD-25- Natural Gas Heating CapacitiesTable PD-28 20 to 75-Tons Electric Heat AirTemperature Rise Table PD-29- 90To 130-Ton Electric Heat AirTemperature RiseTable PD-30- Electric Heat KW Ranges Table PD-31- HotWater Heating Capacities Q/ITD1 RPM BHP 20, 25TonsPressure 1409 4000 10371225 1271 136410 HP 1200 RPM 80% 1100 RPM 22.22 6000 883 927 968 1007 1043 10781400 RPM Wocfm 40% 1300 RPM 25 HP Inches 1200 RPM 50% 20 HP Table PD-35 Supply Fan PerformanceWITH Inletvanes 30Ton 6000 890 933 974 1012 10491357 20.45 1000 RPM 10 HP Dual 18 X 18 Fans Wocfm Entrance LossesIthout Exhaust 15 HP 1200 RPM Fan Curve Limits40, 50, 55Tons 30.4732.36 40, 50, 55Tons 1161 32.63 Cfm Total Static Pressure Std 250 500 750 000 800 14.86 820Inches w.c 43.85 60, 70, 75Tons60, 70, 75Tons 14000 729 800 RPM 20 HP 70% 15 HP 897 12.88 928 14.40 957 15.80 985 27000 646 690 732 773 808 840 10.71 872904 13.34 28000 667 710 750 791 826 10.15 857 30000 708 749 787 826 10.13 8611515 53.66 30000 1382 43.16 1406 45.18 1428 27000 1363 39.85 1388 41.68 1414 43.54 1437 45.26 146129000 1375 42.04 1398 43.93 1423 45.91 1445 1469 49.80 1491897 13.19 928 14.59 958 16.05 987 27000 695 734 770 805 840904 13.44 935 14.77 28000 718 756 791 825 10.28 858 891 12.90 922 14.26 952 15.65 29000 741 778 812 84537000 1494 157932000 1442 49.55 1464 1496 55.23 1518 57.33 1541 59.53 1565Performance 105,115,130Tons 100 900 RP 1623 76.74 1640 78.9500 R 1500 110030.40 1216 32.05 1240 33.79 1086 23.37 25.3526.95 32.56 1233 34.40 1255 36.26 1277 38.17 46000 1138 26.671641 79.40 1625 76.92 1643 79.30 46000 1624Performance 20 -75Tons Data Table PD-44 Component Static Pressure Drops in.W.GSFHF/G SEHF/G SLHF/G SSHF/G SLHF/G SSHF/G Performance 90-130Tons DataTable PD-45 Component Static Pressure Drops in.W.G SFHF/GTable PD-47 90-130 -Tons Supply Air Fan Drive Selections Table PD-46 20-75 -Tons Supply Air Fan Drive SelectionsBHP RPM 835 39.71 859885 44.08 910 46.33 934 48.32 Table PD-51 90-130Tons -100% Exhaust Fan Drive Selections Table PD-50 20-75Tons 100% Exhaust Fan Drive SelectionsTable PD-52 20-75Tons 50% Exhaust Fan Performance Table PD-53 90-130 Tons 50% Exhaust Fan Performance18.97 835 19.86 859 20.87 885 22.05 910 23.18 934 24.17 Table PD-54- 50% Exhaust Fan Drive Selections Controls VAV UnitsVAV Units Only ZoneTemperature Control Unoccupied Zone Heating and Cooling Supply Air Setpoint ResetReset based on outdoor air temperature Reset based on zone temperatureCV Units CV Units OnlyHeating Gas Heating -Two-Stage HotWater or Steam Heating Unoccupied ZoneTemperature Control Cooling and HeatingGas Heating Modulating Gas Electric HeatingVAV/CV Units Human Interface Panel H.I Exhaust sequence CPurge sequence D Purge with duct pressure control EHuman Interface Panel Main Menu Generic Building Automation System odule GbasEvaporator Coil Frost Protection Occupied/Unoccupied input on the RTM Occupied/Unoccupied SwitchingDry BulbTemperature Control of Economizer Night Setback SensorsSet 2. Rooftop units with Electric Heat Electrical Service SizingDual Source Power units 200V Electrical Data178 21.8 143 RLA1 LRAFLA Table ED-6 -Voltage Utilization Range48.5 39.0 Motor Hp 48.5 39.0Dimensional 20 75Tons Detail B Covers 40, 60, 70 and 75 TON Units Figure DD-1 20-75Ton Cooling Only Unit Dimensions Sahf20 & 25 5-8 15/ 16 24-1 3 5/ 8 1-7 9 10’-1 7 ’-10 15/ 16 2’-0 ’-6 SahfFigure DD-5 90 130Tons Service Clearance Dimensional 90 130TonsSection B-B RT-PRC010-EN Figure DD-6 90 130Ton Roof Curb DimensionsField Installed Sensors DimensionalConstant Integrated Comfort System Sensors CV and VAV14740 15380 15930 16080 WeightsTableW-1 -Approximate OperatingWeights Lbs./Kg SL/SSOptions OptionsAmbient Control Agency ApprovalMiscellaneous Options Roof Curb Electronic Zone SensorsGeneral Mechanical SpecificationsUnit Controller Supply Fan 20 75Ton Units90 130Ton Units ControlsPercent cartridge filter option Permanent cleanable wire mesh optionHigh efficiency throwaway option Percent bag filter optionUltra low-leak economizer dampers option Outside Air GeneralManual outside air option Percent modulating economizer optionHeating System AccessoriesLiterature Order Number File Number PL-RT-S*HF/S*HG-20-130TONS-PRC0010-EN-10-2001Supersedes RT-DS-8 05/98 Stocking Location Inland-LaCrosse

RT-PRC010-EN specifications

The Trane RT-PRC010-EN is a prominent model in the line of Trane's packaged rooftop units, designed to offer efficient heating, cooling, and ventilation for commercial applications. Renowned for its robust performance, this unit integrates advanced technologies and superior engineering to meet diverse environmental needs while ensuring energy efficiency and reliability.

One of the key features of the RT-PRC010-EN is its energy-efficient operation. The unit is equipped with variable-speed fans and scroll compressors, which allow for precise control over temperature and airflow. This adaptability not only enhances comfort but also contributes to significant energy savings. The inclusion of high-efficiency cooling coils further optimizes performance, making it an excellent choice for businesses looking to lower their operational costs.

The RT-PRC010-EN model integrates smart controls that allow for seamless integration into building management systems. These controls facilitate real-time monitoring and diagnostics, enabling facility managers to maintain optimum operational efficiency and promptly address any maintenance needs. This technology minimizes downtime and extends the lifecycle of the unit.

Moreover, the unit’s construction is targeted toward resilience and durability. Built with a corrosion-resistant cabinet and extensive insulation, the RT-PRC010-EN can withstand the rigors of various climates, making it suitable for installation across different geographical locations. Its compact design allows for easy installation on rooftops, maximizing space utilization in commercial buildings.

Another standout characteristic is the unit's versatility in application. The RT-PRC010-EN can be tailored to suit a wide range of commercial settings, including retail establishments, educational institutions, and healthcare facilities. Options for various indoor and outdoor configurations enhance its adaptability to specific operational requirements.

In conclusion, the Trane RT-PRC010-EN stands out as an energy-efficient, reliable, and versatile solution for commercial heating and cooling needs. Its advanced features, smart controls, and robust design make it an ideal choice for businesses looking to enhance comfort while minimizing energy expenditures and ensuring operational reliability. Whether dealing with extreme weather conditions or managing indoor air quality concerns, this rooftop unit provides a comprehensive solution tailored to modern commercial requirements.