Trane RT-PRC010-EN manual Occupied/Unoccupied Switching, Night Setback Sensors, TraneTracer System

Page 82

Controls

(VAV/CV Units)

 

 

 

 

near theTXV bulb location to shut the cooling off when coil frosting conditions occur.The supply fans are not shut off and will de-ice the coil.Timers prevent the compressors from rapid cycling.

7

Occupied/Unoccupied Switching

a

Description — 3 ways to switch Occupied/Unoccupied:

(1)NSB Panel

(2)Field-supplied contact closure (hardwired binary input to RTM)

(3)TRACER

Night Setback Sensors

Trane’s night setback sensors are programmable with a time clock function that provides communication to the rooftop unit through a 2-wire communications link.The desired transition times are programmed at the night setback sensor and communicated to the rooftop.

Night setback (unoccupied mode) is operated through the time clock provided in the sensors with night setback. When the time clock switches to night setback operation, the outdoor air dampers close and heating/cooling can be enabled or disabled depending on set-up parameters. As the building load changes, the night setback sensor energizes the rooftop heating/cooling (if enabled) function and the evaporator fan.The rooftop unit will cycle through the evening as heating/cooling (if enabled) is required in the space.When the time clock switches from night setback to occupied mode, all heating/ cooling functions begin normal operation.

When using the night setback options with a VAV heating/cooling rooftop, airflow must be maintained through the rooftop unit.This can be accomplished by electrically tying the VAV boxes to the Unoccupied output relay contacts on the Rooftop Module (RTM) or by using changeover thermostats. Either of these methods will assure adequate airflow through the unit and satisfactory temperature control of the building.

Occupied/Unoccupied input on the RTM

This input accepts a field supplied switch or contacts closure such as a time clock.

TraneTracer® System

TheTraneTracer System can control the Occupied/Unoccupied status of

the rooftop.

8

Timed Override Activation — ICS

This function is operational when the RTM is the zone temperature sensor source, which was set up at the Human Interface Panel. When this function is initiated by the push of a override button on the ICS sensor, theTracer will switch the unit to the Occupied mode. Unit operation (Occupied mode) during timed override is terminated by a signal from Tracer.

Timed Override Activation — Non-ICS

This function is active whenever the RTM is selected as the ZoneTemperature Sensor source, which was set up at the Human Interface Panel. When this function is initiated by the push of an override button on the zone sensor, the unit will switch to the Occupied mode. Automatic Cancellation of theTimed Override Mode occurs after three hours of operation.

9

Low Ambient Compressor Lockout

This function will lock out the compressor if the outdoor air temperature is below the low ambient compressor lock out temperature set point.The factory setpoint is 50 F on standard units and 0 F on low ambient units.This setpoint is adjustable at the Human Interface Panel. Compressors will be locked out when outdoor air temperatures falls below that selected temperature and will be allowed to start again when the temperature rises 5 F above the setpoint.

10

Comparative Enthalpy Control of Economizer

An optional Comparative Enthalpy system is used to control the operation of the economizer, and measures the temperature and humidity of both return

air and outside air to determine which source has lower enthalpy.This system allows true comparison of outdoor air and return air enthalpy by measurement of outdoor air and return air temperatures and humidities.

Reference Enthalpy Control of

Economizer

The optional reference enthalpy compares ambient temperature and humidity to the economizer enthalpy control setpoint. If ambient temperature and humidity are below the economizer enthalpy control setpoint the economizer will operate freely.This system provides more sophisticated control where outdoor air humidity levels may not be acceptable for building comfort and indoor air quality.

Dry BulbTemperature Control of Economizer

The optional dry bulb system measures ambient temperature comparing it to the economizer control temperature setpoint. If the ambient temperature is below the economizer dry bulb temperature control setpoint, the economizer will operate freely.This system is best suited for arid regions where the humidity levels of fresh air would not be detrimental to building comfort and indoor air quality.

11

Compressor Lead/Lag

Compressor lead/lag is a user-selectable feature through the Human Interface Panel available on all units. After each request for compressor operation, the lead refrigeration circuit or compressor on 20-30 tons units switches, thereby causing a more equitable or balanced run time among compressors.

12

Emergency Stop Input

A binary input is provided on the Rooftop Module (RTM) for installation of field provided switch or contacts for immediate shutdown of all unit functions.

82

RT-PRC010-EN

Image 82
Contents 20 75Tons 90 130Tons Introduction American Standard IncContents Optional Features Features and BenefitsStandard Features Field Installed AccessoriesEasy to Service Features SummaryInstallation Ease ReliabilitySimplifyingThe Comfort System Integrated Comfort System ICSTracer control points for IntelliPak Rooftops FansWith Inlet GuideVanes Features and Benefits Optimum Building Comfort ControlVariable Frequency Drives VFD Simple Design with 70% Fewer Parts Proven DesignThroughTesting and ResearchTrane 3-DScroll Compressor LowTorqueVariationApplication Considerations Percent Exhaust System Barometric Relief Dampers20 75 tons SXHF, SFHF, SLHF, SSHF, Panel C DimensionsHorizontal Discharge SXHF, SFHF, SLHF, Sshf UnitsTable AC-5 SXHG, SLHG, Sshg Z Dimensions Table AC-4 SXHG, SLHG, Sshg Panel a and B Dimensions2508 17.4 Ventilation Override Sequences High Capacity Evaporator CoilCorrosive Atmospheres Natural Gas Heating ConsiderationsAcoustical Considerations Clearance RequirementsFigure AC-4 Unit Placement Duct DesignSelection Procedure Gas Heating System Natural Gas DetermineTotalWinter Heating LoadElectric Heating System HotWater HeatingExhaust Fan Motor Sizing Supply Fan Motor SizingAltitude Corrections Selection Procedure Model Number Description H F C1 1 567 20Ton 25Ton 30Ton 40Ton General DataTable GD-1- General Data 20-40Tons RPMFilters Table GD-2 General Data 50-75Tons 50Ton 55Ton 60Ton 70Ton 75Ton Low Ambient Option Min. Outside AirTemp90Ton 105Ton 115Ton 130Ton Table GD-3 General Data 90-130Tons50% 100% Number/Size/Type 22/FC Table GD-5 ARI Correction Multipliers Table GD-4 ARI Performance DataEER Iplv Performance Adjustment Factors Table PAF-1 Enthalpy of Saturated AIRPerformance 20Ton Data Performance 25Ton Data Performance 30Ton Data 561 207 451 399 493 302 537 199 429 389 468 292 Performance 40Ton Data345 452 265 496 183 431 551Performance 50Ton Data Performance 55Ton Data Performance 60Ton Data Performance 70Ton Data AmbientTemperature FFlow Performance 75Ton Data Performance 90Ton Data Performance 105Ton Data Performance 115, 130TonsTable PD-25- Natural Gas Heating Capacities Performance DataTable PD-24 Natural Gas Heating Capacities Table PD-26 Steam Heating Capacities Q/ITD1Table PD-29- 90To 130-Ton Electric Heat AirTemperature Rise Table PD-28 20 to 75-Tons Electric Heat AirTemperature RiseTable PD-30- Electric Heat KW Ranges Table PD-31- HotWater Heating Capacities Q/ITD1 20, 25Tons RPM BHPPressure 1364 4000 10371225 1271 140910 HP 1200 RPM 80% 1100 RPM 6000 883 927 968 1007 1043 1078 22.221400 RPM Wocfm 40% 1300 RPM 25 HP Inches 1200 RPM 50% 20 HP 6000 890 933 974 1012 1049 Table PD-35 Supply Fan PerformanceWITH Inletvanes 30Ton1357 20.45 15 HP 1200 RPM Fan Curve Limits Dual 18 X 18 Fans Wocfm Entrance LossesIthout Exhaust 1000 RPM 10 HP30.47 40, 50, 55Tons32.36 40, 50, 55Tons 800 14.86 820 1161 32.63 Cfm Total Static Pressure Std 250 500 750 000Inches w.c 60, 70, 75Tons 43.8560, 70, 75Tons 14000 729 800 RPM 20 HP 70% 15 HP 30000 708 749 787 826 10.13 861 27000 646 690 732 773 808 840 10.71 872904 13.34 28000 667 710 750 791 826 10.15 857 897 12.88 928 14.40 957 15.80 9851469 49.80 1491 27000 1363 39.85 1388 41.68 1414 43.54 1437 45.26 146129000 1375 42.04 1398 43.93 1423 45.91 1445 1515 53.66 30000 1382 43.16 1406 45.18 1428891 12.90 922 14.26 952 15.65 29000 741 778 812 845 27000 695 734 770 805 840904 13.44 935 14.77 28000 718 756 791 825 10.28 858 897 13.19 928 14.59 958 16.05 9871496 55.23 1518 57.33 1541 59.53 1565 157932000 1442 49.55 1464 37000 1494Performance 105,115,130Tons 1100 1623 76.74 1640 78.9500 R 1500 100 900 RP32.56 1233 34.40 1255 36.26 1277 38.17 46000 1138 26.67 25.3526.95 30.40 1216 32.05 1240 33.79 1086 23.371625 76.92 1643 79.30 46000 1624 1641 79.40Table PD-44 Component Static Pressure Drops in.W.G Performance 20 -75Tons DataSFHF/G SEHF/G SLHF/G SSHF/G SFHF/G Performance 90-130Tons DataTable PD-45 Component Static Pressure Drops in.W.G SLHF/G SSHF/GTable PD-46 20-75 -Tons Supply Air Fan Drive Selections Table PD-47 90-130 -Tons Supply Air Fan Drive Selections835 39.71 859 BHP RPM885 44.08 910 46.33 934 48.32 Table PD-50 20-75Tons 100% Exhaust Fan Drive Selections Table PD-51 90-130Tons -100% Exhaust Fan Drive SelectionsTable PD-53 90-130 Tons 50% Exhaust Fan Performance Table PD-52 20-75Tons 50% Exhaust Fan Performance18.97 835 19.86 859 20.87 885 22.05 910 23.18 934 24.17 Table PD-54- 50% Exhaust Fan Drive Selections VAV Units ControlsVAV Units Only Reset based on zone temperature Supply Air Setpoint ResetReset based on outdoor air temperature ZoneTemperature Control Unoccupied Zone Heating and CoolingCV Units Only CV UnitsHeating Gas Heating -Two-Stage Electric Heating Unoccupied ZoneTemperature Control Cooling and HeatingGas Heating Modulating Gas HotWater or Steam HeatingVAV/CV Units Purge with duct pressure control E Exhaust sequence CPurge sequence D Human Interface Panel H.IGeneric Building Automation System odule Gbas Human Interface Panel Main MenuEvaporator Coil Frost Protection Night Setback Sensors Occupied/Unoccupied SwitchingDry BulbTemperature Control of Economizer Occupied/Unoccupied input on the RTMElectrical Data Electrical Service SizingDual Source Power units 200V Set 2. Rooftop units with Electric HeatRLA1 LRA 178 21.8 14348.5 39.0 Table ED-6 -Voltage Utilization Range48.5 39.0 Motor Hp FLADimensional 20 75Tons Figure DD-1 20-75Ton Cooling Only Unit Dimensions Sahf Detail B Covers 40, 60, 70 and 75 TON Units20 & 25 5-8 15/ 16 24-1 3 5/ 8 1-7 9 Sahf 10’-1 7 ’-10 15/ 16 2’-0 ’-6Dimensional 90 130Tons Figure DD-5 90 130Tons Service ClearanceFigure DD-6 90 130Ton Roof Curb Dimensions Section B-B RT-PRC010-ENDimensional Field Installed SensorsConstant CV and VAV Integrated Comfort System SensorsSL/SS WeightsTableW-1 -Approximate OperatingWeights Lbs./Kg 14740 15380 15930 16080Options OptionsAgency Approval Ambient ControlMiscellaneous Options Electronic Zone Sensors Roof CurbMechanical Specifications GeneralControls Supply Fan 20 75Ton Units90 130Ton Units Unit ControllerPercent bag filter option Permanent cleanable wire mesh optionHigh efficiency throwaway option Percent cartridge filter optionPercent modulating economizer option Outside Air GeneralManual outside air option Ultra low-leak economizer dampers optionAccessories Heating SystemFile Number PL-RT-S*HF/S*HG-20-130TONS-PRC0010-EN-10-2001 Literature Order NumberSupersedes RT-DS-8 05/98 Stocking Location Inland-LaCrosse

RT-PRC010-EN specifications

The Trane RT-PRC010-EN is a prominent model in the line of Trane's packaged rooftop units, designed to offer efficient heating, cooling, and ventilation for commercial applications. Renowned for its robust performance, this unit integrates advanced technologies and superior engineering to meet diverse environmental needs while ensuring energy efficiency and reliability.

One of the key features of the RT-PRC010-EN is its energy-efficient operation. The unit is equipped with variable-speed fans and scroll compressors, which allow for precise control over temperature and airflow. This adaptability not only enhances comfort but also contributes to significant energy savings. The inclusion of high-efficiency cooling coils further optimizes performance, making it an excellent choice for businesses looking to lower their operational costs.

The RT-PRC010-EN model integrates smart controls that allow for seamless integration into building management systems. These controls facilitate real-time monitoring and diagnostics, enabling facility managers to maintain optimum operational efficiency and promptly address any maintenance needs. This technology minimizes downtime and extends the lifecycle of the unit.

Moreover, the unit’s construction is targeted toward resilience and durability. Built with a corrosion-resistant cabinet and extensive insulation, the RT-PRC010-EN can withstand the rigors of various climates, making it suitable for installation across different geographical locations. Its compact design allows for easy installation on rooftops, maximizing space utilization in commercial buildings.

Another standout characteristic is the unit's versatility in application. The RT-PRC010-EN can be tailored to suit a wide range of commercial settings, including retail establishments, educational institutions, and healthcare facilities. Options for various indoor and outdoor configurations enhance its adaptability to specific operational requirements.

In conclusion, the Trane RT-PRC010-EN stands out as an energy-efficient, reliable, and versatile solution for commercial heating and cooling needs. Its advanced features, smart controls, and robust design make it an ideal choice for businesses looking to enhance comfort while minimizing energy expenditures and ensuring operational reliability. Whether dealing with extreme weather conditions or managing indoor air quality concerns, this rooftop unit provides a comprehensive solution tailored to modern commercial requirements.