Trane Application Considerations for SXHF Air Conditioners

Page 12

Application Considerations

Figure AC-3 is a simplified sketch showing which panels can be used for horizontal supply and/or return. On 90 to 130 ton units, only one side of the extended casing may be used for horizontal supply because of the location of the unit control panel.There are, however, on SXHF models two panels (Panels A) on the side opposite the control box which can be removed along with the vertical support which separates the two. Removal of the vertical support is optional, but will ensure maximum airflow. On SLHG, SSHG models only one of the Panel A’s may be used for horizontal supply

because of the location of the heating coil. Horizontal return is accomplished in much the same way as on S*HFs by removing the exhaust fan access door (Panel B). SeeTables AC-4 and 5 for S*HG panel dimensions.

When using an IntelliPak® Rooftop for horizontal supply and return, an additional pressure drop must be added to the supply external static to account for the 90 degree turn the air is making. This additional pressure drop depends on airflow and rooftop size, but a range of 0.10 inches to 0.30 inches can be expected.The openings on the rooftop all have a one inch lip around the

perimeter to facilitate ductwork attachment. If exhaust fans are being used on an IntelliPak Rooftop unit with horizontal return, provisions should be made for access to the exhaust components, since the access door opening is now being used as a return. Perhaps the return ductwork attachment to the rooftop can include a section of removable duct. Use the dimensions provided and the supply and exhaust CFM to calculate the velocity (ft/min) through the openings.

Horizontal Discharge SXHG, SLHG, SSHG Rooftops (90 to 130 tons)

The SXHG, SLHG, SSHG rooftops can be field modified to supply and return air

Figure AC-3 — Horizontal Discharge Panel Dimensions — 90 - 130Tonss SXHG, SLHG, SSHG Units

horizontally without the use of a horizontal supply/return curb.

To supply air horizontally, use Panel A only.The Panel on the opposite side cannot be used due to the location of the unit control Panel. SXHG rooftop air conditioners do not have a panel configuration like the 20 to 75 ton rooftops.To achieve maximum airflow, vertical support can be removed after the unit has been placed on the roof curb. It is secured by four screws. (See Note 1) For horizontal discharge on SLHG and SSHG units, only the Panel A next to the condenser fan section can be removed. The other Panel A next to the supply fan cannot be used due to the location of the heating coils.

To return air horizontally, the exhaust fan access door (Panel B) can be removed and used as a return opening.

Note:

1.SXHG units have two Panel A’s that can be removed. Once unit is installed, panel(s) and the 61/2” vertical support channel in between may be removed.

Table AC-4 — SXHG, SLHG, SSHG —

Panel A and B Dimensions

 

 

 

Total Area (H X W)

Panel

H (in.)

W (in.)

(in.2)

(ft2)

A

72.7

27.5

1999

13.9

B

72.7

34.5

2508

17.4

Notes:

1.Add an extra 0.20-inches pressure drop to the supply external static to account for the extra turn the air is making.

2.The openings all have a 1.25-inch lip around the perimeter to facilitate ductwork attachment.

Table AC-5 — SXHG, SLHG, SSHG —

X,Y and Z Dimensions

Model

X (in.)

Y (in.)

Z (in.)

S*HG 90-130

69.0

77.8

244.7

* = X, L, or S

 

 

 

3.If exhaust fans are being used, provisions should be made for access to the exhaust components, since the access door is now being used as a return.

4.Use the dimensions provided and the supply Cfm to calculate the velocity (ft/min) through the openings to be sure they are acceptable.

12

RT-PRC010-EN

Image 12
Contents 20 75Tons 90 130Tons Introduction American Standard IncContents Features and Benefits Standard FeaturesOptional Features Field Installed AccessoriesFeatures Summary Installation EaseEasy to Service ReliabilityIntegrated Comfort System ICS SimplifyingThe Comfort SystemTracer control points for IntelliPak Rooftops Features and Benefits Optimum Building Comfort Control FansWith Inlet GuideVanesVariable Frequency Drives VFD Proven DesignThroughTesting and Research Trane 3-DScroll CompressorSimple Design with 70% Fewer Parts LowTorqueVariationApplication Considerations Percent Exhaust System Barometric Relief DampersPanel C Dimensions Horizontal Discharge20 75 tons SXHF, SFHF, SLHF, SSHF, SXHF, SFHF, SLHF, Sshf UnitsTable AC-4 SXHG, SLHG, Sshg Panel a and B Dimensions Table AC-5 SXHG, SLHG, Sshg Z Dimensions2508 17.4 High Capacity Evaporator Coil Corrosive AtmospheresVentilation Override Sequences Natural Gas Heating ConsiderationsAcoustical Considerations Clearance RequirementsFigure AC-4 Unit Placement Duct DesignSelection Procedure DetermineTotalWinter Heating Load Electric Heating SystemGas Heating System Natural Gas HotWater HeatingSupply Fan Motor Sizing Exhaust Fan Motor SizingAltitude Corrections Selection Procedure Model Number Description H F C1 1 567 General Data Table GD-1- General Data 20-40Tons20Ton 25Ton 30Ton 40Ton RPMFilters Table GD-2 General Data 50-75Tons 50Ton 55Ton 60Ton 70Ton 75Ton Low Ambient Option Min. Outside AirTempTable GD-3 General Data 90-130Tons 90Ton 105Ton 115Ton 130Ton50% 100% Number/Size/Type 22/FC Table GD-4 ARI Performance Data Table GD-5 ARI Correction MultipliersEER Iplv Performance Adjustment Factors Table PAF-1 Enthalpy of Saturated AIRPerformance 20Ton Data Performance 25Ton Data Performance 30Ton Data Performance 40Ton Data 345 452 265 496 183561 207 451 399 493 302 537 199 429 389 468 292 431 551Performance 50Ton Data Performance 55Ton Data Performance 60Ton Data AmbientTemperature F Performance 70Ton DataFlow Performance 75Ton Data Performance 90Ton Data Performance 105Ton Data Performance 115, 130TonsPerformance Data Table PD-24 Natural Gas Heating CapacitiesTable PD-25- Natural Gas Heating Capacities Table PD-26 Steam Heating Capacities Q/ITD1Table PD-28 20 to 75-Tons Electric Heat AirTemperature Rise Table PD-29- 90To 130-Ton Electric Heat AirTemperature RiseTable PD-30- Electric Heat KW Ranges Table PD-31- HotWater Heating Capacities Q/ITD1 20, 25Tons RPM BHPPressure 4000 1037 1225 12711364 140910 HP 1200 RPM 80% 1100 RPM 6000 883 927 968 1007 1043 1078 22.221400 RPM Wocfm 40% 1300 RPM 25 HP Inches 1200 RPM 50% 20 HP Table PD-35 Supply Fan PerformanceWITH Inletvanes 30Ton 6000 890 933 974 1012 10491357 20.45 Dual 18 X 18 Fans Wocfm Entrance Losses Ithout Exhaust15 HP 1200 RPM Fan Curve Limits 1000 RPM 10 HP40, 50, 55Tons 30.4732.36 40, 50, 55Tons 800 14.86 820 1161 32.63 Cfm Total Static Pressure Std 250 500 750 000Inches w.c 60, 70, 75Tons 43.8560, 70, 75Tons 14000 729 800 RPM 20 HP 70% 15 HP 27000 646 690 732 773 808 840 10.71 872 904 13.34 28000 667 710 750 791 826 10.15 85730000 708 749 787 826 10.13 861 897 12.88 928 14.40 957 15.80 98527000 1363 39.85 1388 41.68 1414 43.54 1437 45.26 1461 29000 1375 42.04 1398 43.93 1423 45.91 14451469 49.80 1491 1515 53.66 30000 1382 43.16 1406 45.18 142827000 695 734 770 805 840 904 13.44 935 14.77 28000 718 756 791 825 10.28 858891 12.90 922 14.26 952 15.65 29000 741 778 812 845 897 13.19 928 14.59 958 16.05 9871579 32000 1442 49.55 14641496 55.23 1518 57.33 1541 59.53 1565 37000 1494Performance 105,115,130Tons 1623 76.74 1640 78.95 00 R 15001100 100 900 RP25.35 26.9532.56 1233 34.40 1255 36.26 1277 38.17 46000 1138 26.67 30.40 1216 32.05 1240 33.79 1086 23.371625 76.92 1643 79.30 46000 1624 1641 79.40Performance 20 -75Tons Data Table PD-44 Component Static Pressure Drops in.W.GSFHF/G SEHF/G SLHF/G SSHF/G Performance 90-130Tons Data Table PD-45 Component Static Pressure Drops in.W.GSFHF/G SLHF/G SSHF/GTable PD-46 20-75 -Tons Supply Air Fan Drive Selections Table PD-47 90-130 -Tons Supply Air Fan Drive SelectionsBHP RPM 835 39.71 859885 44.08 910 46.33 934 48.32 Table PD-50 20-75Tons 100% Exhaust Fan Drive Selections Table PD-51 90-130Tons -100% Exhaust Fan Drive SelectionsTable PD-52 20-75Tons 50% Exhaust Fan Performance Table PD-53 90-130 Tons 50% Exhaust Fan Performance18.97 835 19.86 859 20.87 885 22.05 910 23.18 934 24.17 Table PD-54- 50% Exhaust Fan Drive Selections Controls VAV UnitsVAV Units Only Supply Air Setpoint Reset Reset based on outdoor air temperatureReset based on zone temperature ZoneTemperature Control Unoccupied Zone Heating and CoolingCV Units CV Units OnlyHeating Gas Heating -Two-Stage Unoccupied ZoneTemperature Control Cooling and Heating Gas Heating Modulating GasElectric Heating HotWater or Steam HeatingVAV/CV Units Exhaust sequence C Purge sequence DPurge with duct pressure control E Human Interface Panel H.IHuman Interface Panel Main Menu Generic Building Automation System odule GbasEvaporator Coil Frost Protection Occupied/Unoccupied Switching Dry BulbTemperature Control of EconomizerNight Setback Sensors Occupied/Unoccupied input on the RTMElectrical Service Sizing Dual Source Power units 200VElectrical Data Set 2. Rooftop units with Electric HeatRLA1 LRA 178 21.8 143Table ED-6 -Voltage Utilization Range 48.5 39.0 Motor Hp48.5 39.0 FLADimensional 20 75Tons Figure DD-1 20-75Ton Cooling Only Unit Dimensions Sahf Detail B Covers 40, 60, 70 and 75 TON Units20 & 25 5-8 15/ 16 24-1 3 5/ 8 1-7 9 Sahf 10’-1 7 ’-10 15/ 16 2’-0 ’-6Dimensional 90 130Tons Figure DD-5 90 130Tons Service ClearanceFigure DD-6 90 130Ton Roof Curb Dimensions Section B-B RT-PRC010-ENDimensional Field Installed SensorsConstant CV and VAV Integrated Comfort System SensorsWeights TableW-1 -Approximate OperatingWeights Lbs./KgSL/SS 14740 15380 15930 16080Options OptionsAmbient Control Agency ApprovalMiscellaneous Options Electronic Zone Sensors Roof CurbMechanical Specifications GeneralSupply Fan 20 75Ton Units 90 130Ton UnitsControls Unit ControllerPermanent cleanable wire mesh option High efficiency throwaway optionPercent bag filter option Percent cartridge filter optionOutside Air General Manual outside air optionPercent modulating economizer option Ultra low-leak economizer dampers optionAccessories Heating SystemLiterature Order Number File Number PL-RT-S*HF/S*HG-20-130TONS-PRC0010-EN-10-2001Supersedes RT-DS-8 05/98 Stocking Location Inland-LaCrosse

RT-PRC010-EN specifications

The Trane RT-PRC010-EN is a prominent model in the line of Trane's packaged rooftop units, designed to offer efficient heating, cooling, and ventilation for commercial applications. Renowned for its robust performance, this unit integrates advanced technologies and superior engineering to meet diverse environmental needs while ensuring energy efficiency and reliability.

One of the key features of the RT-PRC010-EN is its energy-efficient operation. The unit is equipped with variable-speed fans and scroll compressors, which allow for precise control over temperature and airflow. This adaptability not only enhances comfort but also contributes to significant energy savings. The inclusion of high-efficiency cooling coils further optimizes performance, making it an excellent choice for businesses looking to lower their operational costs.

The RT-PRC010-EN model integrates smart controls that allow for seamless integration into building management systems. These controls facilitate real-time monitoring and diagnostics, enabling facility managers to maintain optimum operational efficiency and promptly address any maintenance needs. This technology minimizes downtime and extends the lifecycle of the unit.

Moreover, the unit’s construction is targeted toward resilience and durability. Built with a corrosion-resistant cabinet and extensive insulation, the RT-PRC010-EN can withstand the rigors of various climates, making it suitable for installation across different geographical locations. Its compact design allows for easy installation on rooftops, maximizing space utilization in commercial buildings.

Another standout characteristic is the unit's versatility in application. The RT-PRC010-EN can be tailored to suit a wide range of commercial settings, including retail establishments, educational institutions, and healthcare facilities. Options for various indoor and outdoor configurations enhance its adaptability to specific operational requirements.

In conclusion, the Trane RT-PRC010-EN stands out as an energy-efficient, reliable, and versatile solution for commercial heating and cooling needs. Its advanced features, smart controls, and robust design make it an ideal choice for businesses looking to enhance comfort while minimizing energy expenditures and ensuring operational reliability. Whether dealing with extreme weather conditions or managing indoor air quality concerns, this rooftop unit provides a comprehensive solution tailored to modern commercial requirements.