Trane RT-PRC010-EN manual Gas Heating Modulating Gas, Electric Heating, HotWater or Steam Heating

Page 78

Controls

(CV Units)

 

 

 

 

Gas Heating: Modulating Gas

Upon a call for heating, the UCM closes the heating contacts, beginning the firing sequence. First, the heat exchanger combustion blower begins operation. Upon positive proving of combustion airflow, a pre-purge cycle is executed. Then the ignition sequence takes place.

If ignition is not proven, the ignition transformer is de-energized. After a time delay, another pre-purge cycle takes place, followed by another attempt to ignite. If ignition fails a second time, the heating section will be shut down and locked out until manually reset at the unit mounted Human Interface Panel.

As additional heat is required, the air damper opens, increasing the firing rate.

During heating operation, an electronic flame safety control provides continuous flame supervision. If combustion should become unstable for any reason, heating will automatically shut down. After one minute, another 60 second pre-purge and ignition cycle begins.

As the heating requirement is satisfied, the UCM will reduce the combustion air, and the firing rate will lower to maintain the desired outlet temperature. When the requirement is fully satisfied, the heating contacts are opened, de- energizing the heat.The specific sequence of operation of the gas heat will depend on the size of the heat exchanger.

Electric Heating

The three stages of electric heat will be sequenced on the zone demand signal from the zone sensor.The signal is sent to the UCM and the stages are sequenced based on load demand.

HotWater or Steam Heating

Upon a call for heat, the UCM will send a varying voltage signal to the valve actuator.The valve will modulate to meet building demand as indicated by the voltage signal. When heating is satisfied, the valve will modulate closed.

A temperature sensor is located on the coldest section of the coil. When it senses an impending freeze condition, a signal is sent to the hydronic valve to

drive it full open. If the supply fan is on, or if the outside air damper is open when this freezing condition is sensed, the supply fan is turned off and the outside air damper is closed.

B

Supply AirTempering

For gas and electric heat units in the Heat mode but not actively heating, if the supply air temperature drops to 10 F below the Occupied zone heating temperature setpoint, one stage of heat will be brought on to maintain a minimum supply air temperature.The heat stage is dropped if the supply air temperature rises to 10 F above the Occupied zone heating temperature setpoint.

C

Auto Changeover

When the System Mode is “Auto,” the mode will change to cooling or heating as necessary to satisfy the zone cooling and heating setpoints.The zone cooling and heating setpoints can be as close as 2 F apart.

2

Unoccupied ZoneTemperature Control

Cooling and Heating

Both cooling or heating modes can be selected to maintain Unoccupied zone temperature deadbands. For Unoccupied periods, heating, economizer operation or compressor operation can be selectively locked out at the Human Interface Panels.

78

RT-PRC010-EN

Image 78
Contents 20 75Tons 90 130Tons Introduction American Standard IncContents Optional Features Features and BenefitsStandard Features Field Installed AccessoriesEasy to Service Features SummaryInstallation Ease ReliabilityIntegrated Comfort System ICS SimplifyingThe Comfort SystemTracer control points for IntelliPak Rooftops Features and Benefits Optimum Building Comfort Control FansWith Inlet GuideVanesVariable Frequency Drives VFD Simple Design with 70% Fewer Parts Proven DesignThroughTesting and ResearchTrane 3-DScroll Compressor LowTorqueVariationApplication Considerations Percent Exhaust System Barometric Relief Dampers20 75 tons SXHF, SFHF, SLHF, SSHF, Panel C DimensionsHorizontal Discharge SXHF, SFHF, SLHF, Sshf UnitsTable AC-4 SXHG, SLHG, Sshg Panel a and B Dimensions Table AC-5 SXHG, SLHG, Sshg Z Dimensions2508 17.4 Ventilation Override Sequences High Capacity Evaporator CoilCorrosive Atmospheres Natural Gas Heating ConsiderationsAcoustical Considerations Clearance RequirementsFigure AC-4 Unit Placement Duct DesignSelection Procedure Gas Heating System Natural Gas DetermineTotalWinter Heating LoadElectric Heating System HotWater HeatingSupply Fan Motor Sizing Exhaust Fan Motor SizingAltitude Corrections Selection Procedure Model Number Description H F C1 1 567 20Ton 25Ton 30Ton 40Ton General DataTable GD-1- General Data 20-40Tons RPMFilters Table GD-2 General Data 50-75Tons 50Ton 55Ton 60Ton 70Ton 75Ton Low Ambient Option Min. Outside AirTempTable GD-3 General Data 90-130Tons 90Ton 105Ton 115Ton 130Ton50% 100% Number/Size/Type 22/FC Table GD-4 ARI Performance Data Table GD-5 ARI Correction MultipliersEER Iplv Performance Adjustment Factors Table PAF-1 Enthalpy of Saturated AIRPerformance 20Ton Data Performance 25Ton Data Performance 30Ton Data 561 207 451 399 493 302 537 199 429 389 468 292 Performance 40Ton Data345 452 265 496 183 431 551Performance 50Ton Data Performance 55Ton Data Performance 60Ton Data AmbientTemperature F Performance 70Ton DataFlow Performance 75Ton Data Performance 90Ton Data Performance 105Ton Data Performance 115, 130TonsTable PD-25- Natural Gas Heating Capacities Performance DataTable PD-24 Natural Gas Heating Capacities Table PD-26 Steam Heating Capacities Q/ITD1Table PD-28 20 to 75-Tons Electric Heat AirTemperature Rise Table PD-29- 90To 130-Ton Electric Heat AirTemperature RiseTable PD-30- Electric Heat KW Ranges Table PD-31- HotWater Heating Capacities Q/ITD1 20, 25Tons RPM BHPPressure 1364 4000 10371225 1271 140910 HP 1200 RPM 80% 1100 RPM 6000 883 927 968 1007 1043 1078 22.221400 RPM Wocfm 40% 1300 RPM 25 HP Inches 1200 RPM 50% 20 HP Table PD-35 Supply Fan PerformanceWITH Inletvanes 30Ton 6000 890 933 974 1012 10491357 20.45 15 HP 1200 RPM Fan Curve Limits Dual 18 X 18 Fans Wocfm Entrance LossesIthout Exhaust 1000 RPM 10 HP40, 50, 55Tons 30.4732.36 40, 50, 55Tons 800 14.86 820 1161 32.63 Cfm Total Static Pressure Std 250 500 750 000Inches w.c 60, 70, 75Tons 43.8560, 70, 75Tons 14000 729 800 RPM 20 HP 70% 15 HP 30000 708 749 787 826 10.13 861 27000 646 690 732 773 808 840 10.71 872904 13.34 28000 667 710 750 791 826 10.15 857 897 12.88 928 14.40 957 15.80 9851469 49.80 1491 27000 1363 39.85 1388 41.68 1414 43.54 1437 45.26 146129000 1375 42.04 1398 43.93 1423 45.91 1445 1515 53.66 30000 1382 43.16 1406 45.18 1428891 12.90 922 14.26 952 15.65 29000 741 778 812 845 27000 695 734 770 805 840904 13.44 935 14.77 28000 718 756 791 825 10.28 858 897 13.19 928 14.59 958 16.05 9871496 55.23 1518 57.33 1541 59.53 1565 157932000 1442 49.55 1464 37000 1494Performance 105,115,130Tons 1100 1623 76.74 1640 78.9500 R 1500 100 900 RP32.56 1233 34.40 1255 36.26 1277 38.17 46000 1138 26.67 25.3526.95 30.40 1216 32.05 1240 33.79 1086 23.371625 76.92 1643 79.30 46000 1624 1641 79.40Performance 20 -75Tons Data Table PD-44 Component Static Pressure Drops in.W.GSFHF/G SEHF/G SLHF/G SSHF/G SFHF/G Performance 90-130Tons DataTable PD-45 Component Static Pressure Drops in.W.G SLHF/G SSHF/GTable PD-46 20-75 -Tons Supply Air Fan Drive Selections Table PD-47 90-130 -Tons Supply Air Fan Drive SelectionsBHP RPM 835 39.71 859885 44.08 910 46.33 934 48.32 Table PD-50 20-75Tons 100% Exhaust Fan Drive Selections Table PD-51 90-130Tons -100% Exhaust Fan Drive SelectionsTable PD-52 20-75Tons 50% Exhaust Fan Performance Table PD-53 90-130 Tons 50% Exhaust Fan Performance18.97 835 19.86 859 20.87 885 22.05 910 23.18 934 24.17 Table PD-54- 50% Exhaust Fan Drive Selections Controls VAV UnitsVAV Units Only Reset based on zone temperature Supply Air Setpoint ResetReset based on outdoor air temperature ZoneTemperature Control Unoccupied Zone Heating and CoolingCV Units CV Units OnlyHeating Gas Heating -Two-Stage Electric Heating Unoccupied ZoneTemperature Control Cooling and HeatingGas Heating Modulating Gas HotWater or Steam HeatingVAV/CV Units Purge with duct pressure control E Exhaust sequence CPurge sequence D Human Interface Panel H.IHuman Interface Panel Main Menu Generic Building Automation System odule GbasEvaporator Coil Frost Protection Night Setback Sensors Occupied/Unoccupied SwitchingDry BulbTemperature Control of Economizer Occupied/Unoccupied input on the RTMElectrical Data Electrical Service SizingDual Source Power units 200V Set 2. Rooftop units with Electric HeatRLA1 LRA 178 21.8 14348.5 39.0 Table ED-6 -Voltage Utilization Range48.5 39.0 Motor Hp FLADimensional 20 75Tons Figure DD-1 20-75Ton Cooling Only Unit Dimensions Sahf Detail B Covers 40, 60, 70 and 75 TON Units20 & 25 5-8 15/ 16 24-1 3 5/ 8 1-7 9 Sahf 10’-1 7 ’-10 15/ 16 2’-0 ’-6Dimensional 90 130Tons Figure DD-5 90 130Tons Service ClearanceFigure DD-6 90 130Ton Roof Curb Dimensions Section B-B RT-PRC010-ENDimensional Field Installed SensorsConstant CV and VAV Integrated Comfort System SensorsSL/SS WeightsTableW-1 -Approximate OperatingWeights Lbs./Kg 14740 15380 15930 16080Options OptionsAmbient Control Agency ApprovalMiscellaneous Options Electronic Zone Sensors Roof CurbMechanical Specifications GeneralControls Supply Fan 20 75Ton Units90 130Ton Units Unit ControllerPercent bag filter option Permanent cleanable wire mesh optionHigh efficiency throwaway option Percent cartridge filter optionPercent modulating economizer option Outside Air GeneralManual outside air option Ultra low-leak economizer dampers optionAccessories Heating SystemLiterature Order Number File Number PL-RT-S*HF/S*HG-20-130TONS-PRC0010-EN-10-2001Supersedes RT-DS-8 05/98 Stocking Location Inland-LaCrosse

RT-PRC010-EN specifications

The Trane RT-PRC010-EN is a prominent model in the line of Trane's packaged rooftop units, designed to offer efficient heating, cooling, and ventilation for commercial applications. Renowned for its robust performance, this unit integrates advanced technologies and superior engineering to meet diverse environmental needs while ensuring energy efficiency and reliability.

One of the key features of the RT-PRC010-EN is its energy-efficient operation. The unit is equipped with variable-speed fans and scroll compressors, which allow for precise control over temperature and airflow. This adaptability not only enhances comfort but also contributes to significant energy savings. The inclusion of high-efficiency cooling coils further optimizes performance, making it an excellent choice for businesses looking to lower their operational costs.

The RT-PRC010-EN model integrates smart controls that allow for seamless integration into building management systems. These controls facilitate real-time monitoring and diagnostics, enabling facility managers to maintain optimum operational efficiency and promptly address any maintenance needs. This technology minimizes downtime and extends the lifecycle of the unit.

Moreover, the unit’s construction is targeted toward resilience and durability. Built with a corrosion-resistant cabinet and extensive insulation, the RT-PRC010-EN can withstand the rigors of various climates, making it suitable for installation across different geographical locations. Its compact design allows for easy installation on rooftops, maximizing space utilization in commercial buildings.

Another standout characteristic is the unit's versatility in application. The RT-PRC010-EN can be tailored to suit a wide range of commercial settings, including retail establishments, educational institutions, and healthcare facilities. Options for various indoor and outdoor configurations enhance its adaptability to specific operational requirements.

In conclusion, the Trane RT-PRC010-EN stands out as an energy-efficient, reliable, and versatile solution for commercial heating and cooling needs. Its advanced features, smart controls, and robust design make it an ideal choice for businesses looking to enhance comfort while minimizing energy expenditures and ensuring operational reliability. Whether dealing with extreme weather conditions or managing indoor air quality concerns, this rooftop unit provides a comprehensive solution tailored to modern commercial requirements.