Trane PTAC-SVX01C-EN manual Configure the display module settings, Field commissioning support

Page 16

Installation

Table 8. Output settings

 

ID

ID

 

 

Rev

 

 

Cond

Vent

 

Fan

Fan

Aux

 

Valve

OD

Rmt

Pump

Door

User Mode / Model

High

Low

Heat

Comp

(PTHE)

Fan

Fan

(PTHE)

/Fan

 

 

 

 

 

 

 

 

 

 

High Heat Pump

ON

OFF

OFF

ON

OF

ON

EN

EN

EN

(PTHE only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Heat Pump

OFF

ON

OFF

ON

OFF

ON

EN

EN

EN

(PTHE only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Emergency/

ON

OFF

ON

OFF

N/C

OFF

EN

EN

EN

Auxiliary Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Emergency/

OFF

ON

ON

OFF

N/C

OFF

EN

EN

EN

Auxiliary Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Cooling

ON

OFF

OFF

ON

ON

ON

EN

EN

EN

 

 

 

 

 

 

 

 

 

 

Low Cooling

OFF

ON

OFF

ON

ON

ON

EN

EN

EN

 

 

 

 

 

 

 

 

 

 

High Fan

ON

OFF

OFF

OFF

N/C

OFF

EN

EN

EN

 

 

 

 

 

 

 

 

 

 

Low Fan

OFF

ON

OFF

OFF

N/C

OFF

EN

EN

EN

 

 

 

 

 

 

 

 

 

 

Off

OFF

OFF

OFF

OFF

N/C

OFF

OFF

EN

OFF

 

 

 

 

 

 

 

 

 

 

The sequence will automatically advance through all outputs and exit when the sequence has completed; it is left to the technician to monitor the status of the end devices during the test to verify that each operates properly.

Manual test is initiated by combining the following conditions:

User Mode = OFF

Press and hold MODE & SETPOINT DOWN for 5 seconds

During the test process, the word "STEP" and the corresponding step number will be lighted on the display. After the final step has been executed, the controller will exit Manual test and force the controller

Notes: EN = Enabled - operations based on other logic

Notes: N/C = No change from prior state

Step 8. Configure the display module settings

Indoor Temperature setpoint

The indoor temperature setpoint buttons tell the unit how warm or cool the occupant wants the room.

The setpoint is set by pressinging the up/down buttons on the interface module. These buttons do not scroll (i.e. holding the button will not continue to adjust the setpoint value) because each adjustment of the setpoint value requires its own unique button press.

Default setpoint on first power up: 72°F (22.0°C – closest approximation)

Setpoint resolution: ± 1°F (± 0.5°C)

User Mode Selection

Pressing the MODE button on the unit tells the unit which mode the occupant prefers. There are four modes to choose from.

1.COOL

2.HEAT

3.FAN (fan only)

4.OFF (default for first power up)

Fan Mode

Figure 16. Digital display module

Fan Speed Selection

Pressing the FAN button on the interface module determines fan speed. There are two fan speeds to choose from.

1.LOW (default for first power up)

2.HIGH

Field commissioning support

Manual Test Mode

A manual test mode is provided to allow a field technician to verify proper output and end device operation through a predetermined, timed sequence.

to into a reset.

Manual test mode may be cancelled by pressing any button on the display.

Manual test is not available if there is no interface module, as is in Class 2 control applications.

The test sequence attempts to clear unit diagnostics and restore normal unit operation prior to testing the outputs. If the diagnostics remain after an attempt to clear them, manual test may be affected or disallowed.

Dehumidification

The PTAC controller does not directly measure room humidity.

The PTAC provides dehumidfication by combining the following actions in a predefined sequence.

1.The PTAC subcools the room to a preset state, a dehumidification offset below the cooling setpoint.

2.The unit will automatically adjust the fan speed.

3.When incorporating the vent door option, the controller will automatically adjust its position.

16

PTAC-SVX01C-EN

Image 16
Contents Packaged Terminal Air Conditioner Table of Contents Model Number Description E E 0 9 0 1 * a aGeneral Information Important Environmental ConcernsOverview of Manual Responsible Refrigerant PracticesGeneral Information Pre-Installation Pre-Installation ConsiderationsChecklist Fire HazardPre-Installation Receiving ChecklistReceiving and Handling Shipping PackageUnit Dimensions Unit with wall sleeve and subbase accessory Wall SleeveUnit Dimensions Air dischargeLive Electrical Components InstallationElectrical Requirements Installation Power receptacle configurationsInstallation Procedure Remove rear closureHazardous Voltage w Panel from wall sleeveInstall unit power supply BottomInstall the unit controls Voltage Options Accessory Accessory part number 115VOption 265 OptionWiring Voltage WireSpecification External Interface Size LengthOutput settings Configure the display module settingsField commissioning support Programmable Settings Set point configurationDisplay units Setpoint limitingSelection Unit Display Measure Example IP English SI MetricEnergy Management System Indoor fan cycle configurationOccupancy arbitration for energy management Ptee manual test sequence Pthe manual test sequenceOff 10 sec Off 20 secOperation Sequence of OperationOperation Remote Fan OperationVent Control Air Discharge GrilleAir conditioner performance data Heat pump performance Voltage 208 230 265 Cooling dataElectric heat Data Heater size Btu/HCooling temperature change heat pumps Cooling temperature change air conditionersCooling amperage air conditioners Cooling amperage heat pumpsVoltage 208 230 265 Heating total wattage input heat pumpsHeating Btu/H Unit accessory model numbers Hydronic heat options Maintenance Maintenance ProceduresMaintenance Refrigeration System ServiceMaintenance Brazing Leak TestingHigh Temperatures Use of Pressure Regulator Valves GaugesEvacuation Procedure Maintenance EvacuationFan Motor Overheat Charging Procedure Charging the SystemRefrigerant Line Piercing ValvesMaintenance Cooling Performance Test ThermometersSling Psychrometer Cooling Performance TestHeating Power Consumption Test Calculating procedureTesting Capacitor Resistance Resistance CheckHeater Assembly with Power OFF to the Unit and Heater Ground TestResistance Test Indoor Coil and Air ThermistorsThermistor indoor coil Resistance Rmin Rnom RmaxPower Cord Removal Component ReplacementUnit Disassembly Procedures Power cord InstallationControl Board Replacement Procedure Hazardous Voltage Removing the Outdoor Coil and Outdoor Air ThermistorsIndoor Fan and Motor Outdoor Fan and MotorTroubleshooting DiagnosticsTroubleshooting Compressor output does not energizeIndoor/remote fan outputs do not energize Outdoor fan output does not energizeRandom restart timer Explanation Reversing valve output does not energizeAuxiliary heat output does not energize Ventilation output does not energizeOutput on when the mode is off SymptomCondensate pump does not energize Control fuse is blownWiring Diagram AIR CoilWiring Diagram PVDWiring diagram 07 models PVD Energy management system Warranty Full 1st Year WarrantyFull 2nd 5th Sealed System Warranty Limited 2nd through 5th Year Functional Parts WarrantyPage PTAC-SVX01C-EN

PTAC-SVX01C-EN specifications

The Trane PTAC-SVX01C-EN is a cutting-edge Packaged Terminal Air Conditioner (PTAC) designed to provide optimal temperature control, energy efficiency, and user comfort in a variety of settings, including hotels, apartments, and office buildings. This unit stands out with its robust features and advanced technologies, making it a reliable choice for meeting diverse heating and cooling needs.

At the heart of the Trane PTAC-SVX01C-EN is its innovative design, which combines powerful performance with quiet operation. This unit utilizes a high-efficiency compressor that ensures rapid cooling and heating, providing ideal comfort regardless of the external climate. With a capacity range suitable for smaller spaces, the PTAC delivers strong performance while maintaining energy efficiency, thus reducing operational costs over time.

One of the key characteristics of the PTAC-SVX01C-EN is its user-friendly interface. The intuitive controls allow users to effortlessly adjust temperature settings, fan speeds, and modes of operation, including cooling, heating, and fan only. This flexibility enhances user comfort while optimizing energy consumption. Additionally, the unit features a programmable timer, enabling users to schedule operation according to their specific needs, further conserving energy when spaces are unoccupied.

The unit's Quiet Operation Technology minimizes noise levels, making it an ideal choice for environments where peace and quiet are paramount. This feature is particularly beneficial in hospitality settings, where guests expect a tranquil atmosphere. The PTAC is engineered to provide ample airflow while minimizing sound, creating a pleasant indoor environment.

Another standout feature of the Trane PTAC-SVX01C-EN is its advanced air filtration system. The integrated filter effectively captures dust, allergens, and other airborne particles, promoting a cleaner and healthier living environment. This is particularly essential for individuals with allergy sensitivities or respiratory issues.

Durability is also a hallmark of the PTAC-SVX01C-EN. Built with high-quality materials, it is designed to withstand the demands of continuous operation while requiring minimal maintenance. The unit's sleek and compact design allows for easy installation in various locations, ensuring versatility without sacrificing performance.

In summary, the Trane PTAC-SVX01C-EN represents a perfect blend of efficiency, comfort, and innovative technology. Its user-friendly controls, quiet operation, and advanced air filtration make it a leading choice for those seeking reliable climate control solutions in residential and commercial spaces alike. Whether for heating or cooling, the Trane PTAC-SVX01C-EN is engineered to deliver exceptional performance and lasting dependability.