Trane PTAC-SVX01C-EN manual Ground Test, Resistance Test, Indoor Coil and Air Thermistors

Page 37

Maintenance

Resistance Test

1.With no power, remove the leads from the compressor terminals.

2.Touch the leads of an ohmmeter to terminals C-S, start windings and C-R, run winding.

If either winding does not test continuous, replace the compressor.

Voltmeter

15 amp fuse

Ammeter

Capacitor

Figure 25. Testing capacitor resistance

Testing capacitance

capacitance (MFD) = 2650 X amperage voltage

Note: Replace the capacitor if the value obtained is not within 10% of the rating printed on the capacitor.

Ground Test

WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

With no power and compressor leads removed:

Set an ohmmeter on its highest scale. Touch one lead to the compressor body (clean point of contact, as a good connection is a must) and the other probe to each compressor terminal in turn. If a reading is obtained, then compressor is grounded and must be replaced.

If the voltage, capacitor, overload and motor windings test fail to show the cause for failure:

Ohmeter Compressor top

Terminals

Outlet Accumulator

Figure 26. Compressor ground test

1.With no power, wire a test cord to line voltage (Line & N).

Note: The wire size of the test cord must equal the line size, and the fuses in the test line must be of the proper size and type.

2.Connect a good capacitor of the right MFD and voltage rating into the circuit as shown in Figure 40.

Figure 27. Test cord connections

3.Carefully apply line voltage.

a.If the compressor starts and continues run, the cause for failure is somewhere else in the system.

b.If the motor fails to start - replace. Since all single phase compressors are of the permanent split capacitor design the high and low side pressure must be approximately equal or the low torque compressor may not start.

Indoor Coil and Air

Thermistors

1.Remove the Indoor Coil Thermistor leads from the circuit board.

2.Check the resistance of the Indoor Coil Thermistor against the table on the next page. The leads of the ohm meter will need to contact the ends of the thermistors that connect to the board.

3.Replace the Indoor Coil Thermistor if it does not test as above.

Outdoor Coil and Air

Thermistors

1.Remove the outdoor coil thermistor leads from the circuit board.

2.Check the resistance of the outdoor coil thermistor against the table on the next page. The leads of the ohm meter will need to contact the ends of the thermistors that connect to the board.

3.Replace the outdoor coil thermistor if it does not test as above.

Heater Assembly with Power OFF to the Unit and Heater

1.Remove the heaters in question and visually inspect the element for broken condition. Refer to the disassembly procedures for information on disassembling the heater.

2.Test the thermal fuse (one time fuse). If open, replace the heater assembly.

PTAC-SVX01C-EN

37

Image 37
Contents Packaged Terminal Air Conditioner Table of Contents E E 0 9 0 1 * a a Model Number DescriptionImportant Environmental Concerns General InformationOverview of Manual Responsible Refrigerant PracticesGeneral Information Pre-Installation Considerations Pre-InstallationChecklist Fire HazardReceiving Checklist Pre-InstallationReceiving and Handling Shipping PackageUnit with wall sleeve and subbase accessory Wall Sleeve Unit DimensionsAir discharge Unit DimensionsLive Electrical Components InstallationElectrical Requirements Power receptacle configurations InstallationRemove rear closure Installation ProcedureHazardous Voltage w Panel from wall sleeveBottom Install unit power supplyVoltage Options Accessory Accessory part number 115V Install the unit controlsOption 265 OptionWire Wiring VoltageSpecification External Interface Size LengthOutput settings Configure the display module settingsField commissioning support Set point configuration Programmable SettingsSetpoint limiting Display unitsSelection Unit Display Measure Example IP English SI MetricEnergy Management System Indoor fan cycle configurationOccupancy arbitration for energy management Pthe manual test sequence Ptee manual test sequenceOff 10 sec Off 20 secSequence of Operation OperationRemote Fan Operation OperationVent Control Air Discharge GrilleAir conditioner performance data Voltage 208 230 265 Cooling data Heat pump performanceElectric heat Data Heater size Btu/HCooling temperature change air conditioners Cooling temperature change heat pumpsCooling amperage heat pumps Cooling amperage air conditionersVoltage 208 230 265 Heating total wattage input heat pumpsHeating Btu/H Unit accessory model numbers Hydronic heat options Maintenance Procedures MaintenanceRefrigeration System Service MaintenanceLeak Testing Maintenance BrazingHigh Temperatures Use of Pressure Regulator Valves GaugesEvacuation Procedure Maintenance EvacuationFan Motor Overheat Charging the System Charging ProcedureRefrigerant Line Piercing ValvesThermometers Maintenance Cooling Performance TestSling Psychrometer Cooling Performance TestCalculating procedure Heating Power Consumption TestTesting Capacitor Resistance Resistance CheckGround Test Heater Assembly with Power OFF to the Unit and HeaterResistance Test Indoor Coil and Air ThermistorsRmin Rnom Rmax Thermistor indoor coil ResistanceComponent Replacement Power Cord RemovalUnit Disassembly Procedures Power cord InstallationRemoving the Outdoor Coil and Outdoor Air Thermistors Control Board Replacement Procedure Hazardous VoltageIndoor Fan and Motor Outdoor Fan and MotorDiagnostics TroubleshootingCompressor output does not energize TroubleshootingIndoor/remote fan outputs do not energize Outdoor fan output does not energizeReversing valve output does not energize Random restart timer ExplanationAuxiliary heat output does not energize Ventilation output does not energizeSymptom Output on when the mode is offCondensate pump does not energize Control fuse is blownAIR Coil Wiring DiagramPVD Wiring DiagramWiring diagram 07 models PVD Energy management system Full 1st Year Warranty WarrantyFull 2nd 5th Sealed System Warranty Limited 2nd through 5th Year Functional Parts WarrantyPage PTAC-SVX01C-EN

PTAC-SVX01C-EN specifications

The Trane PTAC-SVX01C-EN is a cutting-edge Packaged Terminal Air Conditioner (PTAC) designed to provide optimal temperature control, energy efficiency, and user comfort in a variety of settings, including hotels, apartments, and office buildings. This unit stands out with its robust features and advanced technologies, making it a reliable choice for meeting diverse heating and cooling needs.

At the heart of the Trane PTAC-SVX01C-EN is its innovative design, which combines powerful performance with quiet operation. This unit utilizes a high-efficiency compressor that ensures rapid cooling and heating, providing ideal comfort regardless of the external climate. With a capacity range suitable for smaller spaces, the PTAC delivers strong performance while maintaining energy efficiency, thus reducing operational costs over time.

One of the key characteristics of the PTAC-SVX01C-EN is its user-friendly interface. The intuitive controls allow users to effortlessly adjust temperature settings, fan speeds, and modes of operation, including cooling, heating, and fan only. This flexibility enhances user comfort while optimizing energy consumption. Additionally, the unit features a programmable timer, enabling users to schedule operation according to their specific needs, further conserving energy when spaces are unoccupied.

The unit's Quiet Operation Technology minimizes noise levels, making it an ideal choice for environments where peace and quiet are paramount. This feature is particularly beneficial in hospitality settings, where guests expect a tranquil atmosphere. The PTAC is engineered to provide ample airflow while minimizing sound, creating a pleasant indoor environment.

Another standout feature of the Trane PTAC-SVX01C-EN is its advanced air filtration system. The integrated filter effectively captures dust, allergens, and other airborne particles, promoting a cleaner and healthier living environment. This is particularly essential for individuals with allergy sensitivities or respiratory issues.

Durability is also a hallmark of the PTAC-SVX01C-EN. Built with high-quality materials, it is designed to withstand the demands of continuous operation while requiring minimal maintenance. The unit's sleek and compact design allows for easy installation in various locations, ensuring versatility without sacrificing performance.

In summary, the Trane PTAC-SVX01C-EN represents a perfect blend of efficiency, comfort, and innovative technology. Its user-friendly controls, quiet operation, and advanced air filtration make it a leading choice for those seeking reliable climate control solutions in residential and commercial spaces alike. Whether for heating or cooling, the Trane PTAC-SVX01C-EN is engineered to deliver exceptional performance and lasting dependability.