Trane PTAC-SVX01C-EN Charging the System, Charging Procedure, Refrigerant, Line Piercing Valves

Page 34

Maintenance

4.Start the vacuum pump and open the shut-off valve to the high vacuum gauge manifold only. After the compound gauge (low side) has dropped to approximately 29 inches of vacuum, open the valve to the vacuum thermocouple gauge. See that the vacuum pump will bank-off to a minimum of 50 microns. A high vacuum pump can only produce a good vacuum if its oil is not contaminated.

5.If the vacuum pump is working properly, close the valve to the vacuum thermocouple gauge and open the high and low side valves or the high vacuum manifold set. With the valve on the charging cylinder closed, open the manifold valve to the cylinder.

6.Evacuate the system to at least 29 inches gauge before opening valve to thermocouple vacuum gauge.

7.Continue to evacuate to a minimum of 250 microns. Close valve pump and watch rate of rise. If vacuum does not rise above 1500 microns in three minutes, system can be considered properly evacuated.

8.If thermocouple vacuum gauge continues to rise and levels off at about 5000 microns, moisture and non-condensables are still present. A leak is present if the gauge continues to rise. Repair and re-evacuate.

9.Close valve to the thermocouple vacuum gauge and vacuum pump. Shut off pump and prepare to charge.

Charging the System

Charge the system with the exact amount of refrigerant. Refer to the unit nameplate for the correct refrigerant charge. An inaccurately charged system will cause future problems.

Charging Procedure

1.When using an ambient- compensated calibrated charging cylinder, allow liquid refrigerant only to enter the high side.

2.After the system receives all the refrigerant it requires, close close the valve on the high side of the manifold.

3.Start the system and charge the balance of the refrigerant though the low side. Do not charge in a liquid form.

4.Close the low side valve on the manifold and pinch-off both process tubes. Remove the manifold set. Crimp shut the open ends of the process tubes and braze.

5.Recheck for refrigerant leaks.

Refrigerant

Do not use a refrigerant other than that shown on the unit nameplate. Follow all precautionary measures recommended by the refrigerant manufacturers.

Line Piercing Valves

Line piercing valves may be used for diagnosis but are not suitable for evacuating or charging due to the minute holes pierced in the tubing.

Line piercing valves must not be left on the refrigerant system. The connection between the valve and the refrigerant tubing is not hermetically sealed and will eventually leak.

Open Lines

Never leave refrigerant lines open to the atmosphere when processing the refrigeration system. Water vapor may enter the lines and cause improper evacuation.

Operating Test

The final step in a successful repair is an accurate operating test. Follow the cooling and heating performance tests on pages 36 - 37 to make sure the product is performing to design standards.

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

Place discharge and inlet air thermostats

Place inlet thermostat in center of grille

Figure 24. Proper placement of discharge and inlet air thermostats

34

PTAC-SVX01C-EN

Image 34
Contents Packaged Terminal Air Conditioner Table of Contents Model Number Description E E 0 9 0 1 * a aOverview of Manual General InformationImportant Environmental Concerns Responsible Refrigerant PracticesGeneral Information Checklist Pre-InstallationPre-Installation Considerations Fire HazardReceiving and Handling Pre-InstallationReceiving Checklist Shipping PackageUnit Dimensions Unit with wall sleeve and subbase accessory Wall SleeveUnit Dimensions Air dischargeLive Electrical Components InstallationElectrical Requirements Installation Power receptacle configurationsHazardous Voltage w Installation ProcedureRemove rear closure Panel from wall sleeveInstall unit power supply BottomOption Install the unit controlsVoltage Options Accessory Accessory part number 115V 265 OptionSpecification Wiring VoltageWire External Interface Size LengthOutput settings Configure the display module settingsField commissioning support Programmable Settings Set point configurationSelection Unit Display Measure Example IP English Display unitsSetpoint limiting SI MetricEnergy Management System Indoor fan cycle configurationOccupancy arbitration for energy management Off 10 sec Ptee manual test sequencePthe manual test sequence Off 20 secOperation Sequence of OperationVent Control OperationRemote Fan Operation Air Discharge GrilleAir conditioner performance data Electric heat Data Heater size Heat pump performanceVoltage 208 230 265 Cooling data Btu/HCooling temperature change heat pumps Cooling temperature change air conditionersCooling amperage air conditioners Cooling amperage heat pumpsVoltage 208 230 265 Heating total wattage input heat pumpsHeating Btu/H Unit accessory model numbers Hydronic heat options Maintenance Maintenance ProceduresMaintenance Refrigeration System ServiceHigh Temperatures Maintenance BrazingLeak Testing Use of Pressure Regulator Valves GaugesEvacuation Procedure Maintenance EvacuationFan Motor Overheat Refrigerant Charging ProcedureCharging the System Line Piercing ValvesSling Psychrometer Maintenance Cooling Performance TestThermometers Cooling Performance TestTesting Capacitor Resistance Heating Power Consumption TestCalculating procedure Resistance CheckResistance Test Heater Assembly with Power OFF to the Unit and HeaterGround Test Indoor Coil and Air ThermistorsThermistor indoor coil Resistance Rmin Rnom RmaxUnit Disassembly Procedures Power Cord RemovalComponent Replacement Power cord InstallationIndoor Fan and Motor Control Board Replacement Procedure Hazardous VoltageRemoving the Outdoor Coil and Outdoor Air Thermistors Outdoor Fan and MotorTroubleshooting DiagnosticsIndoor/remote fan outputs do not energize TroubleshootingCompressor output does not energize Outdoor fan output does not energizeAuxiliary heat output does not energize Random restart timer ExplanationReversing valve output does not energize Ventilation output does not energizeCondensate pump does not energize Output on when the mode is offSymptom Control fuse is blownWiring Diagram AIR CoilWiring Diagram PVDWiring diagram 07 models PVD Energy management system Full 2nd 5th Sealed System Warranty WarrantyFull 1st Year Warranty Limited 2nd through 5th Year Functional Parts WarrantyPage PTAC-SVX01C-EN

PTAC-SVX01C-EN specifications

The Trane PTAC-SVX01C-EN is a cutting-edge Packaged Terminal Air Conditioner (PTAC) designed to provide optimal temperature control, energy efficiency, and user comfort in a variety of settings, including hotels, apartments, and office buildings. This unit stands out with its robust features and advanced technologies, making it a reliable choice for meeting diverse heating and cooling needs.

At the heart of the Trane PTAC-SVX01C-EN is its innovative design, which combines powerful performance with quiet operation. This unit utilizes a high-efficiency compressor that ensures rapid cooling and heating, providing ideal comfort regardless of the external climate. With a capacity range suitable for smaller spaces, the PTAC delivers strong performance while maintaining energy efficiency, thus reducing operational costs over time.

One of the key characteristics of the PTAC-SVX01C-EN is its user-friendly interface. The intuitive controls allow users to effortlessly adjust temperature settings, fan speeds, and modes of operation, including cooling, heating, and fan only. This flexibility enhances user comfort while optimizing energy consumption. Additionally, the unit features a programmable timer, enabling users to schedule operation according to their specific needs, further conserving energy when spaces are unoccupied.

The unit's Quiet Operation Technology minimizes noise levels, making it an ideal choice for environments where peace and quiet are paramount. This feature is particularly beneficial in hospitality settings, where guests expect a tranquil atmosphere. The PTAC is engineered to provide ample airflow while minimizing sound, creating a pleasant indoor environment.

Another standout feature of the Trane PTAC-SVX01C-EN is its advanced air filtration system. The integrated filter effectively captures dust, allergens, and other airborne particles, promoting a cleaner and healthier living environment. This is particularly essential for individuals with allergy sensitivities or respiratory issues.

Durability is also a hallmark of the PTAC-SVX01C-EN. Built with high-quality materials, it is designed to withstand the demands of continuous operation while requiring minimal maintenance. The unit's sleek and compact design allows for easy installation in various locations, ensuring versatility without sacrificing performance.

In summary, the Trane PTAC-SVX01C-EN represents a perfect blend of efficiency, comfort, and innovative technology. Its user-friendly controls, quiet operation, and advanced air filtration make it a leading choice for those seeking reliable climate control solutions in residential and commercial spaces alike. Whether for heating or cooling, the Trane PTAC-SVX01C-EN is engineered to deliver exceptional performance and lasting dependability.