Maintenance

Maintenance Procedures

Perform the following maintenance procedures to ensure proper unit operation.

WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

Chassis

Clean the chassis every four months or more often as the atmospheric conditions require. Use water and detergent to clean the basepan, center partition and coils.

Using harsh cleaning materials may cause a deterioration of the coil fins or end plates.

Do not use a high pressure cleaner as it could cause severe damage to the PTAC fins and coils.

Note: It is very important to not get any of the electronic parts wet.

A hose is okay to use to clean the coils, but make sure to cover the control with a blanket or plastic bag to prevent it from getting wet.

Wall Sleeve

Clean the wall sleeve every four months or more often as the atmospheric conditions require.

Remove any debris from the bottom of the panel, and from around any internal or external drain kit accessory item prior to using water or detergent. This will ensure that no debris clogs up the drain holes.

The use of harsh cleaning materials may cause a deterioration of the bottom panel over time. Do not use a high pressure cleaner because it could spray the side or top panel insulation material and cause future air quality problems like mold and mildew.

Clean side and top panel insulation material with a lint brush or piece of tape. Press tape against insulation lightly and slowly peel away to remove dirt and debris.

Compressor/Fan Motor

The compressor and fan motor are hermetically sealed, permanently lubricated, and require no additional oiling.

Cabinet Front

The cabinet front and discharge air grille can be cleaned with a mild soap or detergent.

Under NO circumstances should hydrocarbon based cleaners (e.g. acetone, benzene, naphtha gasoline, etc.) be used to clean the front or air grilles.

Use care when cleaning the control area. Do not use an excessively wet cleaning cloth.

Intake Air Filter

The intake air filter and vent door filter are both constructed of durable polypropylene. Clean filters monthly to ensure proper unit operation.

The fan must be off before the filters are cleaned.

To remove the air filters, grasp the top of the filter and lift out of the front cabinet (Figure 19.) Reverse the procedure to reinstall the filters.

Figure 19. Intake air filter removal is through top of unit. Inspect and clean filters monthly for proper unit operation.

Vent Filter

Before cleaning the vent filter, disconnect power to the unit by unplugging the power cord at the wall outlet or subbase, or disconnect power at the fuse box or circuit breaker. If unit is operated with vent door closed, the vent filter does not need to be cleaned.

1.Remove the cabinet front as described in front removal.

2.Remove the six screws securing the chassis to the wall sleeve with a Phillips-Head screwdriver.

3.Slide the chassis out of the wall sleeve far enough so that the vent filter is accessible as shown in Figure 20.

4.Remove the vent filter by unscrewing the two screws at the top of the filter and gently pulling the filter away from the partition panel. Refer to Figure 21. The filter can be cleaned by running under a low pressure hose or sink faucet.

30

PTAC-SVX01C-EN

Image 30
Contents Packaged Terminal Air Conditioner Table of Contents Model Number Description E E 0 9 0 1 * a aOverview of Manual General InformationImportant Environmental Concerns Responsible Refrigerant PracticesGeneral Information Checklist Pre-InstallationPre-Installation Considerations Fire HazardReceiving and Handling Pre-InstallationReceiving Checklist Shipping PackageUnit Dimensions Unit with wall sleeve and subbase accessory Wall SleeveUnit Dimensions Air dischargeInstallation Live Electrical ComponentsElectrical Requirements Installation Power receptacle configurationsHazardous Voltage w Installation ProcedureRemove rear closure Panel from wall sleeveInstall unit power supply BottomOption Install the unit controlsVoltage Options Accessory Accessory part number 115V 265 OptionSpecification Wiring VoltageWire External Interface Size LengthConfigure the display module settings Output settingsField commissioning support Programmable Settings Set point configurationSelection Unit Display Measure Example IP English Display unitsSetpoint limiting SI MetricIndoor fan cycle configuration Energy Management SystemOccupancy arbitration for energy management Off 10 sec Ptee manual test sequencePthe manual test sequence Off 20 secOperation Sequence of OperationVent Control OperationRemote Fan Operation Air Discharge GrilleAir conditioner performance data Electric heat Data Heater size Heat pump performanceVoltage 208 230 265 Cooling data Btu/HCooling temperature change heat pumps Cooling temperature change air conditionersCooling amperage air conditioners Cooling amperage heat pumpsHeating total wattage input heat pumps Voltage 208 230 265Heating Btu/H Unit accessory model numbers Hydronic heat options Maintenance Maintenance ProceduresMaintenance Refrigeration System ServiceHigh Temperatures Maintenance BrazingLeak Testing Use of Pressure Regulator Valves GaugesMaintenance Evacuation Evacuation ProcedureFan Motor Overheat Refrigerant Charging ProcedureCharging the System Line Piercing ValvesSling Psychrometer Maintenance Cooling Performance TestThermometers Cooling Performance TestTesting Capacitor Resistance Heating Power Consumption TestCalculating procedure Resistance CheckResistance Test Heater Assembly with Power OFF to the Unit and HeaterGround Test Indoor Coil and Air ThermistorsThermistor indoor coil Resistance Rmin Rnom RmaxUnit Disassembly Procedures Power Cord RemovalComponent Replacement Power cord InstallationIndoor Fan and Motor Control Board Replacement Procedure Hazardous VoltageRemoving the Outdoor Coil and Outdoor Air Thermistors Outdoor Fan and MotorTroubleshooting DiagnosticsIndoor/remote fan outputs do not energize TroubleshootingCompressor output does not energize Outdoor fan output does not energizeAuxiliary heat output does not energize Random restart timer ExplanationReversing valve output does not energize Ventilation output does not energizeCondensate pump does not energize Output on when the mode is offSymptom Control fuse is blownWiring Diagram AIR CoilWiring Diagram PVDWiring diagram 07 models PVD Energy management system Full 2nd 5th Sealed System Warranty WarrantyFull 1st Year Warranty Limited 2nd through 5th Year Functional Parts WarrantyPage PTAC-SVX01C-EN

PTAC-SVX01C-EN specifications

The Trane PTAC-SVX01C-EN is a cutting-edge Packaged Terminal Air Conditioner (PTAC) designed to provide optimal temperature control, energy efficiency, and user comfort in a variety of settings, including hotels, apartments, and office buildings. This unit stands out with its robust features and advanced technologies, making it a reliable choice for meeting diverse heating and cooling needs.

At the heart of the Trane PTAC-SVX01C-EN is its innovative design, which combines powerful performance with quiet operation. This unit utilizes a high-efficiency compressor that ensures rapid cooling and heating, providing ideal comfort regardless of the external climate. With a capacity range suitable for smaller spaces, the PTAC delivers strong performance while maintaining energy efficiency, thus reducing operational costs over time.

One of the key characteristics of the PTAC-SVX01C-EN is its user-friendly interface. The intuitive controls allow users to effortlessly adjust temperature settings, fan speeds, and modes of operation, including cooling, heating, and fan only. This flexibility enhances user comfort while optimizing energy consumption. Additionally, the unit features a programmable timer, enabling users to schedule operation according to their specific needs, further conserving energy when spaces are unoccupied.

The unit's Quiet Operation Technology minimizes noise levels, making it an ideal choice for environments where peace and quiet are paramount. This feature is particularly beneficial in hospitality settings, where guests expect a tranquil atmosphere. The PTAC is engineered to provide ample airflow while minimizing sound, creating a pleasant indoor environment.

Another standout feature of the Trane PTAC-SVX01C-EN is its advanced air filtration system. The integrated filter effectively captures dust, allergens, and other airborne particles, promoting a cleaner and healthier living environment. This is particularly essential for individuals with allergy sensitivities or respiratory issues.

Durability is also a hallmark of the PTAC-SVX01C-EN. Built with high-quality materials, it is designed to withstand the demands of continuous operation while requiring minimal maintenance. The unit's sleek and compact design allows for easy installation in various locations, ensuring versatility without sacrificing performance.

In summary, the Trane PTAC-SVX01C-EN represents a perfect blend of efficiency, comfort, and innovative technology. Its user-friendly controls, quiet operation, and advanced air filtration make it a leading choice for those seeking reliable climate control solutions in residential and commercial spaces alike. Whether for heating or cooling, the Trane PTAC-SVX01C-EN is engineered to deliver exceptional performance and lasting dependability.