12. DUCTS AND REGISTER MEASUREMENTS
|
|
|
| (sample calculations) |
|
| |||
| SIMPLIFIED METHOD |
|
| WARM AIR SYSTEM INSTALLATION |
| ||||
| DISTRIBUTION SYSTEM |
|
|
|
|
| |||
| Ducts size (heat) |
|
|
|
| HOUSE DIMENSIONS |
|
| |
|
|
|
|
| Example: 28 x 40 bungalow: 1,120 sq. ft. |
|
| ||
| 4 inch outlet | reduce by 1” |
|
|
|
|
| ||
|
|
|
|
|
|
| |||
| 5 inch outlet | reduce by 2” | Always by 8” thick |
|
| 28 x 40 x 8: 8,960 cu. ft. x 1.8 Ch. air/hr: | 16,128 Btu |
| |
|
|
|
|
|
| ||||
| 6 inch outlet | reduce by 3” |
|
|
| Exposed walls: |
|
| |
| N.B.: The main duct must | be reduced every 2 |
|
| 40 + 40 + 28 + 28: 136 x 8: 1,088 cu. ft. x 22: | 23,936 Btu |
| ||
| outlets. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Number of windows: |
|
|
|
|
|
|
|
|
| 12 of 3 x 4: 144 x 60: | 8,640 Btu |
|
| Ducts specifications (heat) |
|
|
|
| ||||
|
|
|
| Number of doors: |
|
| |||
| Dimensions | Length Elbow | Average equivalence |
|
|
|
| ||
|
|
| 2 x 3 x 7: 42 x 100: | 4,200 Btu |
| ||||
| 4” | 10’ | 1 x 90o | Max 4,000 Btu |
|
|
| ||
| 5” | 10’ | 1 x 90o | Max 6,000 Btu |
|
|
| 52,904 Btu |
|
| 6” | 10’ | 1 x 90o | Max 7,000 Btu |
|
|
|
|
|
|
|
|
|
|
|
| Insulated basement: 15% | 7,906 Btu |
|
|
|
|
|
|
|
| or 54 Btu per sq. ft. | 60,840 Btu |
|
|
|
|
|
|
| ||||
| DAMPER |
|
|
|
|
| FOR ELECTRIC ELEMENTS 80%:48,672 Btu or 14,28 kW |
| |
|
|
|
|
|
|
| TO BE ADDED:House 1 1/2 floor = 25% |
|
|
| For a 4” warm air outlet: 2” x 10” damper |
|
| House 2 floors = 40% |
|
| |||
|
|
|
|
|
| ||||
| For a 5” warm air outlet: 2” x 12” damper or 4” x 10” |
|
|
|
|
| |||
|
|
| BEDROOM (for example: 12 x 12) |
|
| ||||
| For a 6” warm air outlet: 2” x 14” damper or 4” x 12” |
|
|
|
| ||||
|
|
| 12 x 12 x 8: 1,152 cu. ft. x 1.8 Ch. air/hr: | 2,074 Btu |
| ||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Exposed walls: |
|
|
|
|
|
|
|
|
| 12 + 12 x 8: 192 x 22: | 4,224 Btu |
|
|
|
|
|
|
|
| Windows: |
|
|
|
|
|
|
|
|
| 3 x 4 x 60 | 720 Btu |
|
|
|
|
|
|
|
|
| 7,018 Btu |
|
|
|
|
|
|
|
|
|
|
|