12. DUCTS AND REGISTER MEASUREMENTS

 

 

 

 

(sample calculations)

 

 

 

SIMPLIFIED METHOD

 

 

WARM AIR SYSTEM INSTALLATION

 

 

DISTRIBUTION SYSTEM

 

 

 

 

 

 

Ducts size (heat)

 

 

 

 

HOUSE DIMENSIONS

 

 

 

 

 

 

 

Example: 28 x 40 bungalow: 1,120 sq. ft.

 

 

 

4 inch outlet

reduce by 1”

 

 

 

 

 

 

 

 

 

 

 

 

 

5 inch outlet

reduce by 2”

Always by 8” thick

 

 

28 x 40 x 8: 8,960 cu. ft. x 1.8 Ch. air/hr:

16,128 Btu

 

 

 

 

 

 

 

 

6 inch outlet

reduce by 3”

 

 

 

Exposed walls:

 

 

 

N.B.: The main duct must

be reduced every 2

 

 

40 + 40 + 28 + 28: 136 x 8: 1,088 cu. ft. x 22:

23,936 Btu

 

 

outlets.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of windows:

 

 

 

 

 

 

 

 

 

12 of 3 x 4: 144 x 60:

8,640 Btu

 

 

Ducts specifications (heat)

 

 

 

 

 

 

 

 

Number of doors:

 

 

 

Dimensions

Length Elbow

Average equivalence

 

 

 

 

 

 

 

2 x 3 x 7: 42 x 100:

4,200 Btu

 

 

4”

10’

1 x 90o

Max 4,000 Btu

 

 

 

 

5”

10’

1 x 90o

Max 6,000 Btu

 

 

 

52,904 Btu

 

 

6”

10’

1 x 90o

Max 7,000 Btu

 

 

Non-insulated basement: 25%

 

 

 

 

 

 

 

 

 

Insulated basement: 15%

7,906 Btu

 

 

 

 

 

 

 

 

or 54 Btu per sq. ft.

60,840 Btu

 

 

 

 

 

 

 

 

DAMPER

 

 

 

 

 

FOR ELECTRIC ELEMENTS 80%:48,672 Btu or 14,28 kW

 

 

 

 

 

 

 

 

TO BE ADDED:House 1 1/2 floor = 25%

 

 

 

For a 4” warm air outlet: 2” x 10” damper

 

 

House 2 floors = 40%

 

 

 

 

 

 

 

 

 

For a 5” warm air outlet: 2” x 12” damper or 4” x 10”

 

 

 

 

 

 

 

 

BEDROOM (for example: 12 x 12)

 

 

 

For a 6” warm air outlet: 2” x 14” damper or 4” x 12”

 

 

 

 

 

 

 

12 x 12 x 8: 1,152 cu. ft. x 1.8 Ch. air/hr:

2,074 Btu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exposed walls:

 

 

 

 

 

 

 

 

 

12 + 12 x 8: 192 x 22:

4,224 Btu

 

 

 

 

 

 

 

 

Windows:

 

 

 

 

 

 

 

 

 

3 x 4 x 60

720 Btu

 

 

 

 

 

 

 

 

 

7,018 Btu

 

 

 

 

 

 

 

 

 

 

 

30

Image 30
Contents WOOD Stove Builder International Inc 1700, Léon-HarmelQuébecQuébec G1N 4R9 COMBINED ELECTRICTable of contents 11. TROUBLESHOOTING LIMITED LIFETIME WARRANTY12. DUCTS AND REGISTER MEASUREMENTS 1.CHIMNEY AND DRAFT 2. SAFETY RULESINTRODUCTION GENERAL REQUIREMENTSDONOT MANIPULATE WITH BARE HANDS W A R N I N GTHEASH DRAWER GET VERY HOT ODOUR FROM THE PAINTSMOKE DETECTOR 3. APPLIANCE INSTALLATIONThe drawer must be cleaned regularly ASH DRAWER24” both sides for PSG5000 PIPE CONNECTOR AND DAMPERCLEARANCES TO COMBUSTIBLE MATERIALS WOOD FLUE PIPEDAMPER PROPER INSTALLATIONUNPROPER INSTALLATION COMBUSTION AIRWOOD ONLY WARNING USE FEEDING WIRES SUITABLE FOR 75OCELECTRICAL CONNECTION WOOD/ELECTRICELECTRIC ELEMENT Red button manual reset Thermodisk L-170WARNING USE FEEDING WIRES SUITABLE FOR 75OC INSIDE VIEW OF THE ELECTRIC ELEMENTTHERMOSTAT FAN CONTROLOUTSIDE VIEW OF THE ELECTRIC ELEMENT LIGHTING 4. OPERATING INSTRUCTIONSControl system PREHEATINGHEATING PROCEDURE TO OPEN THE LOADING DOORexcept for lighting and maintenance EARLY SIGNS OF OVERFIRED FURNACECHIMNEY FIRES LOCAL FIRE DEPARTMENTMAINTENANCE OF THE BLOWER MOTOR 5. MAINTENANCEMAINTENANCE OF THE EXCHANGERS CHIMNEY MAINTENANCEFILTERS 6. REPLACEMENT PARTSDOOR GASKET MAINTENANCE GASKETTHERMINAL 7. ELECTRIC DIAGRAMS FOR UNITS BUILT FROMWOOD-ONLYFURNACES BOARDWOOD/ELECTRIC FURNACES 15 KW @ 30KW2 SPEED PSG5000 WOOD-ONLYFURNACESBLOWER MOTORPSG5000 WOOD/ELECTRIC FURNACES 20 KW @ 30KW20 KW @ 30KW WOOD ONLY FURNACES PSG 8. ELECTRIC DIAGRAMS FOR UNITS BUILT BEFORESWITCH BLOWERMOTOR WOOD ONLY FURNACES PSGBLOWER 1 SPEEDWOOD/ELECTRIC FURNACES PSG 15 KW @ 30KW20 KW @ 30KW COMMAND WOOD/ELECTRIC FURNACES PSG 5000 40KW @ 60KW20 KW @ 30KW WOOD ONLY FURNACES PSG TERMINALBOARD BLOWERWOOD/ELECTRIC FURNACES PSG 15 KW @ 30KW9. TECHNICAL SPECIFICATIONS RESIDENTIAL AREA COMMERCIAL AREA11. TROUBLESHOOTING IMPORTANT NOTEExposed walls 12. DUCTS AND REGISTER MEASUREMENTSDAMPER N.B. The main duct must1700, rue Léon-Harmel,Québec Québec G1N 4R9 LIMITED LIFETIME WARRANTYWARRANTY APPLICATION tel. 418 527-3060fax