PROPER INSTALLATION

For a proper installation, follow the advices below:

1. All the joints of the evacuation pipe must be secured, using three screws.

Make sure that each screw goes through the inner walls of both connectors (male and female). See pictures below showing a male-female coupling.

PROPER INSTALLATION

UNPROPER INSTALLATION

CAUSE RESTRICTION

2. A minimum rise of 1/4 inch per horizontal foot must be respected.

DAMPER

The barometric control must be adjusted so that the maximum draft measured at the furnace outlet is limited to -0.06 in. w.c. Please note that a draft higher than -0.06 in. H2O could result in an uncontrollable fire. On the other hand, the minimum draft to be respected is -0.04 in. w.c. in the evacuation pipe on the solid fuel side, no matter what type of furnace.

COMBUSTION AIR

In the event that the furnace and the chimney are completely cold, it might be necessary before lighting, to provide fresh air by opening a door or a window for a few minutes.

Take note that a house constructed or renovated in order to be airtight is liable to lack fresh air which is necessary for a proper combustion and a proper operation of heating units.

In such a case, when starting up the fire, do not operate appliances which evacuate air outside the house such as:

-Range hood

-Air exchanger

-Cloths dryer

-Bathroom fan

-Ventilated central vacuum system

8

Image 8
Contents Stove Builder International Inc 1700, Léon-Harmel QuébecQuébec G1N 4R9WOOD COMBINED ELECTRICTable of contents 12. DUCTS AND REGISTER MEASUREMENTS 11. TROUBLESHOOTINGLIMITED LIFETIME WARRANTY 2. SAFETY RULES INTRODUCTION1.CHIMNEY AND DRAFT GENERAL REQUIREMENTSW A R N I N G THEASH DRAWER GET VERY HOTDONOT MANIPULATE WITH BARE HANDS ODOUR FROM THE PAINT3. APPLIANCE INSTALLATION The drawer must be cleaned regularlySMOKE DETECTOR ASH DRAWERPIPE CONNECTOR AND DAMPER CLEARANCES TO COMBUSTIBLE MATERIALS24” both sides for PSG5000 WOOD FLUE PIPEPROPER INSTALLATION UNPROPER INSTALLATIONDAMPER COMBUSTION AIRWARNING USE FEEDING WIRES SUITABLE FOR 75OC ELECTRICAL CONNECTIONWOOD ONLY WOOD/ELECTRICRed button manual reset Thermodisk L-170 WARNING USE FEEDING WIRES SUITABLE FOR 75OCELECTRIC ELEMENT INSIDE VIEW OF THE ELECTRIC ELEMENTOUTSIDE VIEW OF THE ELECTRIC ELEMENT THERMOSTATFAN CONTROL 4. OPERATING INSTRUCTIONS Control systemLIGHTING PREHEATINGPROCEDURE TO OPEN THE LOADING DOOR except for lighting and maintenanceHEATING EARLY SIGNS OF OVERFIRED FURNACECHIMNEY FIRES LOCAL FIRE DEPARTMENT5. MAINTENANCE MAINTENANCE OF THE EXCHANGERSMAINTENANCE OF THE BLOWER MOTOR CHIMNEY MAINTENANCE6. REPLACEMENT PARTS DOOR GASKET MAINTENANCEFILTERS GASKET7. ELECTRIC DIAGRAMS FOR UNITS BUILT FROM WOOD-ONLYFURNACESTHERMINAL BOARDWOOD/ELECTRIC FURNACES 15 KW @ 30KWPSG5000 WOOD-ONLYFURNACES BLOWER2 SPEED MOTOR20 KW @ 30KW PSG5000 WOOD/ELECTRIC FURNACES20 KW @ 30KW 8. ELECTRIC DIAGRAMS FOR UNITS BUILT BEFORE SWITCHWOOD ONLY FURNACES PSG BLOWERWOOD ONLY FURNACES PSG BLOWERMOTOR 1 SPEEDWOOD/ELECTRIC FURNACES PSG 15 KW @ 30KW20 KW @ 30KW 20 KW @ 30KW COMMANDWOOD/ELECTRIC FURNACES PSG 5000 40KW @ 60KW TERMINAL BOARDWOOD ONLY FURNACES PSG BLOWERWOOD/ELECTRIC FURNACES PSG 15 KW @ 30KW9. TECHNICAL SPECIFICATIONS RESIDENTIAL AREA COMMERCIAL AREA11. TROUBLESHOOTING IMPORTANT NOTE12. DUCTS AND REGISTER MEASUREMENTS DAMPERExposed walls N.B. The main duct mustLIMITED LIFETIME WARRANTY WARRANTY APPLICATION1700, rue Léon-Harmel,Québec Québec G1N 4R9 tel. 418 527-3060fax