D9412GV2/D7412GV2 Operation and Installation Guide 6.0 Power Outputs

6.4.2Terminals 6 and 7

When activated, Terminals 6 (Relay A) and 7 (Relay B), provide positive (+) 10.2 VDC to 13.9 VDC power output. Use the power at Terminals 6 and 7 to power bells, siren drivers, piezoelectric fire sounders, electronic horns, or other devices.

Programming determines the format of the output and the conditions that activate it. One PTC protects Terminals 6, 7, and 8 against shorts.

Available Power

The system combines the 1.4 A of primary power produced by the power supply with the secondary power source (the battery) to produce a total of 2.0 A of alarm power at 10.2 VDC to 13.9 VDC. Terminals 6 and 7 share the available alarm power.

Power Restricted for Fire and Combined Fire and Burglary Systems: Fire systems are prohibited from using the battery for determining alarm power. Use the fire system power formula that follows to calculate the current available for fire and combined fire and burglary systems.

6.4.3Fire System Power Formula

To calculate the current available at Terminals 6 and 7 for fire and combined fire and burglary systems:

1.Add together the current draws for all devices connected to Terminals 3, 8, 24, and 32, and the accessory connector. This is the total current required for the normal standby condition (NSC).

2.The current available for NSC is 1.4 A. Subtract the NSC current required calculated in Step 1 from the NSC current available, 1.4 A. The difference is the alarm current available for Terminals 6 and 7.

In formula format:

1.4 A NSC current required

= Alarm current

(Step 1)

available

Refer to the D9412GV2/D7412GV2 Approved Applications Compliance Guide (P/N: F01U003639) for module or accessory current requirements.

6.4.4Terminal 8

Terminal 8 provides continuous positive (+) 10.2 VDC to 13.9 VDC power. Relay C interrupts the power at Terminal 8 when activated. Use Terminal 8 to power smoke detectors or other devices that are reset by interrupting power. One self-resetting circuit breaker protects Terminals 6, 7, and 8 against shorts.

Verification/Reset Relay

The default program sets Relay C (Terminal 8) as a verification and reset relay. Refer to Relay Parameters and Point Assignments in the D9412GV2/D7412GV2 Program Entry Guide (P/N: F01U003636) for instructions on programming verification and reset relays and points.

Performing a sensor reset at a keypad produces a five- second relay activation of verification/reset relays. The control panel ignores verification/reset points during the five seconds.

26

Bosch Security Systems, Inc. 5/05 F01U003641B

Image 26
Contents Operation and Installation Guide D9412GV2/D7412GV2Listings and Approvals TrademarksCertifications and Approvals Federal Communications Commission FCC RulesBosch Security Systems, Inc /05 F01U003641B Contents D9412GV2/D7412GV2 Operation and Installation Guide Figures TablesIntroduction Related DocumentationEffects Precautions during InstallationLightning Strikes GV2 Series Control Panel Differences Configuration and PartsOverview Literature Pack Parts ListAssembly Parts Available by Separate OrderAccessories Compatible AccessoriesFeatures in the D9412GV2 and D7412GV2 Ground Fault Detection KeyswitchAccess Control Ground Fault Detection Added FeatureProgramming Other FeaturesNetCom Functions Enclosure Options InstallationInstallation Preparation Mounting EnclosureTerminals to earth ground Ground Fault Detect Enable Installing the Control PanelConnecting Earth Ground Terminal4 D9412GV2 and D7412GV2 Ground Fault Specifications Enabling Ground Fault DetectionGround Fault Detection Status Ground Fault ImpedanceCompleting the Installation Programming the Control Panel Installing the Point Chart LabelTesting the System Secondary Power Terminals Power SupplyPrimary Power Terminals 1 Installing the Battery Non-Power-Limited Wiring Replacing the BatteryBattery Discharge and Recharge Schedule Battery SupervisionBattery Charging Circuit Float Charge Charging Status and Low Battery LEDs Continuous Power Output Terminals 24, Power OutputsTotal Available Power Programmable Power Output Terminals 6, 7,Verification/Reset Relay Available PowerFire System Power Formula Terminals 6Notification Telephone ConnectionsRegistration LocationDialing Format Phone LED RedOperation Monitor LED Green Telephone Line MonitorOperation 11 D928 Dual Phone Line SwitcherDescription AC Power LED Installing the D928 MountingWiring Telephone ConnectionsPoint Sensor Loops On-Board PointsTerminals 11 to 22 Description Point ParametersPoint Response Time 3 4 5 Off-Board Points Point Zonex Bus D9412GV2 Terminals and D7412GV2 Terminals5 D9412GV2/D7412GV2 Responses to Missing Point Conditions Off-Board Point ErrorsD8125, D8127 and D9127 Popit Modules ListingsConnecting the D8125 Popex to the D9412GV2 Control Panel Connecting the D8125 Popex to the D7412GV2 Panel Wiring POPITs to the Data Expansion Loop Installing the D8125 Popex ModuleWiring the D8125 to the Control Panel Data Expansion Loop Wire SpecificationsPopit Module Point Assignments Wiring Data Expansion Loops to Popex ModulesPopit Sensor Loops D8128D OctoPOPIT Module Address Switches InstallationSetting the OctoPOPIT Switches Wiring OctoPOPITs D8128D OctoPOPIT Switch Settings for D9412GV2 and D7412GV2Point DIP Switches Mounting OctoPOPITsUsing the Terminal Strip Terminal Strip ConnectionsConnecting D8128D OctoPOPITs to the D9412GV2 First address on Zonex Bus Sensor loops Using Molex Connectors OctoPOPIT Sensor LoopsTesting Off-Board Points D8128D OctoPOPIT Sensor LoopsOff-Board Relays 10.1 D8129 OctoRelayRelay outputs can activate when you are Configuring the D8129 OctoRelayD8129 OctoRelay Switch Settings Setting the OctoRelay switches or10.2 D811 Arm Status Relay Module Wiring ConnectionsOutputs when you perform this function Number of D8128Ds Used with D8129sD811 for Relay On-board points D811 for Relay Keypad Terminals 29 to Arming DevicesDescription Wire Limits for Individual Keypads Extra Power for More KeypadsKeyswitch Maintained ContactMomentary Contact Silencing the Bell12.3 D9131A Parallel Printer Interface Module InstallationSDI Devices 12.4 D9210B Wiegand Control Interface ModuleAddress Settings AccessAddress Switch Settings for Access Control Module SDI AddressUsed as an External Modem Connecting the D9133DC12.6.1 D9133DC Direct Connect Programming Module Network Interface ModulesDX4020 DIP Switch Settings Programmer Access Reports Programmer and Accessory ConnectionsProgrammer Connector Accessory ConnectorFaceplates 14.1 D9412GV2 Faceplate14.2 D7412GV2 Faceplate D7412GV2Appendix a System Wiring Diagrams, Issue a D9412GV2 Control PanelD9412GV2 Popex D7412GV2, Power Supply Side D7412GV2 Control PanelD7412GV2, Input Points and Peripheral Devices UL Smoke Detector Compatibility P/N 33284 forD7412GV2, SDI Devices Appendix B Point Address Charts Zonex 1 Point Address ChartZonex 2 Point Address Chart Zonex 2, Points 129 to 247 D9412GV2 OnlySpecifications D9412GV2/D7412GV2 Program Entry Guide P/N F01U003636Bosch Security Systems, Inc /05 F01U003641B Bosch Security Systems F01U003641B
Related manuals
Manual 158 pages 17.38 Kb

D9412GV2 specifications

The Bosch D9412GV2 is an exceptional dishwasher that stands out in the competitive world of home appliances. Known for its reliability and advanced features, this model offers a blend of cutting-edge technology and user-friendly design that appeals to modern households.

One of the most noteworthy features of the D9412GV2 is its impressive cleaning performance. Boasting a unique combination of powerful jets and specialized wash cycles, it ensures that even the toughest stains are removed effectively. The dishwasher features Bosch’s patented PrecisionWash system, which utilizes intelligent sensors to monitor the wash cycle’s progress and adjust the water spray for optimal cleaning results. This not only guarantees sparkling dishes but also conserves water and energy.

In terms of capacity, the D9412GV2 does not disappoint. It has a spacious interior that is designed to accommodate up to 16 place settings, making it an ideal choice for families or those who frequently entertain guests. The adjustable racks and flexible loading options allow users to maximize space and customize the dishwasher to suit their unique needs. The third rack is particularly useful for utensils and smaller items, providing additional space that enhances efficiency.

The dishwasher is also engineered with noise reduction features for a quieter operation. With a sound rating of 44 decibels, it operates silently in the background, allowing for uninterrupted conversations and a peaceful home environment. This is especially beneficial for open-concept living spaces.

Energy efficiency is another hallmark of the Bosch D9412GV2. It is Energy Star certified, reflecting its commitment to sustainable practices. It uses less water and electricity without compromising performance, making it a responsible choice for eco-conscious consumers.

Moreover, the presence of the Home Connect feature allows users to control and monitor their dishwasher remotely via a smartphone app. This innovative technology enables users to start or stop cycles, receive notifications, and even download new wash programs, adding convenience and flexibility to busy lifestyles.

In conclusion, the Bosch D9412GV2 is a state-of-the-art dishwasher that excels in cleaning performance, capacity, and energy efficiency. With its innovative technologies and thoughtful design, it represents Bosch's commitment to quality and customer satisfaction, making it a valuable addition to any kitchen.