D9412GV2/D7412GV2 Operation and Installation Guide 10.0 Off-Board Relays

10.0Off-Board Relays

10.1D8129 OctoRelay

Use the D8129 OctoRelay to add relay outputs to the system in groups of eight. On the D9412GV2, up to 128 OctoRelay outputs (relay numbers 1 to 128) can be added to the system using 16 OctoRelays. D7412GV2 allows up to 64 relay outputs. Review Section 6.0 Power Outputs on page 25 to ensure that enough power is provided for the OctoRelays and other powered devices that are connected to the system.

OctoRelays for relay numbers 1 to 64 connect to Zonex 1, Terminal 28. OctoRelays for relay numbers 65 to 128 connect to Zonex 2 (D9412GV2 only), Terminal 26 on the D9412GV2. Refer to Figure 20 on this page and Figure 21 on page 49.

Alarm output, auxiliary relay, sensor reset, arming status, point status, alarm memory, or remote functions can be assigned to the OctoRelay outputs individually. Refer to Relay Parameters in the D9412GV2/D7412GV2 Program Entry Guide (P/N: F01U003635) for programming details.

D8129 Restricted for Fire Systems: D8129 relay outputs are not supervised and cannot be used in fire or combined fire and burglary installations for primary indicating devices.

Figure 20: D8129 Connections to the D9412GV2

2122

Reset Pin

Disable All Except Battery

Charging And Programming

PERIPHERAL DEVICE CONNECTIONS

RED

POWER +

32

YELLOW

DATA BUS A

31

GREEN

DATA BUS B

30

BLACK

COMMON

29

 

 

 

N.F.P.A.

ZONEX OUT 1

28

Style 3.5

 

 

Signaling

 

 

Line

 

27

Circuits

ZONEX IN 1

 

ZONEX OUT 2

26

 

ZONEX IN 2

25

 

ZONEX POWER +

24

 

ZONEX COMMON

23

Point 8

D5200/D5360

S3 Option

PROG CONN

Closed = 1KEOL

 

Normal Operation

 

Open =AB-12 UL

 

Bell Box 220 K

 

GRN

 

 

 

 

 

 

 

4

 

 

 

 

GND

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATA

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

3

4

5

6

7 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

3

GND

2

 

AUX

 

DATA

 

1 2 3 4 5 6 7 8

5

1 - D8129 OctoRelays for relay numbers 1 to 64. Connect OctoRelays in parallel.

2 - D8129 OctoRelays for relay numbers 65 to 128. Connect OctoRelays in parallel.

3 - Power limited

4 - Supervised, power limited

5 - On-board points

48

Bosch Security Systems, Inc. 5/05 F01U003641B

Image 48
Contents Operation and Installation Guide D9412GV2/D7412GV2Trademarks Certifications and ApprovalsListings and Approvals Federal Communications Commission FCC RulesBosch Security Systems, Inc /05 F01U003641B Contents D9412GV2/D7412GV2 Operation and Installation Guide Figures TablesIntroduction Related DocumentationPrecautions during Installation Lightning StrikesEffects Configuration and Parts OverviewGV2 Series Control Panel Differences Parts List AssemblyLiterature Pack Parts Available by Separate OrderAccessories Compatible AccessoriesFeatures in the D9412GV2 and D7412GV2 Keyswitch Access ControlGround Fault Detection Ground Fault Detection Added FeatureOther Features NetCom FunctionsProgramming Installation Installation PreparationEnclosure Options Mounting EnclosureInstalling the Control Panel Connecting Earth GroundTerminals to earth ground Ground Fault Detect Enable TerminalEnabling Ground Fault Detection Ground Fault Detection Status4 D9412GV2 and D7412GV2 Ground Fault Specifications Ground Fault ImpedanceCompleting the Installation Installing the Point Chart Label Testing the SystemProgramming the Control Panel Power Supply Primary Power Terminals 1Secondary Power Terminals Installing the Battery Non-Power-Limited Wiring Replacing the BatteryBattery Supervision Battery Charging Circuit Float ChargeBattery Discharge and Recharge Schedule Charging Status and Low Battery LEDs Power Outputs Total Available PowerContinuous Power Output Terminals 24, Programmable Power Output Terminals 6, 7,Available Power Fire System Power FormulaVerification/Reset Relay Terminals 6Telephone Connections RegistrationNotification LocationPhone LED Red Operation Monitor LED GreenDialing Format Telephone Line Monitor11 D928 Dual Phone Line Switcher DescriptionOperation Installing the D928 Mounting WiringAC Power LED Telephone ConnectionsOn-Board Points Terminals 11 to 22 DescriptionPoint Sensor Loops Point ParametersPoint Response Time 3 4 5 Off-Board Points Point Zonex Bus D9412GV2 Terminals and D7412GV2 TerminalsOff-Board Point Errors D8125, D8127 and D9127 Popit Modules5 D9412GV2/D7412GV2 Responses to Missing Point Conditions ListingsConnecting the D8125 Popex to the D9412GV2 Control Panel Connecting the D8125 Popex to the D7412GV2 Panel Installing the D8125 Popex Module Wiring the D8125 to the Control PanelWiring POPITs to the Data Expansion Loop Data Expansion Loop Wire SpecificationsWiring Data Expansion Loops to Popex Modules Popit Sensor LoopsPopit Module Point Assignments D8128D OctoPOPIT Module Installation Setting the OctoPOPIT SwitchesAddress Switches D8128D OctoPOPIT Switch Settings for D9412GV2 and D7412GV2 Point DIP SwitchesWiring OctoPOPITs Mounting OctoPOPITsUsing the Terminal Strip Terminal Strip ConnectionsConnecting D8128D OctoPOPITs to the D9412GV2 First address on Zonex Bus Sensor loops Using Molex Connectors OctoPOPIT Sensor LoopsTesting Off-Board Points D8128D OctoPOPIT Sensor LoopsOff-Board Relays 10.1 D8129 OctoRelayConfiguring the D8129 OctoRelay D8129 OctoRelay Switch SettingsRelay outputs can activate when you are Setting the OctoRelay switches orWiring Connections Outputs when you perform this function10.2 D811 Arm Status Relay Module Number of D8128Ds Used with D8129sD811 for Relay On-board points D811 for Relay Arming Devices DescriptionKeypad Terminals 29 to Wire Limits for Individual Keypads Extra Power for More KeypadsKeyswitch Maintained ContactMomentary Contact Silencing the BellInstallation SDI Devices12.3 D9131A Parallel Printer Interface Module 12.4 D9210B Wiegand Control Interface ModuleAccess Address Switch Settings for Access Control ModuleAddress Settings SDI AddressConnecting the D9133DC 12.6.1 D9133DC Direct Connect Programming ModuleUsed as an External Modem Network Interface ModulesDX4020 DIP Switch Settings Programmer and Accessory Connections Programmer ConnectorProgrammer Access Reports Accessory ConnectorFaceplates 14.1 D9412GV2 Faceplate14.2 D7412GV2 Faceplate D7412GV2Appendix a System Wiring Diagrams, Issue a D9412GV2 Control PanelD9412GV2 Popex D7412GV2, Power Supply Side D7412GV2 Control PanelD7412GV2, Input Points and Peripheral Devices UL Smoke Detector Compatibility P/N 33284 forD7412GV2, SDI Devices Appendix B Point Address Charts Zonex 1 Point Address ChartZonex 2 Point Address Chart Zonex 2, Points 129 to 247 D9412GV2 OnlySpecifications D9412GV2/D7412GV2 Program Entry Guide P/N F01U003636Bosch Security Systems, Inc /05 F01U003641B Bosch Security Systems F01U003641B
Related manuals
Manual 158 pages 17.38 Kb

D9412GV2 specifications

The Bosch D9412GV2 is an exceptional dishwasher that stands out in the competitive world of home appliances. Known for its reliability and advanced features, this model offers a blend of cutting-edge technology and user-friendly design that appeals to modern households.

One of the most noteworthy features of the D9412GV2 is its impressive cleaning performance. Boasting a unique combination of powerful jets and specialized wash cycles, it ensures that even the toughest stains are removed effectively. The dishwasher features Bosch’s patented PrecisionWash system, which utilizes intelligent sensors to monitor the wash cycle’s progress and adjust the water spray for optimal cleaning results. This not only guarantees sparkling dishes but also conserves water and energy.

In terms of capacity, the D9412GV2 does not disappoint. It has a spacious interior that is designed to accommodate up to 16 place settings, making it an ideal choice for families or those who frequently entertain guests. The adjustable racks and flexible loading options allow users to maximize space and customize the dishwasher to suit their unique needs. The third rack is particularly useful for utensils and smaller items, providing additional space that enhances efficiency.

The dishwasher is also engineered with noise reduction features for a quieter operation. With a sound rating of 44 decibels, it operates silently in the background, allowing for uninterrupted conversations and a peaceful home environment. This is especially beneficial for open-concept living spaces.

Energy efficiency is another hallmark of the Bosch D9412GV2. It is Energy Star certified, reflecting its commitment to sustainable practices. It uses less water and electricity without compromising performance, making it a responsible choice for eco-conscious consumers.

Moreover, the presence of the Home Connect feature allows users to control and monitor their dishwasher remotely via a smartphone app. This innovative technology enables users to start or stop cycles, receive notifications, and even download new wash programs, adding convenience and flexibility to busy lifestyles.

In conclusion, the Bosch D9412GV2 is a state-of-the-art dishwasher that excels in cleaning performance, capacity, and energy efficiency. With its innovative technologies and thoughtful design, it represents Bosch's commitment to quality and customer satisfaction, making it a valuable addition to any kitchen.