New Buck Corporation MODEL FP-327-ZC manual Page

Page 6
Manual background

Page 4

Image 6
Contents Manufacturer NEW BUCK CORPORATION P.O. Box MODEL FP-327-ZCNEW BUCK CORPORATION 8000 Highway 226 South Spruce Pine, NCPage TABLE OF CONTENTS Page SECTION I SAFETY INFORMATION WARNINGS Page Page GAS LINE SECTION ZERO CLEARANCE INSTALLATIONCHOOSING THE LOCATION FOR YOUR FIREPLACE DRAFTS7 1/2 Fireplace and Framing Dimensions inches3 1/4 PageInstall the Firebox INSTALLING THE FIREBOXFIREPLACE CLEARANCES Framing the FireboxFINISHING YOUR FIREPLACE CLEARANCESMANTEL 3/4 FLAT SURFACE MANTEL PROFILES FOR ZERO CLEARANCE CABINETMUST BE FOLLOWED MANTEL 3/4 FLAT SURFACEINSTALLATION OF MODEL FP - 327- ZC WITH OPTIONAL WOODEN MANTELREAR OF HEATER 1/2 WOOD SCREWSTOP MANTEL MANTEL BASESECTION AFTER MARKET MOBILE HOME INSTALLATION PRODUCING ADEQUATE VENTILATION DETERMINING FRESH-AIRFLOW FOR HEATER LOCATIONVent-freeheater VENTILATION AIR VENTILATION AIR FROM INSIDE BUILDINGVENTILATION AIR FROM OUTDOORS GAS CONNECTION FLAMEPLACEMENT OF LOGS SEE DIAGRAM ON PAGEGAS PRESSURE CHECK PLACEMENT OF LOGS 3 1 2 FigurePage FOR YOUR SAFETY, READ BEFORE LIGHTING LIGHTING INSTRUCTIONS MILLIVOLT VALVE ITTWHAT TO DO IF YOU SMELL GAS REMOVE METAL CONNECTOR ROCKER SWITCHBEFORE INSTALLING THERMOSTAT PageTHERMO--COUPLEPILE IGNITOR ELECTRODEPILOT BURNER PageMANUAL LIGHTING PROCEDURE THERMOSTAT CONTROL OPERATIONLIGHTING INSTRUCTIONS MODULATING VALVEMAXITROL FOR YOUR SAFETY, READ BEFORE LIGHTINGfor “LOW” LIGHTING INSTRUCTIONSto IGNITE and for “HIGH”IGNITER ELECTRODE THERMO-COUPLE O.D.S PILOT BURNERTO TURN OFF GAS TO APPLIANCE MANUAL LIGHTING PROCEDURE THERMOSTAT CONTROL OPERATIONBURNER FLAME CHECKNATURAL PILOT PROPANE PILOTWIRING DIAGRAM NOTE #PESBRO84 Blower Model FP-327-ZC Rating 120 volts/60HZ/0.54 AmpsPage IMPORTANT SAFEGUARDS CLEANINGTROUBLE SHOOTING Air in gas lines when OBSERVED PROBLEM OBSERVED REPAIR PARTS SERVICINGPARTS LIST Maxitrol ValveBLOWN UP VIEW OF BURNER ASSEMBLY PageITT Valve PARTS LISTBLOWN UP VIEW OF BURNER ASSEMBLY PagePage Page