Desa (V)DVF36TCRP(E), (V)DVF36TCLP(E) installation manual Gas Supply Testing, Not Overtighten

Page 21

Installation

Continued

IMPORTANT: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig. (3.5 kPa). The appliance must be isolated from the gas supply piping system by closing its individual equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.5 kPa).

CAUTION: Do not kink flex- ible gas line.

CAUTION: Compounds used on threaded joints of gas piping shall be resistant to the action of Liquefied Petroleum (LP or propane), and should be applied lightly to ensure excess sealant does not enter the gas line.

1.Install a sediment trap between the incoming gas line and the gas control valve (see Figure 40). The sediment trap should extend down the center of the pipe. Refer to your local codes.

2.Prepare incoming gas line and check with local codes regarding the use of teflon tape.

Complete your gas line installation by con- necting incoming gas line with flexible gas line. Secure tightly with a wrench, but Do

NOT Overtighten.

Incoming 1/2" Gas

Line Permitted by

Local Codes

Sediment

 

all

Trap (Not

 

 

W

Supplied)

Side

 

Appliance

3" Min.

Of

 

Figure 40 - Sediment Trap

WARNING: All gas piping and connections must be tested for leaks after the installation is completed. After ensuring that the gas valve is open, ap- ply a soap and water solution to all connections and joints. If bubbles appear, leaks can be de- tected and corrected. Do not use an open flame for leak testing and do not operate any appliance if a leak is detected.

WARNING: Improper installa- tion, adjustment, alteration, ser- vice, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer, service agency, or gas supplier.

Gas Supply Testing

Note: This section is intended as a guide for qualified service technicians installing gas to the appliance.

CAUTION: Do not connect appliance before pressure test- ing gas piping. Damage to the gas valve may result and an un- safe condition may be caused.

The millivolt system with a manual HI/LO ap- plies only to the DVF36TCR, DVF36TCRP, DVF36TCL and DVF36TCLP models. The gas control valve is accessible from the lower control compartment. Two pressure taps are provided on the gas control valve for a pressure gauge connec- tion (see Figure 41, page 22).

The electronic system applies to the DVF36TCRE, DVF36TCRPE, DVF36TCLE and DVF36TCLPE models (see Figure 42, page 22).

112108-01C

www.desatech.com

21

Image 21
Contents Right Side Corner Model Shown What to do if YOU Smell GASSafety Information Table of ContentsSafety Information High traffic areas Pre-Installation Preparation DimensionsTOP View Back View Right Side Front ViewClearances Mantel ClearancesFraming Alternate Gas Supply Location Vent Termination Clearances General VentingMinimum Clearances for Termination Cap Venting Installation Instructions Installation PrecautionsInstallation Planning Installing Vent System in a Chase Installation for horizontal terminationVent Pipe Connections Venting with Two 90 Elbows Horizontal VentingFlat Ceiling Installation Installation for vertical TerminationCathedral Ceiling Support Box Installation Cathedral Ceiling InstallationVenting with One 90 Elbow Vertical Rigid Venting Configuration Using One 90 ElbowParts list for Desa venting kits and components High altitude installationVertical Venting Desa 5/8 Pipe & Vent Kits Number Description Wall Switch Installation InstallationOptional Wireless hand-held Remote Control Installation Electrical Hookup for optional blower accessoryRemoved from ignition control circuit for GAS Line HOOK-UPNot Overtighten Gas Supply TestingON/OFF Installing Log SetDecorative Facing Pilot/Electrode Assembly AdjustmentBurner Removal Burner Flame AdjustmentCleaning and Replacing Glass Door Cleaning MaintenanceFor Your Safety Read Before Lighting Operating FireplaceLighting Instructions To Turn OFF GAS To Appliance Operating FireplaceTechnical Service Service HintsSpecifications Replacement PartsProblem Possible Cause Remedy TroubleshootingTroubleshooting See Wiring Diagrams Wiring DiagramsParts Accessories Pilot AssemblySkytech Remote Control KIT Screen Assembly Burner AssemblY Piezo Ignitor Grate End Glass Assembly Peninsula OnlyBlower kit End Louver Kit Peninsula OnlyIgnition Control Side Door Assembly 27200 CeramicLOG SET Refractory Pieces High Voltage Cable112108-01C Warranty Information Keep this WarrantyLimited Warranty DIRECT-VENT Fireplace