Desa EFS10TN, EFS26NR, FMH26PR, FMH26NR Ventilation AIR, Ventilation Air From Inside Building

Page 7

AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow for Fireplace Location (Cont.) Ventilation Air

7

AIR FOR COMBUSTION AND VENTILATION

Continued

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

 

30,000

Gas water heater

 

 

_____________ Btu/Hr

Vent-free fireplace

+

10,000

_____________ Btu/Hr

Total

=

40,000

_____________ Btu/Hr

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 5). You can also remove door into adjoining room (see option 3, Figure 5). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 35,840 Btu/Hr (maximum the space can support) 40,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventilation Air From Out- doors, page 8.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

12"

Figure 5 - Ventilation Air from Inside Building

WARNING: If the area in which the fireplace may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

For morevisit www..com

107032-01E

Image 7
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualSafety Information Table of ContentsVent-Free Compact Classic Hearth Fireplace Product IdentificationUnpacking Optional Remote Control AccessoriesProduct Features Local CodesAssembling Fireplace AssemblyProviding Adequate Ventilation AIR for Combustion and VentilationDetermining FRESH-AIR Flow for Fireplace Location Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors InstallationMinimum Clearance to Combustible Materials Installation ItemsCheck GAS Type Fireplace ClearancesRough Opening for Installing in Wall BUILT-IN Fireplace InstallationMantel Clearances for Built-In Installation Optional Mantel InstallationInstalling Blower Accessory Removing Upper Louver Assembly and Branch SupportAssembling Brass Trim Brass trim shipped with mantel Valve cover shield. see Figure For Built-In InstallationExtension Cord Removing Upper Louver AssemblyRemoving Valve Cover Shield Installing Blower AssemblyValve Cover Shield Switch PlateScrew Attaching Wood Base to Solid Floor Connecting to GAS SupplyInstallation Items Needed Connecting Equipment Shutoff Valve to Heater ControlChecking GAS Connections Pressure Testing gas Supply Piping systemPressure Testing Fireplace Gas Connections Optional Wireless HAND-HELD Remote Control AccessoriesInstalling Receiver Optional Wall Mounted Thermostat GWMT1 Installing 9-Volt Battery in Hand-Held Remote Control UnitBack View of Thermostat Base Installing LOG SET and ScreenLighting Instructions Operating FireplaceThermostat Control Operation Manual Lighting ProcedureREMOTE-READY Models For Your Safety Read Before Lighting To Turn OFF GAS to AppliancePropane/LPGasPilot Natural Gas Pilot Ghrcta Series Operation Optional Remote OperationGWMT1 Wall Mounted Thermostat Optional Thermostat Control OperationPilot Flame Pattern GWMS2 Wall Mounted Switch OptionalInspecting Burners Burner Flame PatternCabinet Cleaning MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole LOG SETObserved Problem Possible Cause Remedy TroubleshootingRemedy Observed Problem Possible CauseGas leak. See Warning statement When Gas Pressure Is Too Low SpecificationsService Hints Technical ServiceRemote-Ready Models Only Replacement Parts Wiring DiagramParts Under Warranty Parts not Under WarrantyTHERMOSTAT-CONTROLLED Models VMH10TPB, VMH10TNB Illustrated Parts BreakdownTHERMOSTAT-CONTROLLED Models Parts ListEFS26PR, EFS26NR REMOTE-READY ModelsParts List Accessories Receiver and HAND-HELD Remote Control KIT Ghrc Cleaning KIT GCKWALL-MOUNT Thermostat Switch GWMT1 WALL-MOUNT ON/OFF Switch GWMS2For . .com Owners Registration Form Postage Required 107032-01E Limited Warranty VENT-FREE Compact Classic Hearth Fireplace Warranty Information