TROUBLE SHOOTING THE GAS CONTROL SYSTEM

TROUBLE SHOOTING THE GAS CONTROL SYSTEM

HONEYWELL MILLIVOLT VALVE

START

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHECK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• GAS SUPPLY ON

 

 

 

 

NO

 

 

 

 

 

• SUPPLY LINE HOOKED UP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• SHUTOFF VALVE OPEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• LOCKOUT HAS ENGAGED. WAIT

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60 SECONDS AND TRY AGAIN.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• FOR SPARK AT ELECTRODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHILE DEPRESSING PIEZO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

— 1/8" GAP TO

PILOT LIGHTS WITH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

PILOT HOOD NEEDED.

PIEZO IGNITOR

 

 

 

 

 

 

 

 

• ALL WIRING CONNECTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• REPLACE PIEZO IGNITOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

• FOR AIR IN THE LINES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• THERMOPILE NEEDS A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MINIMUM 325mV. ADJUST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PILOT FLAME HEIGHT.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• ALL WIRING CONNECTIONS.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PILOT STAYS LIT

 

 

 

 

NO

 

 

 

 

 

• REPLACE THERMOPILE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• THERMOCOUPLE NEEDS A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MINIMUM OF 14mV.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• DEFECTIVE VALVE. TURN TO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PILOT, METER SHOULD READ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GREATER THAN 100 mV. IF

YES

 

 

 

 

 

 

 

 

 

 

 

NOT, REPLACE.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• VALVE IS TURNED ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• ON/OFF SWITCH IS NOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TURNED ON. WATCH

PILOT LIGHTS MAIN

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

FOR GROUNDED WIRES!

BURNER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• THERMOPILE NEEDS A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MINIMUM 325mV.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• PLUGGED BURNER ORIFICE.

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYSTEM OK.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- 22 -

Image 22
Contents Free-Standing Direct Vented Fireplaces FOR YOUR SAFETYFOR YOUR SAFETY MODEL D232TABLE OF CONTENTS Crimped Ends Venting ComponentsLOCATING YOUR GAS FIREPLACE INSTALLATION AND OPERATING INSTRUCTIONSCLEARANCE TO COMBUSTIBLES PLEASE REVIEW THE FOLLOWINGMODEL D232 A K C D EG F BI J H FIREPLACE DIMENSIONSPREPARATION GAS SPECIFICATIONSGAS LINE INSTALLATION D232 CERTIFIED TOVALVE INSTALLATION OF REMOTE SWITCH FOR RN/RP GAS VALVEON/OFF SWITCH OR MILLIVOLT THERMOSTATF= clearance to outside comer see next page GENERAL VENTING INFORMATIONLocation of Vent Termination G= clearance to inside comer see next pageTermination Clearances D CC EGENERAL INFORMATION ON ASSEMBLING THE VENT PIPES CRIMPED END PIPESTWIST LOCK PIPES Screw HolesTotal VERTICAL SIDEWALL INSTALLATIONSVERTICAL SIDEWALL APPLICATIONS 270oSIDEWALL VENTING GRAPH Dimensions in FeetTO USE THE VENT GRAPH HORIZONTAL DIMENSIONSTEP VENT PIPE ASSEMBLYBEAD OF SEALANT STEPSTEP BELOW GRADE INSTALLATIONSSTEP STEPVERTICAL THROUGH THE ROOF APPLICATIONS run if the vertical exceedsTO INSTALL VERTICAL VENTING VERTICAL THRU THE ROOF APPLICATIONSCRIMPED ENDS VENTING COMPONENTS TWIST LOCK VENTING COMPONENTS LOUVRE REMOVAL OPERATING INSTRUCTIONSGENERAL GLASS INFORMATION TRIM REMOVALINSTALLATION OF LOGS & BURNER LAVA ROCK MATERIAL GLASS CLEANINGClean glass after first two weeks of operation CLEANING PROCEDURE MAINTENANCEFLAME ADJUSTMENT RN/RP MODELS FLAME CHARACTERISTICSLIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTINGLIGHTING AND OPERATING INSTRUCTIONS TO TURN OFF GAS TO FIREPLACESTART TROUBLE SHOOTING THE GAS CONTROL SYSTEMHONEYWELL MILLIVOLT VALVE CHECKPOSSIBLE CAUSES SYMPTOMSIT NOVA 820 MILLIVOLT VALVE CORRECTIVE ACTIOND232 REPLACEMENT PARTS LISTDESCRIPTION D232 FREESTANDING REPLACEMENT PARTS#1 - COMPLETE LOG SET OPTIONS REMOTE CONTROLFAN KIT - FK24 Page For Gas Appliance Products LIMITED WARRANTY & EXTENDED LIFE TIME PROTECTIONCFM Majestic, Inc