Vermont Casting D232 SIT NOVA 820 MILLIVOLT VALVE, Symptom, Possible Causes, Corrective Action

Page 23
TROUBLE SHOOTING THE GAS CONTROL SYSTEM

TROUBLE SHOOTING THE GAS CONTROL SYSTEM

SIT NOVA 820 MILLIVOLT VALVE

Note: Before trouble shooting the gas control system, be sure external gas shut off is in the "On" position.

WARNING: BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE GLASS FRONT.

 

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

 

 

 

 

 

1.

Spark ignitor will not light.

A. Defective or misaligned

Using a match, light pilot. If pilot lights, turn off pilot and

 

 

 

electrode at pilot.

push the red button again. If pilot will not light - check gap

 

 

 

 

at electrode and pilot-should be 1/8" to have a strong spark.

 

 

 

 

 

 

 

 

B. Defective ignitor (Push Button)

Push Piezo Ignitor Button. Check for spark at electrode and

 

 

 

 

pilot. If no spark to pilot, and electrode wire is properly

 

 

 

 

connected, replace ignitor.

 

 

 

 

2. Pilot will not stay lit after

A. Defective pilot generator

1. Check pilot flame. Must impinge on thermocouple/

 

carefully following lighting

(thermocouple), remote wall

thermopile. Note: this pilot burner assembly utilizes both

 

instructions.

switch.

a thermocouple and a thermopile. The thermocouple

 

 

 

 

operates the main valve operation (On and Off). Clean

 

 

 

 

and or adjust pilot for maximum flame impingement on

 

 

 

 

thermopile and thermocouple.

 

 

 

 

 

 

 

 

B. Defective automatic valve

Turn valve knob to "Pilot". Maintain flow to pilot; millivolt

 

 

 

operator.

meter should read greater than 10 mV. If the reading is

 

 

 

 

okay and the pilot does not stay on, replace the gas

 

 

 

 

valve. Note: An interrupter block (not supplied) must be

 

 

 

 

used to conduct this test.

 

 

 

 

3. Pilot burning, no gas to

A. Wall switch or wires

Check wall switch and wires for proper connections. Jumper

 

burner.

 

replace defective wall switch. If okay, jumper wires across

 

 

 

 

wall switch wires at valve, if burner comes on, wires are

 

 

 

 

faulty or connections are bad.

 

 

 

 

 

 

 

 

B. Thermopile may not be

1. Be sure wire connections from thermopile at gas valve

 

 

 

generating sufficient

terminals are tight and thermopile is fully inserted into pilot

 

 

 

millivoltage.

bracket.

 

 

 

 

2. One of the wall switch wires may be grounded. Remove

 

 

 

 

wall switch wires from valve terminals if pilot now stays lit,

 

 

 

 

trace wall switch wiring for ground. May be grounded to

 

 

 

 

fireplace or gas supply.

 

 

 

 

3. Check thermopile with millivolt meter. Take reading at

 

 

 

 

thermopile terminals of gas valve. Should read 250-300

 

 

 

 

millivolts (minimum 150) while holding valve knob de-

 

 

 

 

pressed in pilot position and wall switch "Off". Replace

 

 

 

 

faulty thermopile if reading is below specified minimum.

 

 

 

 

 

 

 

 

C. Plugged burner orifice.

Check burner orifices for debris and remove.

 

 

 

 

 

 

 

 

D. Defective automatic valve

Turn valve knob to "On", place wall switch to "On" millivolt

 

 

 

operator.

meter should read greater than 100 mV. If the reading is

 

 

 

 

okay and the burner does not come on, replace the gas

 

 

 

 

valve.

 

 

 

 

 

4.

Frequent pilot outage

A. Pilot flame may be too low

Clean and/or adjust pilot flame for maximum flame

 

problem.

or blowing (high) causing the

impingement on thermopile and thermocouple.

 

 

 

pilot safety to drop out.

 

 

 

 

 

 

 

 

 

B. Possible blockage of the vent

Check the vent terminal for blockage (recycling the flue gases)

 

 

 

terminal.

 

 

 

 

 

 

- 23 -

Image 23
Contents MODEL D232 FOR YOUR SAFETYFOR YOUR SAFETY Free-Standing Direct Vented FireplacesCrimped Ends Venting Components TABLE OF CONTENTSPLEASE REVIEW THE FOLLOWING INSTALLATION AND OPERATING INSTRUCTIONSCLEARANCE TO COMBUSTIBLES LOCATING YOUR GAS FIREPLACEFIREPLACE DIMENSIONS A K C D EG F BI J H MODEL D232D232 CERTIFIED TO GAS SPECIFICATIONSGAS LINE INSTALLATION PREPARATIONMILLIVOLT THERMOSTAT INSTALLATION OF REMOTE SWITCH FOR RN/RP GAS VALVEON/OFF SWITCH OR VALVEG= clearance to inside comer see next page GENERAL VENTING INFORMATIONLocation of Vent Termination F= clearance to outside comer see next pageD CC E Termination ClearancesScrew Holes CRIMPED END PIPESTWIST LOCK PIPES GENERAL INFORMATION ON ASSEMBLING THE VENT PIPES270o VERTICAL SIDEWALL INSTALLATIONSVERTICAL SIDEWALL APPLICATIONS TotalHORIZONTAL DIMENSION Dimensions in FeetTO USE THE VENT GRAPH SIDEWALL VENTING GRAPHSTEP VENT PIPE ASSEMBLYBEAD OF SEALANT STEPSTEP BELOW GRADE INSTALLATIONSSTEP STEPrun if the vertical exceeds VERTICAL THROUGH THE ROOF APPLICATIONSVERTICAL THRU THE ROOF APPLICATIONS TO INSTALL VERTICAL VENTINGCRIMPED ENDS VENTING COMPONENTS TWIST LOCK VENTING COMPONENTS TRIM REMOVAL OPERATING INSTRUCTIONSGENERAL GLASS INFORMATION LOUVRE REMOVALClean glass after first two weeks of operation GLASS CLEANINGINSTALLATION OF LOGS & BURNER LAVA ROCK MATERIAL FLAME CHARACTERISTICS MAINTENANCEFLAME ADJUSTMENT RN/RP MODELS CLEANING PROCEDURETO TURN OFF GAS TO FIREPLACE FOR YOUR SAFETY READ BEFORE LIGHTINGLIGHTING AND OPERATING INSTRUCTIONS LIGHTING INSTRUCTIONSCHECK TROUBLE SHOOTING THE GAS CONTROL SYSTEMHONEYWELL MILLIVOLT VALVE STARTCORRECTIVE ACTION SYMPTOMSIT NOVA 820 MILLIVOLT VALVE POSSIBLE CAUSESDESCRIPTION REPLACEMENT PARTS LISTD232 #1 - COMPLETE LOG SET FREESTANDING REPLACEMENT PARTSD232 FAN KIT - FK24 REMOTE CONTROLOPTIONS Page CFM Majestic, Inc LIMITED WARRANTY & EXTENDED LIFE TIME PROTECTIONFor Gas Appliance Products