Vermont Casting D232 Vertical Through The Roof Applications, run if the vertical exceeds

Page 14
run if the vertical exceeds 24".

Ensure sidewall venting clearances are observed.

If installing a snorkel a minimum 24" vertical rise is necessary. The maximum horizontal run with the 24" vertical pipe is 36" (915mm). This measurement is taken from the collar of the fireplace to the face of the exterior wall. See vent graph for extended horizontal

DO NOT BACK FILL AROUND SNORKEL. SOIL SHOULD NOT BE LESS THAN 4" BELOW SNORKEL.

run if the vertical exceeds 24".

1.

Establish vent hole through the wall (Fig. 13,14 & 15).

2.

Remove soil to a depth of approximately 16" below

 

base of snorkel. Install drain pipe. Install window well

 

(not supplied). Refill hole with 12" of coarse gravel

 

leaving a clearance of approximately 4" below snorkel.

 

See Fig. 22.

3.

Install vent system.

FOUNDATION

RECESS

WATERTIGHT

SEAL

AROUND

PIPE

SNORKEL

WALL

SCREWS

SHEET METAL

Fig. 23

SCREWS

4.

Ensure a watertight seal is made around the vent pipe

 

coming through the wall.

5.

Apply high temperature sealant caulking (supplied)

 

around the 4 and 7 inch snorkel collars.

6.

Slide into vent pipe and secure to the wall.

7.

Level the soil so as to maintain a 4" clearance below

 

snorkel. See Fig. 22.

FIRESTOP

SNORKEL

 

7" PIPE

SCREWS

4" CLEARANCE

 

 

GROUND

 

WINDOW WELL

 

GRAVEL

24"/608mm

DRAIN

MINIMUM*

 

 

FOUNDATION WALL

*A minimum of 24"/608mm vertical pipe must be installed when using the snorkel kit.

*The 22" vertical rise (center to center) of the snorkel may be included for calculation of max. horizontal run.

Fig. 22

- 14 -

If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to wall first and then secure to snorkel with self drilling #8 x 1/2 sheet metal screws. It will be necessary to extend the vent pipes out as far as the protruding wall face (Fig. 22).

VERTICAL THROUGH THE ROOF

APPLICATIONS

MAXIMUM

10 FT

(305cm)

MINIMUM

8FT./

MAXIMUM 40 FT.

VERTICAL

RISE

PIPE STRAPS

EVERY 3’

(92cm)

Fig. 24

This Gas Fireplace has been approved for,

a)Vertical installations up to 40 feet (12 metres) in height. Up to a 10 ft. horizontal vent run can be installed within the vent system using a maximum of two 90o elbows. (Fig. 24)

b)Up to two 45o elbows may be used within the horizontal run. For each 45o elbow used on the horizontal level the maximum horizontal length must be reduced by 18 inches.

Example: Maximum horizontal length

 

0

-

45o elbows

10 ft.

1

-

45o elbows

8.5 ft.

2

-

45o elbows

7 ft.

Image 14
Contents Free-Standing Direct Vented Fireplaces FOR YOUR SAFETYFOR YOUR SAFETY MODEL D232TABLE OF CONTENTS Crimped Ends Venting ComponentsLOCATING YOUR GAS FIREPLACE INSTALLATION AND OPERATING INSTRUCTIONSCLEARANCE TO COMBUSTIBLES PLEASE REVIEW THE FOLLOWINGMODEL D232 A K C D EG F BI J H FIREPLACE DIMENSIONSPREPARATION GAS SPECIFICATIONSGAS LINE INSTALLATION D232 CERTIFIED TOVALVE INSTALLATION OF REMOTE SWITCH FOR RN/RP GAS VALVEON/OFF SWITCH OR MILLIVOLT THERMOSTATF= clearance to outside comer see next page GENERAL VENTING INFORMATIONLocation of Vent Termination G= clearance to inside comer see next pageTermination Clearances D CC EGENERAL INFORMATION ON ASSEMBLING THE VENT PIPES CRIMPED END PIPESTWIST LOCK PIPES Screw HolesTotal VERTICAL SIDEWALL INSTALLATIONSVERTICAL SIDEWALL APPLICATIONS 270oSIDEWALL VENTING GRAPH Dimensions in FeetTO USE THE VENT GRAPH HORIZONTAL DIMENSIONSTEP VENT PIPE ASSEMBLYBEAD OF SEALANT STEPSTEP BELOW GRADE INSTALLATIONSSTEP STEPVERTICAL THROUGH THE ROOF APPLICATIONS run if the vertical exceedsTO INSTALL VERTICAL VENTING VERTICAL THRU THE ROOF APPLICATIONSCRIMPED ENDS VENTING COMPONENTS TWIST LOCK VENTING COMPONENTS LOUVRE REMOVAL OPERATING INSTRUCTIONSGENERAL GLASS INFORMATION TRIM REMOVALClean glass after first two weeks of operation GLASS CLEANINGINSTALLATION OF LOGS & BURNER LAVA ROCK MATERIAL CLEANING PROCEDURE MAINTENANCEFLAME ADJUSTMENT RN/RP MODELS FLAME CHARACTERISTICSLIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTINGLIGHTING AND OPERATING INSTRUCTIONS TO TURN OFF GAS TO FIREPLACESTART TROUBLE SHOOTING THE GAS CONTROL SYSTEMHONEYWELL MILLIVOLT VALVE CHECKPOSSIBLE CAUSES SYMPTOMSIT NOVA 820 MILLIVOLT VALVE CORRECTIVE ACTIONDESCRIPTION REPLACEMENT PARTS LISTD232 #1 - COMPLETE LOG SET FREESTANDING REPLACEMENT PARTSD232 FAN KIT - FK24 REMOTE CONTROLOPTIONS Page CFM Majestic, Inc LIMITED WARRANTY & EXTENDED LIFE TIME PROTECTIONFor Gas Appliance Products