MINIMUM CLEARANCE TO COMBUSTIBLES

ULTRA FLAME DV “0” Clearance Fireplace

J = 12" Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance

K = 72" Clearance to a mechanical air supply inlet

L = 84" Clearance above paved sidewalk or a paved driveway located on public property M =36" Clearance under veranda, porch, deck, or balcony

A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings *

Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of 2 sides beneath the floor *

*As specified in current CGA B149 Installation Codes.

NOTE: Local codes or regulations may require different clearances

In addition, the following restrictions also apply.

When the vent terminal is accessible, a certified guard shall be installed around the terminal. This guard is available as an option, identified as part #E5480, for straight and corner terminals and #E5482 for the basement terminal.

The vent terminal may not be recessed into the wall or siding.

The vent terminal shall not terminate :

Within 3 ft. of a building mechanical air supply.

Less than 12 inches from a perpendicular wall.

In an area which is allocated to the occupancy.

Under a window that pivots open.

In addition, in a structure with three walls and a roof , the following restrictions apply:

a)The minimum distance between the two side walls must be 72".

b)The roof must not exceed the walls more than 24".

c)If both those conditions apply, the clearance shall be as follows:

18" to a side wall.

12" to an unventilated soffit, 24" for basement or distant installation.

18" to a ventilated soffit, 24" for basement or distant installation.

NOTE: If the fireplace is installed in an outside chase, the chase walls must be insulated with vapour barrier and insulation similar to the house exterior wall.

MINIMUM CLEARANCE TO COMBUSTIBLES

13

Image 13
Contents FOR YOUR SAFETY INSTALLATION AND OPERATING INSTRUCTIONSFOR YOUR SAFETY WHAT TO DO IF YOU SMELL GAS DIRECT VENT 0 CLEARANCE GAS FIREPLACELIGHTING PROCEDURE SPECIFICATIONSMAINTENANCE INSTRUCTIONS GLASS MAINTENANCEKEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE GENERAL INFORMATIONDO NOT MODIFY THIS APPLIANCE SPECIFICATIONS OPERATION LIGHTING PROCEDUREBEFORE LIGHTING THE FIRST FIRESHUTDOWN WALL THERMOSTATBLOWER GLASS MAINTENANCE MAINTENANCE INSTRUCTIONSNever clean this glass with abrasive cleaners Use only a cleaner recommended by your dealerBURST DISC REPLACEMENT FRONT VIEW TOP, FRONT AND SIDE VIEWSTOP VIEW SIDE VIEWSAFETY NOTICE INSTALLATIONPOSITIONING THE FIREPLACE VENT TERMINAL LOCATION MINIMUM CLEARANCE TO COMBUSTIBLES INSTALLATION OF THE UNIT WARNING DO NOT USE OPEN FLAME TO CHECK LEAKS STRAIGH OUT VENTING KITSCORNER BASEMENT2 CORNER INSTALLATION 1 STRAIGHT OUT INSTALLATION3 BASEMENT INSTALLATION ULTRA FLAME DV “0” Clearance Fireplace VENTING SYSTEMVENT TERMINAL, BASEMENT INSTALLATION OPTIONAL BLOWER INSTALLATION VENT TERMINAL, ROOF INSTALLATIONBURNER REMOVAL AND INSTALLATION GLASS FRONT REMOVAL, CLEANING AND INSTALLATIONEMBER KIT INSTALLATION LOG INSTALLATION LOUVRE INSTALLATION 1.Remove the glass front assembly OPTIONAL REFRACTORY PANEL INSTALLATION6.Install the glass front assembly ULTRA FLAME DV “0” Clearance FireplaceNatural Gas Pressure Settings ADJUSTMENTSPropane Pressure Settings ELEVATIONRemember to replace all covers ADJUSTING THE GAS PRESSUREWALL THERMOSTAT ADJUSTING AIR SHUTTEROPTIONAL PARTS REPLACEMENT PARTSITEM DESCRIPTION ITEM DESCRIPTIONDROLET STOVES AND FIREPLACES INC LIMITED 5 YEAR WARRANTY