VENT TERMINAL LOCATION

ULTRA FLAME DV “0” Clearance Fireplace

VENT TERMINAL LOCATION

Your Ultra Flame fireplace vents through a vent terminal installed on the roof or on the outside of any exterior wall of your house. Many restrictions apply to the vent terminal location that should be considered before locating your fireplace.

The following drawing presents a summary of most of these restrictions.

A = 12" Clearance above grade, veranda, porch, deck or balcony B = 12" Clearance to window or door that may be opened

C = 12" Clearance to permanently closed window

D = 18" Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (60 cm) from the center-line of terminal (straight out or

corner installation)

D = 24" (Basement installation)

E = 12" Clearance to unventilated soffit (straight out or corner installation) E = 24" (Basement installation)

F = 12" Clearance to outside corner G =12" Clearance to inside corner

H = Not to be installed above a meter/regulator assembly within 3 feet (90 cm) horizontally from the center-line of the regulator *

I = 72" Clearance to service regulator vent outlet

12

Image 12
Contents INSTALLATION AND OPERATING INSTRUCTIONS FOR YOUR SAFETYFOR YOUR SAFETY WHAT TO DO IF YOU SMELL GAS DIRECT VENT 0 CLEARANCE GAS FIREPLACESPECIFICATIONS LIGHTING PROCEDUREMAINTENANCE INSTRUCTIONS GLASS MAINTENANCEGENERAL INFORMATION KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCEDO NOT MODIFY THIS APPLIANCE SPECIFICATIONS LIGHTING PROCEDURE OPERATIONBEFORE LIGHTING THE FIRST FIREWALL THERMOSTAT SHUTDOWNBLOWER MAINTENANCE INSTRUCTIONS GLASS MAINTENANCENever clean this glass with abrasive cleaners Use only a cleaner recommended by your dealerBURST DISC REPLACEMENT TOP, FRONT AND SIDE VIEWS FRONT VIEWTOP VIEW SIDE VIEWINSTALLATION SAFETY NOTICEPOSITIONING THE FIREPLACE VENT TERMINAL LOCATION MINIMUM CLEARANCE TO COMBUSTIBLES INSTALLATION OF THE UNIT WARNING DO NOT USE OPEN FLAME TO CHECK LEAKS VENTING KITS STRAIGH OUTCORNER BASEMENT1 STRAIGHT OUT INSTALLATION 2 CORNER INSTALLATION3 BASEMENT INSTALLATION VENTING SYSTEM ULTRA FLAME DV “0” Clearance FireplaceVENT TERMINAL, BASEMENT INSTALLATION VENT TERMINAL, ROOF INSTALLATION OPTIONAL BLOWER INSTALLATIONGLASS FRONT REMOVAL, CLEANING AND INSTALLATION BURNER REMOVAL AND INSTALLATIONEMBER KIT INSTALLATION LOG INSTALLATION LOUVRE INSTALLATION OPTIONAL REFRACTORY PANEL INSTALLATION 1.Remove the glass front assembly6.Install the glass front assembly ULTRA FLAME DV “0” Clearance FireplaceADJUSTMENTS Natural Gas Pressure SettingsPropane Pressure Settings ELEVATIONADJUSTING THE GAS PRESSURE Remember to replace all coversADJUSTING AIR SHUTTER WALL THERMOSTATREPLACEMENT PARTS OPTIONAL PARTSITEM DESCRIPTION ITEM DESCRIPTIONLIMITED 5 YEAR WARRANTY DROLET STOVES AND FIREPLACES INC