ADJUSTMENTS

ULTRA FLAME DV “0” Clearance Fireplace

ADJUSTMENTS

NOTE: Adjustments to the valve assembly must be performed by a qualified service person.

The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psi (3.5 kPa).

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less that ½ psi (3.5 kPa).

Natural Gas Pressure Settings:

The inlet supply or line pressure must be a minimum of 5” WC and a maximum of 8” WC. The orifice has a #36 hole.

ELEVATION

INPUT RATING

0 - 2000 ft.

30,000 BTU/hr

 

2000 - 4500 ft.

30,000 BTU/hr

4500 ft. +

30,000 BTU/hr less 4% per 1000 ft.

or reduce manifold pressure by 0.25” per 1000 ft.

Propane Pressure Settings:

The inlet supply or line pressure must be a minimum of 10.5” WC and a maximum of 12” WC. The orifice has a #52 hole.

ELEVATION

INPUT RATING

0-2000 ft.

26,000 BTU/hr

 

2000 - 4500 ft.

26,000 BTU/hr

4500 ft. +

26,000 less 4% per 1000 ft.

or reduce manifold pressure by 1” per 1000 ft.

NOTE: THE INPUT RATING SHOULD ALWAYS BE CHECKED WHEN FIRST RUNNING THIS APPLIANCE. To do this, reduce the background flow rate, time the meter, light the fireplace and take another reading. Check with your gas supplier for the gas BTU content at your elevation. Input is the rate of flow multiplied by the heating value of the gas (cubic feet/hour x BTU per cubic feet). Adjust the manifold pressure so that the unit does not operate above the rated input.

27

Image 27
Contents DIRECT VENT 0 CLEARANCE GAS FIREPLACE INSTALLATION AND OPERATING INSTRUCTIONSFOR YOUR SAFETY FOR YOUR SAFETY WHAT TO DO IF YOU SMELL GASGLASS MAINTENANCE SPECIFICATIONSLIGHTING PROCEDURE MAINTENANCE INSTRUCTIONSKEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE GENERAL INFORMATIONDO NOT MODIFY THIS APPLIANCE SPECIFICATIONS THE FIRST FIRE LIGHTING PROCEDUREOPERATION BEFORE LIGHTINGWALL THERMOSTAT SHUTDOWNBLOWER Use only a cleaner recommended by your dealer MAINTENANCE INSTRUCTIONSGLASS MAINTENANCE Never clean this glass with abrasive cleanersBURST DISC REPLACEMENT SIDE VIEW TOP, FRONT AND SIDE VIEWSFRONT VIEW TOP VIEWINSTALLATION SAFETY NOTICEPOSITIONING THE FIREPLACE VENT TERMINAL LOCATION MINIMUM CLEARANCE TO COMBUSTIBLES INSTALLATION OF THE UNIT WARNING DO NOT USE OPEN FLAME TO CHECK LEAKS BASEMENT VENTING KITSSTRAIGH OUT CORNER2 CORNER INSTALLATION 1 STRAIGHT OUT INSTALLATION3 BASEMENT INSTALLATION ULTRA FLAME DV “0” Clearance Fireplace VENTING SYSTEMVENT TERMINAL, BASEMENT INSTALLATION OPTIONAL BLOWER INSTALLATION VENT TERMINAL, ROOF INSTALLATIONBURNER REMOVAL AND INSTALLATION GLASS FRONT REMOVAL, CLEANING AND INSTALLATIONEMBER KIT INSTALLATION LOG INSTALLATION LOUVRE INSTALLATION ULTRA FLAME DV “0” Clearance Fireplace OPTIONAL REFRACTORY PANEL INSTALLATION1.Remove the glass front assembly 6.Install the glass front assemblyELEVATION ADJUSTMENTSNatural Gas Pressure Settings Propane Pressure SettingsRemember to replace all covers ADJUSTING THE GAS PRESSUREWALL THERMOSTAT ADJUSTING AIR SHUTTERITEM DESCRIPTION REPLACEMENT PARTSOPTIONAL PARTS ITEM DESCRIPTIONDROLET STOVES AND FIREPLACES INC LIMITED 5 YEAR WARRANTY