Regency P42-LP4 Installation Procedures, Offset Chart, For Regency Direct Vent System Flex

Page 23

INSTALLATION

Diagram 5

Roof Pitch

Minimum Vent Height

 

 

 

 

Feet

Meters

fl at to 7/12

2

0.61

over 7/12 to 8/12

2

0.61

over 8/12 to 9/12

2

0.61

over 9/12 to 10/12

2.5

0.76

over 10/12 to 11/12

3.25

0.99

over 11/12 to 12/12

4

1.22

over 12/12 to 14/12

5

1.52

over 14/12 to 16/12

6

1.83

over 16/12 to 18/12

7

2.13

over 18/12 to 20/12

7.5

2.29

over 20/12 to 21/12

8

2.44

 

 

 

A poor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the vent height may solve the problem.

7)Ensure vent is vertical and secure the base of the fl ashing to the roof with roofi ng rails, slide storm collar over the pipe section and seal with a mastic.

8)Install the vertical termination cap by twist- locking it.

Note: Any closets or storage spaces, which the vent passes through must be enclosed.

Offset Chart

INSTALLATION

PROCEDURES

for Regency® Direct Vent

System (Flex)

1)Locate the unit in the framing, rough in the gas (preferably on the right side of the unit) and the electrical (Junction block is on the left side) on the left. Locate the centerline of the termination and mark wall accordingly. Cut a 10"(254mm) hole in the wall (inside dimension).

Note: To make the installation more aesthetically p l e a s i n g , w e recommendframing out a square to mount the terminal to.

Note: A 1-1/2"(38mm) clearance around the liner must be maintained except that only a 1" (25mm) clearance is needed at the termination end. We recommend framing a 10"(254mm) x 10"(254mm)(insidedimensions)hole togivestructuralrigidityformounting the termination.

Note: If installing termination on a siding covered wall, furring strips must be used to ensure that the termination is not recessed into the siding.

2)Levelthefireplaceandfastenittotheframing using nails or screws through the nailing strips.

3)Assemble the vent assembly by applying Mill Pac to the 4"(100mm) inner collar of the terminationand slippingthe4"(100mm)liner over it at least 1-3/8" (35mm). Fasten with the 3 screws (drilling pilot holes will make this easier). Apply Mill Pac or high temperature silicone to the 6-7/8"(175mm) fl ex pipe and slip it over the 6-7/8" outer collar of the vent terminal at least 1-3/8"(35mm) and fasten with the 3 screws.

NOTE: Horizontal sections must be supported at intervals not exceeding 3 feet (0.9 meter). (Flame picture and performance will be affected by sags in the liner).

4)Separate the 2 halves of the wall thimble and securely fasten the one with the tabs to the outside wall making sure that the tabs are on top and bottom. Fasten the other thimble half to the inside wall. The thimble halves slip inside each other and can be adjusted for 2 x 4 or 2 x 6 walls. The liners must slip over the collars a minimum of 1-3/8".

5)Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up (there are markings on the cap that show which way is up). This will position the termination cap with proper down slope for draining water. Fasten the cap to the outer wall with the 4 supplied screws.

6)Pull the centre 4"(100mm) liner and outer 6-7/8"(175mm) liner out enough to slip over the fl ue collars of the fi replace. (You may wish to cut the liner shorter to make it more workable.) Do not bend liner more than 90o.

7)Apply Mill Pac over the fi replace inner collar and slip the 4"(100mm) liner down over it and attach with 3 supplied screws.

8)Do the same with the 6-7/8"(175mm) liner.

9)Apply a bead of silicone between the thimble and termination and around the outer edge of the terminal at the wall in order to keep the water out.

IMPORTANT:

Do not locate termination hood where excessive snow or ice buildup may occur.Besuretocheckventtermination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.

Regency® P42-4 Zero Clearance Direct Vent Gas Fireplace

23

Image 23
Contents 918-523a 03/06/08 P42 Gas FireplaceTo the New Owner Information for MOBILE/MANUFACTURED Homes After First SaleTable of Contents Copy of Safety Decal for P42 Safety LabelMA Code CO Detector RequirementsImportant Message Save These Instructions InstallationGeneral Safety Information Installation ChecklistOptional Heat Release KIT Unit Specifications Locating Your GAS FireplaceManufactured Mobile Home Additional Requirements Heatwave Optional Duct System KITMantel LEG Clearances ClearancesmantelsVent Restrictor TOP Assembly Nailing StripsFraming Finishing Venting IntroductionExterior Vent Termination Requirements Run of 4 feet VentingDescription 6-5/8 Rigid Pipe Cross Reference Chart6-5/8 Rigid Pipe Cross Reference Chart Termination Caps Rigid Pipe VentingAlternate HorizontalVent guard may be required, check local codes Rigid Pipe Venting Arrangements Horizontal Terminations8 outer diameter Regency Flex Vent 4 inner diameter For All Horizontal TerminationsPropane & Natural Gas Rigid Pipe Venting Arrangements Vertical TerminationsVent restrictor #6 must be used Alternate Approved Caps Vertical Termination With CO-LINEAR Flex SystemRequired Parts DescriptionVenting Arrangements Vertical Terminations Snorkel Terminations Below Grade InstallationHorizontal Terminations Vertical Terminations DiagramFor Regency Direct Vent System Flex Installation ProceduresOffset Chart System Data GAS Line InstallationGAS Pipe Pressure Testing High ElevationFront Aeration Brick Panels AdjustmentConditions may occur if the panels Are brokenPropane LOG SET InstallationNatural GAS Double Screen Doors Standard Flush DoorFlush Louvers Optional Bay Trim Optional BAY DoorBAY Louvers Full Screen Doors Full Screen Door Frame InstallationHinge Location Bottom Grill Hinge Screen Door Do not cut the ground terminal off under Wiring DiagramsAny circumstances Live until the fan is installed For Propane Units and Units Equipped with DC Spark Boxes Operating Instructions Wall SwitchLighting Procedure Thermostat Wire TableCopy of the Lighting Plate Instructions For Your Safety Read Before LightingFirst Fire MaintenanceShutdown Procedure Maintenance InstructionsDoor Glass GOLD-PLATEDGLASS Louvers ReplacementLOG Replacement Thermopile ThermocoupleRemoving the FAN Replacing the FAN Shut the power offInstalling Valve P42 Main Assembly Parts ListP42 Burner & LOG Assembly P42 Flush Door & Louvers P42 BAY Front & Louvers Regency P42-4 Zero Clearance Direct Vent Gas Fireplace Regency P42-4 Zero Clearance Direct Vent Gas Fireplace Regency P42-4 Zero Clearance Direct Vent Gas Fireplace Conditions WarrantyInstaller Please complete the following information

P42-LP4, P42-NG4 specifications

The Regency P42-LP4 and P42-NG4 are two exceptional gas fireplace models that beautifully combine functionality and aesthetic appeal, making them ideal for various home settings. Built with durability and efficiency in mind, these models are equipped with advanced features that enhance user experience.

One of the main highlights of the P42 series is its impressive heating capacity. Both the P42-LP4 and P42-NG4 are designed to deliver substantial warmth, ensuring that spaces of different sizes can be comfortably heated. With a maximum input of up to 40,000 BTUs, these units can effectively warm large living areas, making them perfect for modern homes.

In terms of design, the P42 models boast a sleek and contemporary look. They feature a large viewing area that allows for an expansive flame presentation, inviting warmth and ambiance into your home. The optional polished or brushed stainless steel front and various media options, including glass rocks or logs, provide customization, allowing homeowners to tailor the look of their fireplace to match their personal style and existing decor.

The technologies integrated into the Regency P42-LP4 and P42-NG4 are notable. Both models come equipped with system safety features, ensuring peace of mind. Additionally, they support the use of a programmable remote control, making adjustments to the temperature and flame appearance effortless while allowing homeowners to maintain comfort with just a click.

Efficiency is another key characteristic. These gas fireplaces highlight energy efficiency, designed to maximize heat output while minimizing fuel consumption. They have received high-efficiency ratings, which may qualify users for rebates or incentives in many regions, aligning with the growing demand for eco-friendly home heating solutions.

Installation flexibility is another advantage, with options for direct vent systems allowing for installation in various orientations and settings. This ensures homeowners can enjoy an attractive fireplace without needing extensive renovations or structural changes.

In conclusion, the Regency P42-LP4 and P42-NG4 are standout choices for anyone seeking a powerful, efficient, and stylish gas fireplace. With their innovative technologies, customizable features, and remarkable heating capabilities, these models offer an ideal focal point and cozy environment for any living space. They embody the perfect blend of modern design and traditional warmth, making them an excellent investment for enhancing home comfort and elegance.