Regency P131, P121RC, P121LC installation manual Installation Procedures, Offset Chart

Page 23

INSTALLATION

local codes. Note that for steep roof pitches, the vertical height must be increased. A poor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the vent height may solve the problem.

7)Ensure vent is vertical and secure the base of the fl ashing to the roof with roofi ng rails, slide storm collar over the pipe section and seal with a mastic.

8)Install the vertical termination cap by twist- locking it.

Note: Any closets or storage spaces, which the vent passes through must be enclosed.

Offset Chart

Note: To make the installation more aesthetically p l e a s i n g , w e recommend framing outasquaretomount the terminal to.

2)Levelthefireplaceandfastenittotheframing using nails or screws through the nailing strips.

3)Assemble the vent assembly by applying Mill Pac to the 4"(100mm) inner collar of the terminationand slippingthe4"(100mm)liner over it at least 1-3/8" (35mm). Fasten with the3screws(drillingpilotholeswillmakethis easier). Apply Mill Pac or high temperature silicone to the 6-7/8"(175mm) fl ex pipe and slip it over the 6-7/8" outer collar of the vent terminal at least 1-3/8"(35mm) and fasten with the 3 screws.

NOTE: Horizontal sections must be supported at intervals not exceeding 3 feet (0.9 meter). (Flame picture and performance will be affected by sags in the liner).

4)Separate the 2 halves of the wall thimble and securely fasten the one with the tabs to the outside wall making sure that the tabs are on top and bottom. Fasten the other thimble half to the inside wall. The thimble halves slip inside each other and can be adjusted for 2 x 4 or 2 x 6 walls. The liners must slip over the collars a minimum of 1-3/8".

5)Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up (there are markings on the cap that show which way is up). This will position the termination cap with proper down slope for draining water. Fasten the cap to the outer wall with the 4 supplied screws.

6)Pull the centre 4"(100mm) liner and outer 6-7/8"(175mm) liner out enough to slip over the fl ue collars of the fi replace. (You may wish to cut the liner shorter to make it more workable.) Do not bend liner more than 45o.

7)Apply Mill Pac over the fi replace inner collar and slip the 4"(100mm) liner down over it and attach with 3 supplied screws.

8)Do the same with the 6-7/8"(175mm) liner.

9)Apply a bead of silicone between the thimble and termination and around the outer edge of the terminal at the wall in order to keep the water out.

IMPORTANT: Do not locate termination hood where excessive snow or ice buildup may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.

INSTALLATION

PROCEDURES

for Regency® AstroCapTM Direct

Vent System (Flex)

1)Locate the unit in the framing, rough in the gas. Locate the centerline of the termination andmarkwallaccordingly.Cuta10"(254mm) hole in the wall (inside dimension).

Note: A 1-1/2"(38mm) clearance around the liner must be maintained except that only a 1" (25mm) clearance is needed at the termination end. We recommend framing a 10"(254mm) x 10"(254mm)(insidedimensions)hole togivestructuralrigidityformounting the termination.

Note: If installing termination on a siding covered wall, furring strips must be used to ensure that the termination is not recessed into the siding.

Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace

23

Image 23
Contents P121 / P121LC / P121RC / P131 To the New Owner Manufactured Mobile Home RequirementsTable of Contents Copy of Safety Decal for P121/P121LC/P121RC/P131 Safety LabelMA Code CO Detector RequirementsImportant Message Save These Instructions InstallationGeneral Safety Information Installation ChecklistNon-load bearing SpecificationsP121LC-2 Left Corner Unit Locations see section Exterior Vent Termination Locations Locating Your GAS FireplaceCombustible Mantels ClearancesCorner Unit Framing DimensionsFraming and Finishing P121-2 See Thru P131-2 PierVenting Introduction Unit Assembly Prior to InstallationTop Standoff Assembly VentHeight Meters Minimum Feet RoofPitch Exterior Vent Termination LocationsSV4LB6 Rigid Pipe Venting Components ListVenting Arrangement Horizontal Terminations Horizontal or Vertical Terminations Rigid Pipe Venting SystemsRegency Direct Vent System Flex Propane & Natural Gas Rigid Pipe Venting Arrangements Horizontal TerminationsHorizontal Venting with Three 3 90o Elbows Horizontal Venting with Two 2 90o ElbowsPropane & Natural Gas Rigid Pipe Venting Arrangements Vertical TerminationsVertical Venting with Three 3 90o Elbows Vertical Venting with Two 2 90o ElbowsSet the unit in its desired location. Check Vertical Terminations This allows for small adjustmentsFor Regency AstroCapTM Direct Vent System Flex Installation ProceduresOffset Chart LPG Conversion Kit Contains Qty Conversion KIT #731-969 from NG to LPInstallation of the DC Sparker Ground Wire from Kit High Elevation Pilot AdjustmentGAS Line Installation GAS Pipe Pressure Testing327 329 326 328 LOG Installation327 P121-2 & P131-2 Corner Models Finishing TrimLouvers & Grills Diagram below Thermostat Wire TableDo not cut the ground terminal off under any circumstances Wiring DiagramsTerminal Block Location For Propane Units and Units Equipped with DC Spark BoxesOperating Instructions Shutdown ProcedureFirst Fire Aeration Adjustment Lighting ProcedureCopy of the Lighting Plate Instructions Normal Operating Sounds of GAS AppliancesMaintenance Remove Left & Right Side Base Brick Panels Removing ValveFAN Replacement Installing ValveDescription Parts ListP121-2 see Thru Main Assembly P131-2 Pier Main Assembly 204 225 P121RC-2 Right Corner Main AssemblyP121LC-2 Left Corner Main Assembly P121/P121LC/P121RC/P131-2 Burner Assembly & LOG SET Page Page Page Conditions WarrantyInstaller Please complete the following information
Related manuals
Manual 40 pages 33.79 Kb

P121LC, P121, P121RC, P131 specifications

The Regency P121RC, P121, P131, and P121LC are advanced technological innovations in the realm of heating, ventilation, and air conditioning (HVAC) systems. Designed for both residential and commercial applications, these models are known for their efficiency, reliability, and comfort-enhancing features.

The Regency P121RC is particularly notable for its high-efficiency rating, making it a popular choice for environmentally conscious consumers. With advanced heat pump technology, it provides optimal heating and cooling throughout the year, reducing energy consumption while maintaining a consistent indoor climate. The use of environmentally friendly refrigerants further emphasizes its commitment to sustainability.

The P121 model stands out for its cutting-edge smart technology integration. It is equipped with Wi-Fi connectivity, allowing users to control their HVAC systems remotely via a mobile application. This feature not only enhances convenience but also enables energy management, reducing operational costs through effective scheduling and monitoring.

The P131 model caters to larger spaces, thanks to its robust cooling and heating capabilities. It employs a variable-speed compressor that adjusts to the specific demands of the space, ensuring optimal performance while minimizing noise disruption. This model is also compatible with smart home systems, contributing to a seamless integration of technology within modern living environments.

Meanwhile, the P121LC is designed with energy conservation in mind, featuring a dual-stage heating and cooling system. Its advanced airflow technology ensures even distribution of temperature, promoting overall comfort and reducing the risk of hot or cold spots in a room. Like its counterparts, it supports remote operation through smart technology, offering users full control over their indoor climate.

In terms of construction, these models prioritize durability and longevity. They feature robust insulation and high-quality materials, which contribute to their energy efficiency and operational lifespan. The compact design also allows for flexible installation options, making them suitable for various types of spaces.

Overall, the Regency P121RC, P121, P131, and P121LC represent the pinnacle of modern HVAC technology, blending efficiency, innovative features, and user-friendly control options to provide optimal comfort in any setting. As homeowners and businesses increasingly prioritize sustainability and energy management, these models are set to play a vital role in achieving a more comfortable and eco-friendly future.