REQUIREMENTS

MA Code - CO Detector

5.08: Modifications to NFPA-54, Chapter 10

(2) Revise 10.8.3 by adding the following additional requirements:

(a)For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1.INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2.APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3.SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight

(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL

OBSTRUCTIONS".

4.INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c)MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1.Detailed instructions for the installation of the venting system design or the venting system components; and

2.A complete parts list for the venting system design or venting system.

(d)MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:

1.The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and

2.The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

(e)A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace

5

Image 5
Contents P121 / P121LC / P121RC / P131 To the New Owner Manufactured Mobile Home RequirementsTable of Contents Copy of Safety Decal for P121/P121LC/P121RC/P131 Safety LabelMA Code CO Detector RequirementsGeneral Safety Information InstallationInstallation Checklist Important Message Save These InstructionsNon-load bearing SpecificationsP121LC-2 Left Corner Unit Locations see section Exterior Vent Termination Locations Locating Your GAS FireplaceCombustible Mantels ClearancesFraming and Finishing Framing DimensionsP121-2 See Thru P131-2 Pier Corner UnitVenting Introduction Unit Assembly Prior to InstallationTop Standoff Assembly VentHeight Meters Minimum Feet RoofPitch Exterior Vent Termination LocationsSV4LB6 Rigid Pipe Venting Components ListVenting Arrangement Horizontal Terminations Horizontal or Vertical Terminations Rigid Pipe Venting SystemsRegency Direct Vent System Flex Propane & Natural Gas Rigid Pipe Venting Arrangements Horizontal TerminationsHorizontal Venting with Three 3 90o Elbows Horizontal Venting with Two 2 90o ElbowsPropane & Natural Gas Rigid Pipe Venting Arrangements Vertical TerminationsVertical Venting with Three 3 90o Elbows Vertical Venting with Two 2 90o ElbowsSet the unit in its desired location. Check Vertical Terminations This allows for small adjustmentsFor Regency AstroCapTM Direct Vent System Flex Installation ProceduresOffset Chart LPG Conversion Kit Contains Qty Conversion KIT #731-969 from NG to LPInstallation of the DC Sparker Ground Wire from Kit GAS Line Installation Pilot AdjustmentGAS Pipe Pressure Testing High Elevation327 329 326 328 LOG Installation327 P121-2 & P131-2 Corner Models Finishing TrimLouvers & Grills Diagram below Thermostat Wire TableDo not cut the ground terminal off under any circumstances Wiring DiagramsTerminal Block Location For Propane Units and Units Equipped with DC Spark BoxesFirst Fire Aeration Adjustment Shutdown ProcedureLighting Procedure Operating InstructionsCopy of the Lighting Plate Instructions Normal Operating Sounds of GAS AppliancesMaintenance Remove Left & Right Side Base Brick Panels Removing ValveFAN Replacement Installing ValveDescription Parts ListP121-2 see Thru Main Assembly P131-2 Pier Main Assembly 204 225 P121RC-2 Right Corner Main AssemblyP121LC-2 Left Corner Main Assembly P121/P121LC/P121RC/P131-2 Burner Assembly & LOG SET Page Page Page Conditions WarrantyInstaller Please complete the following information
Related manuals
Manual 40 pages 33.79 Kb

P121LC, P121, P121RC, P131 specifications

The Regency P121RC, P121, P131, and P121LC are advanced technological innovations in the realm of heating, ventilation, and air conditioning (HVAC) systems. Designed for both residential and commercial applications, these models are known for their efficiency, reliability, and comfort-enhancing features.

The Regency P121RC is particularly notable for its high-efficiency rating, making it a popular choice for environmentally conscious consumers. With advanced heat pump technology, it provides optimal heating and cooling throughout the year, reducing energy consumption while maintaining a consistent indoor climate. The use of environmentally friendly refrigerants further emphasizes its commitment to sustainability.

The P121 model stands out for its cutting-edge smart technology integration. It is equipped with Wi-Fi connectivity, allowing users to control their HVAC systems remotely via a mobile application. This feature not only enhances convenience but also enables energy management, reducing operational costs through effective scheduling and monitoring.

The P131 model caters to larger spaces, thanks to its robust cooling and heating capabilities. It employs a variable-speed compressor that adjusts to the specific demands of the space, ensuring optimal performance while minimizing noise disruption. This model is also compatible with smart home systems, contributing to a seamless integration of technology within modern living environments.

Meanwhile, the P121LC is designed with energy conservation in mind, featuring a dual-stage heating and cooling system. Its advanced airflow technology ensures even distribution of temperature, promoting overall comfort and reducing the risk of hot or cold spots in a room. Like its counterparts, it supports remote operation through smart technology, offering users full control over their indoor climate.

In terms of construction, these models prioritize durability and longevity. They feature robust insulation and high-quality materials, which contribute to their energy efficiency and operational lifespan. The compact design also allows for flexible installation options, making them suitable for various types of spaces.

Overall, the Regency P121RC, P121, P131, and P121LC represent the pinnacle of modern HVAC technology, blending efficiency, innovative features, and user-friendly control options to provide optimal comfort in any setting. As homeowners and businesses increasingly prioritize sustainability and energy management, these models are set to play a vital role in achieving a more comfortable and eco-friendly future.