Regency B36X Pilot Adjustment, GAS Pipe Pressure Testing, High Elevation, T. Valve Description

Page 35

INSTALLATION

PILOT ADJUSTMENT

Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).

Note: If you have an incorrect flame pattern, contact your FPI dealer for further instructions.

Incorrect flame pattern will have small, probably yellow flames, not coming into proper contact with the rear burner or thermopile or thermocouple.

B36X -NG System Data

Conversion Kit# 556-969

For 0 to 4500 feet altitude

Burner Inlet Orifice Sizes: #45

Max. Input Rating

18,500 Btu/h

Min. Input Rating

12,500 Btu/h

 

 

Supply Pressure

min.5.0" w.c.

 

 

Manifold Pressure

 

(High)

3.5"+/- 0.2" w.c.

Manifold Pressure

 

(Low)

1.6" +/- 0.2" w.c.

B36X - LP System Data

For 0 to 4500 feet altitude

Burner Inlet Orifice Sizes: #55

Max. Input Rating

17,500 Btu/h

Min. Input Rating

14,500 Btu/h

 

 

Supply Pressure

min.11.0" w.c.

 

 

Manifold Pressure

 

(High)

10"+/- 0.2" w.c.

Manifold Pressure

 

(Low)

6.4" =/- 0.2" w.c.

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.

The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.

Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.

1)Make sure the valve is in the "OFF" position.

2)Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a 1/8" wide flat screwdriver.

3)Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.

4)Light the pilot and turn the valve to "ON" position.

5)The pressure check should be carried out with the unit burning and the setting should be within the limits specified on the safety label.

6)When finished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" flat screwdriver. Note: Screw should be snug, but do not over tighten.

HIGH ELEVATION

This unit is approved in Canada for altitude to 4500 ft. (CAN/CGA-2.17-M91). For Natural Gas installations above 4500 ft. follow current CAN/ CGA-B149.1.

S.I.T. VALVE DESCRIPTION

1)Gas on/off knob

2)Manual high/low adjustment

3) Pilot Adjustment

4) Thermocouple Connection - option

5) Outlet Pressure Tap

6)Inlet Pressure Tap

7)Pilot Outlet

8)Main Gas Outlet

9)Alternative TC Connection Point

Regency Bellavista™ B36X Gas Fireplace

35

Image 35
Contents Regency Bellavista B36X Gas Fireplace Regency Bellavista B36X Gas Fireplace Information for MOBILE/MANUFACTURED Homes After First SaleTable of Contents Copy of Safety Decal Safety LabelMA Code CO Detector RequirementsUnit Dimensions DimensionsBefore YOU Start InstallationGeneral Safety Information Important Message Save These InstructionsHeatwave Duct System Optional Installation ChecklistDiagram Locating Your GAS FireplaceClearances Mantel LEG Clearances Mantel ClearancesFraming Framing Dimensions Description B36XFull Screen Doors Only FinishingImportant Finishing Detail Note Plates can be Folded out Unit Assembly Prior to Installation Before YOU StartScrew Position Baffle Plate Unit Assembly Prior to InstallationAdjustable Tension Latch location Venting Introduction Exhaust Assembly Intake Collar DiagramDiagram Exhaust Assembly Intake Collar Minimum Clearance Requirements Exterior Vent Termination RequirementsInstallation Vertical Venting Configurations Approved Venting Configurations6-5/8 Rigid Pipe Cross Reference ChartInstallation Installation Installation Horizontal Terminations Regency Direct Vent Flex System 5 X Rear Vent w/ Horizontal Termination Horizontal Terminations Rigid Pipe Venting Arrangements 5 XHorizontal Termination Top Vent No Vertical RiseHorizontal or Vertical Terminations Rigid Pipe Venting Systems58DVA-WT 6 5/8 Pipe Venting Arrangements Venting ArrangementsAllowable Vertical Terminations Horizontal Venting with TWO 2 90O Elbows Venting Arrangements Horizontal TerminationVertical Venting with Three 3 90O Elbows Horizontal Venting with Three 3 90O ElbowsAlternate Approved Caps Vertical Termination With CO-LINEAR Flex SystemFor Both Residential & Manufactured Homes Rigid Vent Systems Astrocapxl Unit InstallationThis allows for small adjustments Unit Installation With Vertical TerminationGAS Line Installation T. Valve Description Pilot AdjustmentGAS Pipe Pressure Testing High ElevationDo not cut the ground terminal off under any circumstances Aeration AdjustmentWiring Diagram Minimum Air Shutter OpeningFor Propane Units and Units Equipped with DC Spark Boxes Wiring Diagram for Gtmf RemoteHeat Defl ector Vent RESTRICTOR, Baffle & Heat Deflector InstallationDiagram 2 Vent restrictor installed on top exhaust assembly Baffl e PlateShut off the gas supply Conversion KIT# 556-969 from NG to LPConversion Kit Contains Qty Description Cap DC Sparker Generator Wires DC Sparker InstallationIgnitor Wire Piezo Sparker Ignitor WireEnsure that the logs are not in the unit Brick Panel InstallationBack Panel Installed Final Brick Panel Installation Handle with care. do not Force Into PositionSlots on Top Panel Panel InstallationOptional Stainless Steel / Black Enamel Black Enamel Panel Installation Notch LOG SET InstallationLog Kit #556-930 contains the following pieces Vermiculite2nd Grate Tab Notch in log BNotch in log F Notch in log D Lava Rocks Wall Thermostat Remote ControlWall Switch Installation Ground Lug FAN InstallationSee Diagram Slide the the Fan control boxAdjustable Tension Latch location Diagram Flush Glass Door InstallationTabs in Firebox Diagram Panel Optional Finishing Trim InstallationFlush Louvers and Flush Panel Installation LowerDo not tighten the screws leave them loose for the next step Full Screen Arch Door and Frame InstallationOperating Instructions Copy of Lighting Plate Instructions Maintenance Removing Valve Installing ValveDiagram 1 Remove the left and right screws Main Assembly Parts List2622 Burner Assembly Regency Bellavista B36X Gas Fireplace Regency Bellavista B36X Gas Fireplace Warranty Limited Lifetime WarrantyInstaller Please complete the following information

B36X specifications

The Regency B36X is a remarkable gas fireplace that combines elegance with efficiency, designed to seamlessly integrate into any contemporary or traditional living space. This model from Regency is especially popular for its powerful performance and stunning aesthetics, providing both warmth and a focal point for any room.

One of the standout features of the B36X is its impressive heating capabilities. It boasts a heat output of up to 34,000 BTUs, allowing it to efficiently warm spaces up to 1,500 square feet, making it suitable for larger areas. The fireplace utilizes a direct vent system, which ensures that combustion gases are expelled outside while drawing in fresh air for combustion. This contributes to enhanced indoor air quality, as it does not rely on the oxygen from within the home.

In terms of design, the B36X features a sleek, contemporary appearance, characterized by its large viewing area framed by a clean face. Its innovative design maximizes the flame visibility, creating a captivating ambiance. Homeowners can choose from a variety of finishing options, including versatile color choices and customizable trim, allowing the fireplace to match specific interior decor styles.

The fireplace is equipped with advanced technology, including an electronic ignition system that ensures reliable, effortless lighting. For added convenience, optional remote control features enable users to adjust the flame height and temperature with ease. Furthermore, the B36X also supports the installation of a wall thermostat, providing enhanced temperature control and efficiency.

Safety is a crucial element of the Regency B36X. Its glass front is designed with safety in mind, remaining cooler to the touch, which is especially important for households with children or pets. Additionally, the unit is equipped with built-in safety shut-off features that activate in the event of any irregularities in operation.

Energy efficiency is another hallmark of the B36X. Its high efficiency rating ensures that the fuel consumed translates into effective heating, ultimately leading to savings on utility bills. The fireplace meets or exceeds various environmental standards, making it an eco-conscious choice for homeowners looking to reduce their carbon footprint.

In conclusion, the Regency B36X offers a perfect blend of style, functionality, and advanced technology. With its powerful heating capabilities, customizable designs, and enhanced safety features, it stands out as an exceptional choice for anyone looking to enhance their home’s comfort and aesthetics.