BURNER SETUP & BOILER OPERATION
5. BURNER SETUP & BOILER OPERATION
Burn only #2 Fuel Oil in this
CAUTION appliance. Do not use gasoline, crankcase drainings or any oil containing gasoline.
A.BURNER INSTALLATION
1.The oil burner is supplied with a mounting flange fixed in position.
2.Mount the burner to the burner mounting plate (item 5) with four (4) 5/16" studs and nuts provided.
Be sure high temperature gasket is NOTICE between the burner mounting flange
and the burner mounting plate.
3.Care must be taken when routing the oil lines so not to interfere with the opening and closing of the burner mounting plate. Flexible oil lines or flared copper disconnects with valves (when copper lines are used) may be installed to assure full opening of the burner mounting plate when servicing.
#C7001026 from Riello dealer.
4.Oil burner specifications:
For information pertinent to the oil burner such as nozzle sizing, fuel supply piping, adjusting or servicing, refer to the charts in this section and the burner installation manual.
B.BURNER START-UP AND ADJUSTMENT
CAUTION | Do not start the burner unless all |
| cleanout doors are in place. |
1.Burner should start automatically when thermostat is turned up and main boiler service switch is turned on. If burner does not start, check to be sure there is oil in the tank and push reset button on burner control:
Beckett: Square red button. Carlin: Round red button.
Riello: Round red button inside clear flexible
cover on back of burner cover.
If burner still does not start, contact serviceman.
Do not attempt to start the burner CAUTION when excess oil has accumulated,
when the unit is full of vapor, or when the combustion chamber is very hot.
2.Adjust burner and barometric draft control for
highest CO² (Maximum 13%) while maintaining a 0 Smoke and
All adjustments must be made using suitable instruments such as found in a Bacharach Combustion Test Kit.
3.Burner and boiler can be shut down by turning down the thermostat and moving the main boiler service switch to the "off" position.
4.See burner manufacturer’s manual for further information regarding the burner.
C.CHECK BOILER CONTROLS
1.Limit and Operating Controls:
a.Lower the set point of each control until the burner shuts down. Note that the system pressure (or temperature) corresponds to the desired set point.
b.Return the controls to the desired set point.
2.Low Water
D.PURGE AIR FROM THE SYSTEM (WATER BOILERS ONLY)
1.Purge the system using purge valves, isolating zones in the process or use system vents. Do not operate the pump(s) while purging. Pumps will hold air in the eye of the impeller.
2.Allow the system to reach 180°F and use manual vents, if installed, to remove any remaining air. Watch the pressure gauge as the system approaches 180°F. If the pressure exceeds the design operating pressure, check:
a.Fill valve pressure.
b.Expansion or compression tank operation and sizing.
13