MAINTENANCE

A.GENERAL

1.Check pipes adjacent to cold walls or in unheated spaces. Insulate and tape them if necessary to be sure they can't freeze up. Keeping the water moving at all times will reduce the likelihood of freezing.

2.If there is considerable foreign matter in the boiler water, the boiler should be shut down and allowed to cool, then drained and thoroughly flushed out. Drain the boiler at the drain cock. Pipe the drain cock to a suitable drain or containment device (if antifreeze is used). Flush the system to remove remaining matter. If there is evidence that hard scale has formed on the internal surfaces, the boiler should be cleaned by chemical means as prescribed by a qualified water treatment specialist.

3.There must be no signs of continuous wetness at the chimney. If signs of continuous wetness are observed, a qualified service agency must be consulted to modify the vent configuration to prevent the formation of condensate, which may damage the vent pipe.

Do not use this appliance if any part WARNING has been under water. Improper or

dangerous operation may result. Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any control which has been under water.

B.DAILY MAINTENANCE (WITH BOILER OPERATING)

Daily boiler observation can be performed by the owner. If any potential problems are found, a qualified installer or service technician/agency must be notified.

1.Remove any combustible materials, gasoline and other flammable liquids and substances that generate flammable vapors from the area where the boiler is contained. Make certain that the boiler area has ample air for combustion and ventilation and that there are no obstructions to the free flow of air to and from the boiler.

2.Observe general boiler conditions (unusual noises, vibrations, etc.)

3.Observe operating temperature and/or pressure gauge on the boiler. Boiler pressure should never be higher than 5 psi below the rating shown on the safety relief valve. The valve rating can be found on the top of the safety relief valve. Boiler temperature should never be higher than 250°F.

4.Check for water leaks in boiler and system piping.

C.WEEKLY MAINTENANCE (WITH BOILER OPERATING)

1.Flush float-type low-water cut-off (if used) to remove sediment from the float bowl as stated in the manufacturer's instructions.

D.MAINTENANCE OF SAFETY RELIEF VALVE

1.Check function and maintain safety relief valve as specified by manufacturer, typically every other month or every month, per the instructions on the tag on the safety relief valve.

E.MONTHLY MAINTENANCE (WITH BOILER OPERATING)

1.Check boiler room floor drains for proper functioning.

2.Test probe type low-water cut-off (if used) by using the Push-to-Test Button.

Turn off power to boiler before

CAUTION adjusting limit control.

3.Test limit by lowering the limit set point until the burner shuts down. When proper operation is confirmed, return the set point to original setting.

4.Follow additional instructions in the Burner Manual for proving the burner component operation.

F.MAINTENANCE – ANNUAL

Entire heating system, including NOTICE boiler, burner and venting system,

must be inspected at least once a year by a qualified heating professional. Boiler is to be cleaned at least once a year.

Disconnect all power to the burner

WARNING before accessing combustion chamber.

TO CLEAN:

1.Remove top jacket panel and flue collector cover plate, Item 11 (Figure 2.1 or 2.2).

17

Image 19
Contents Series WBV/WV Table of Contents Installation Clearance Using this ManualSpecial Attention Boxes Required from Jacket Recommended From Jacket for PreinstallationClearances AIR for Combustion and VentilationOld New Comments Installation SurveyChimney / Vent and Draft Control Planning the LayoutJacket Assembly Knockdown Boilers Boiler Placement and AssemblySetting the Boiler Connecting the Flue OutletSteam boiler Water Boiler Piping Pressure Test Block AssemblyPiping and Controls Boiler Return ClearanceControls Tankless Heater or CoverplateFloat Low Water Cut-off Electrical Burner WiringGeneral Water Boilers, Knockdown Steam with Float Low Water Cut-Off Zoning with Circulators Check Boiler Controls Burner Setup & Boiler OperationBurner Installation Burner START-UP and AdjustmentCleaning the boiler requires the use Clean the Boiler Steam Boilers only65 60 B Hago Hago85 x 60 B Hago DELMaintenance Monthly Maintenance with Boiler Operating Daily Maintenance with Boiler OperatingWeekly Maintenance with Boiler Operating Maintenance of Safety Relief ValveOpened to facilitate this operation If a Long Shutdown is RequiredBoiler Jacket Rear of Jacket to Boiler Dimensions & RatingsBoiler Jacket Rear of Jacket to Top DepthInput Water ContentHeating CapacityItem No Stock Code Description Additional Information Repair PartsPage Page Series WBV/WV