1.1.10 Configuring the Humidifier Maintenance Interval
Select “Maintenance” in the settings menu, then press the <Set> key. In the following dialogue set the desired maintenance interval time in hours. After the maintenance interval time has elapsed a maintenance message appears in the display and the yellow LED lights up. If the maintenance is not performed and the maintenance indication is not reset within a certain time (168 h) , an error message is triggered. Factory setting: 800 h Setting range: 100... 50000 h
Note: to determine the maintenance interval time please refer to 1.3 in section
1.1.11Activating/deactivating the softstart function
If the mats in the humidifier boxes became dry due to a operation interruption, they need a certain time until they are again moistened with water. In order to prevent too much water flows over the humidification boxes in this phase and water droplets are carried in the air flow, the amount of water can be reduced for a fixed time with the “Softstart” function.
Select “Softstart” in the settings menu, then press the <Set> key. In the modification dialogue you can activate or deactivate the softstart function. Factory setting: Off Options: Off (Softstart function deactivated)
On (Softstart function activated)
10-10