Nortec MH Series installation manual Troubleshooting 1.2.1 System Faults

Page 33

1.2TROUBLESHOOTING 1.2.1 System Faults

 

Warning

 

Error

Cause

Remedy

LED

Display

LED

 

Display

 

 

MH Card

missing (Test run

MH Card Missing

 

 

 

possible)

 

 

 

 

 

 

Red

 

Red lights

 

 

No MH Card

Install MH

flashes

 

 

 

 

installed on the

Card or start

 

 

 

 

 

control board.

test run.

 

 

MH Card is

Empty

 

 

 

--

--

Red lights

 

 

No data stored on

Install new

 

 

 

 

 

the MH Card

MH Card.

 

 

 

 

 

 

 

 

MH Card is

defective

 

 

--

--

Red lights

 

 

Invalid data stored

Install new

 

 

 

 

 

on the MH Card

MH Card.

 

 

 

 

 

 

 

 

MH Card is

incompatible

 

 

--

--

Red lights

 

 

The MH Card is

Install new

 

 

 

 

 

not compatible

MH Card.

 

 

 

 

 

with the hardware

Modify basic

 

 

 

 

 

or the basic

settings.

 

 

 

 

 

settings on the

 

 

 

 

 

 

control board.

 

 

 

Unit Module

B missing

 

 

--

--

Red lights

 

 

No response from

Plug in flat

 

 

 

 

 

module B. Flat

ribbon cable,

 

 

 

 

 

ribbon cable

plug in 120V

 

 

 

 

 

interrupted or

supply

 

 

 

 

 

disconnected

cable.

 

 

 

 

 

120V supply cable

 

 

 

 

 

 

disconnected.

 

 

 

Wrong parameter settings

 

 

--

--

Red lights

 

 

Data of CPU and

Install

 

 

 

 

 

MH Card do not

correct MH

 

 

 

 

 

match.

Card.

 

 

 

 

 

 

Contact your

 

 

 

 

 

 

Nortec

 

 

 

 

 

 

supplier.

 

 

Hardware Fault (flash)

 

 

--

--

 

 

 

CPU on control

Replace

 

 

 

 

 

board defective.

control

 

 

 

 

 

 

board.

 

 

Hardware Fault (clock)

 

 

--

--

 

 

 

CPU on control

Replace

 

 

 

 

 

board defective.

control

 

 

 

 

 

 

board.

10-30

Page 29 2008-12-03

Image 33
Contents 2544831-A SeriesTMRevision Number Date Date Put Manual Table of Contents This page Intentionally Left Blank Introduction Limitation SafetySafekeeping Copyright protectionDisplay Function of the Display and Operating ElementsRemote Operating and Fault Indication Switching the Control Unit on and OFFMenu Overview Overview and Operating of the MenuExplanation of the Status Information Indication Status Explanation of Configuration SettingsInfo Page Clean Trg Info Page UV Module option Info Page Box dryingPath Main menu Info Unit Status Explanation of Unit InformationPath Main menu Info Error History Explanation of Error History ListConfiguration Launching the unit settings menu Unit SettingsFactory setting English Select dialogue languageDescription of the Settings Control SettingsDescription of the Settings Setting the capacity limitationFactory setting Options Factory settingFactory setting Drain Setting the Cleaning Mode Mhtc Reflow onlyConfiguring the cleaning trigger 1 Clean Trg 10-10 Configuring the humidification box drying Activating/deactivating the softstart function Configuring the Humidifier Maintenance IntervalPerforming remote relay tests Seconds Setting range 1...600 Seconds Factory setting NoneThis page Intentionally Left Blank Operational Functions Briefly press the drain key . The drain/flush Carrying OUT Manual Draining / Pipe FlushingEmpties. The yellow LED flashes Yellow LED flashesPath Main menu User Password entry 8808 Maintenance Resetting the Maintenance IndicationResetting the Hours Meter of the UV Lamp Troubleshooting Fault Indication Fault IndicationTroubleshooting 1.2.1 System Faults Unit Faults Tub the float is not open Maximum lifespan UV lamp reached 2008-12-03 Resetting the Error Indication Warranty Authorized Agent