1.1.4 Setting the capacity limitation
Select “Power Limit” in the settings menu, then press the <Set> key. In the upcoming modification dialogue set the desired capacity limitation in % of the maximum capacity of the humidifier.
Factory setting: 100 %
Setting range: 30...100 %
1.1.5 Configuring the supply pipe flushing
Select “Inlet Flush” in the settings menu, then press the <Set> key.
Used to configure the unit to flush supply lines even if there is no demand signal. You can;
-enable / disable inlet flush
-set length of flush
-set time between flushes
DESCRIPTION OF THE SETTINGS
Inlet Flush | Enable or disable the supply pipe flushing. | |
| Factory setting: | On |
| Options: | On (enable) |
|
| Off (disable) |
|
| |
Drain Time | Setting the flushing time in seconds. | |
| Factory setting: | 60s |
| Setting range: | 5...600s |
|
| |
Periodic Int | Setting the time without demand after which | |
| the supply pipe should be flushed. | |
| Factory setting: | 12.0 h |
| Setting range: | 0.5 ... 24.0 h |
|
|
|