1.1.3 Control Settings
Select “Controls” in the settings menu, then press the <Set> key.
The control settings appear. The settings available depend on the selected signal source and the control type. The opposite display shows the maximum number of settings available.
DESCRIPTION OF THE SETTINGS
SignalSource | Selecting the signal source. | |
| Factory setting: Analog | |
| Options: | Analog |
|
| Modbus |
Hum.Control: | Selecting the control type. | |
| Factory setting: External | |
| Options: External (external continuous controller) | |
| 24VOn/Off (external On/Off humidistat) | |
| Int. (P) (Internal P controller) | |
| Int. (PI) (Internal PI controller) | |
Controlsign. | Selecting the control signal. | |
| NOTE: This setting is available only if control type | |
| “External”, “Int. (P)” or “Int. (PI)” is selected. | |
| Factory setting: | |
| Options: | |
| 16V, | |
Hum.Setpoint: | Setting the nominal humidity value inn %rh. | |
| NOTE: This setting is available only if the internal P | |
| or PI controller is activated. | |
| Factory setting: 50 %rH | |
| Setting range: 20...99 %rH | |
| Setting the proportional range inn % for the internal | |
| P/PI conntroller. |
|
| NOTE: This setting is available only if the internal P | |
| or PI controller is activated. | |
| Factory setting: 18 % | |
| Setting range: | 1...100 % |
| Setting the integral time in minutes for the internal | |
| PI controller. |
|
| NOTE: This setting is available only if the internal P | |
| or PI controller is activated. | |
| Factory setting: 18 Minutes | |
| Setting range: | 1...60 Minutes |