Nortec MH Series installation manual Control Settings, Description of the Settings

Page 17

1.1.3 Control Settings

Select “Controls” in the settings menu, then press the <Set> key.

The control settings appear. The settings available depend on the selected signal source and the control type. The opposite display shows the maximum number of settings available.

DESCRIPTION OF THE SETTINGS

SignalSource

Selecting the signal source.

 

Factory setting: Analog

 

Options:

Analog

 

 

Modbus

Hum.Control:

Selecting the control type.

 

Factory setting: External

 

Options: External (external continuous controller)

 

24VOn/Off (external On/Off humidistat)

 

Int. (P) (Internal P controller)

 

Int. (PI) (Internal PI controller)

Controlsign.

Selecting the control signal.

 

NOTE: This setting is available only if control type

 

“External”, “Int. (P)” or “Int. (PI)” is selected.

 

Factory setting: 0–10V

 

Options: 0–5V, 1–5V, 0–10V, 2–10V, 0–16V, 3.2–

 

16V, 0–20mA, 4–20mA

Hum.Setpoint:

Setting the nominal humidity value inn %rh.

 

NOTE: This setting is available only if the internal P

 

or PI controller is activated.

 

Factory setting: 50 %rH

 

Setting range: 20...99 %rH

P-Band:

Setting the proportional range inn % for the internal

 

P/PI conntroller.

 

 

NOTE: This setting is available only if the internal P

 

or PI controller is activated.

 

Factory setting: 18 %

 

Setting range:

1...100 %

Integr.-Time:

Setting the integral time in minutes for the internal

 

PI controller.

 

 

NOTE: This setting is available only if the internal P

 

or PI controller is activated.

 

Factory setting: 18 Minutes

 

Setting range:

1...60 Minutes

10-10

Page 13 2008-12-03

Image 17
Contents 2544831-A SeriesTMRevision Number Date Date Put Manual Table of Contents This page Intentionally Left Blank Introduction Limitation SafetySafekeeping Copyright protectionDisplay Function of the Display and Operating ElementsRemote Operating and Fault Indication Switching the Control Unit on and OFFMenu Overview Overview and Operating of the MenuExplanation of the Status Information Indication Status Explanation of Configuration SettingsInfo Page Clean Trg Info Page UV Module option Info Page Box dryingPath Main menu Info Unit Status Explanation of Unit InformationPath Main menu Info Error History Explanation of Error History ListConfiguration Launching the unit settings menu Unit SettingsFactory setting English Select dialogue languageDescription of the Settings Control SettingsDescription of the Settings Setting the capacity limitationFactory setting Options Factory settingFactory setting Drain Setting the Cleaning Mode Mhtc Reflow onlyConfiguring the cleaning trigger 1 Clean Trg 10-10 Configuring the humidification box drying Activating/deactivating the softstart function Configuring the Humidifier Maintenance IntervalPerforming remote relay tests Seconds Setting range 1...600 Seconds Factory setting NoneThis page Intentionally Left Blank Operational Functions Briefly press the drain key . The drain/flush Carrying OUT Manual Draining / Pipe FlushingEmpties. The yellow LED flashes Yellow LED flashesPath Main menu User Password entry 8808 Maintenance Resetting the Maintenance IndicationResetting the Hours Meter of the UV Lamp Troubleshooting Fault Indication Fault IndicationTroubleshooting 1.2.1 System Faults Unit Faults Tub the float is not open Maximum lifespan UV lamp reached 2008-12-03 Resetting the Error Indication Warranty Authorized Agent