Generac Power Systems H-100 Governor Speed Regulator Option Chart, ‹ Remote Trending

Page 11

General Information

H-100 Control Panel Technical Manual

Dump Enable — Indicates if extra load dump gov- ernor compensation is desired to reduce increase in frequency caused by drop in load. The following three selections are available:

-No Dump — No additional compensation.

-Dump — Reset governor algorithm when load dump detected.

-Dump & Hold — Same as Dump, but also hold throttle closed until frequency back in range.

Engine Linearization — Selects engine torque to actuator position translation curve for Bosch Actuators.

0 = No conversion - torque = position

1 = Butterfly Actuator with minimum position same as unpowered actuator

2 = Diesel arm with Horizontal rod

3 = Diesel arm with Vertical rod

4 = Same as 1, but minimum position at actuator mechanical stop

5 = Same as 4, but with limited position resolu- tion of 1

6 = Same as 4, but with added energy to accom- modate throttles that normally operate in the nearly closed position at no load

Integral limit/Antiwindup — Choose whether to use an integral limit or an anti-windup strategy.

YES = integral limit NO = anti-windup

Limit/windup parameter — If “Integral Limit” is selected, this is the maximum value the integral is allowed. If “Anti-Windup” is selected, this is the integral value above which the anti-windup algo- rithm becomes active.

Pwm Counts per ampx10 — Number of PWM counts required to drive one tenth of an amp into a linear current driven actuator. This only applies to the “Linear Current” actuator type.

Desynch Offset — Offset of –0.9 to +0.9 Hertz to be applied to the target frequency to improve passive synchronizing by Automatic Transfer Switches. If an in-phase or synchronized transfer is required, use this setting to adjust the generator frequency to 0.1 Hz above nominal Utility frequency.

Governor (Speed Regulator) Option Chart

NO.

PARAMETER

UNITS

1

Standby KP

-

2

Standby KI

-

3

Standby KD

-

4

QuietTest® KP

-

5

QuietTest® KI

-

6

QuietTest® KD

-

7

Actuator Type

-

8

Actuator Offset

-

9

Actuator Fullscale

-

10

Actuator Normal Start Position

-

11

Actuator QuietTest® Start Position

-

12

Soft Start Time

Seconds

13

Soft Start Frequency

Hz

14

Diesel

Y/N

15

Dump Enable

-

16

Engine Linearization

-

17

Integral limit/Antiwindup

Y/N

18

Limit / windup parameter

-

19

Pwm Counts per ampx10

-

20

Desynch Offset

Hz

 

 

 

TRENDING

Just like in the PM-DCP, there are two types of trend- ing available - Remote and Local.

‹REMOTE TRENDING

GenLink performs remote trending by polling the controller for the selected data at the desired rate. Up to 8 analog channels can be monitored at a 0.3 second rate. If a faster rate is desired, reducing the number of analog channels monitored will allow for a

0.1second rate. The polling rate can be varied from

0.1seconds to several hours. GenLink can save the data to a file and/or display it as a near real-time graph. The file is MS Excel compatible ( CSV format ). Examples of things you can trend are the generator frequency response (in 0.1 second steps) to a block load or Generated power over a day.

9

Image 11
Contents Control Panel Technical Manual  General Hazards  Inside Front Cover Authorized Service Dealer Location‹ Customization FeaturesPanel Setup IntroductionThen Measurement Engine‹ Analog Channels ‹ Analog Maths‹ Analog Alarms ‹ Analog Sensor Ratings Output Functions‹ Other Analog Options ‹ Spare Analog ChannelsParameter Units ‹ Engine SettingsEngine Management ‹ Generator ParametersCLOSED? Starting and Stopping Sequence DiagramsGovernor Speed Regulator Option Voltage Regulator Option ChartVoltage Regulator Option ‹ Remote Trending Governor Speed Regulator Option ChartTrending ‹ Local Trending ‹ Genlink Local Trending SetupILC ‹ Right Display Front Panel Display‹ Left Display Pages ‹ Left DisplayAlrm Log SwitchVolts Other Power‹ Alarms Graph HzEngine General Information Status Service Generator Diagnostics General Information EXERCISE/HTS TDN Event LOG Alarm LOGHome Control PanelI2T Current Monitoring Option Maintenance SettingsAIR/FUEL Ratio Control Option Internal Exercise Function Quiettest Setup Using GenlinkNormal Exercise Setup Using Genlink Quiettest Setup Using Front Panel General Information General Information Normal Exercise Setup Using Front Panel General Information General Information SET Date and Time ‹ Date and Time Setup Using Genlink‹ Date and Time Setup Using Front Panel Adjust Display Contrast ‹ HTS Setup Using Front Panel ‹ HTS Setup Using GenlinkGeneral Information Remote Annunciator Connection Option NEW Generation Genlink NGG CommunicationsLinear POLY1ST Appendix a Analog FunctionsThermistor Pressure POLY3RDCurrent Calscale POLY1STN2‹ H-100 Analog Inputs Appendix B H-100 General I/O and Connector Information‹ H-100 Digital Inputs ‹ H-100 Digital Outputs‹ H-100 Digital Output Functions GOV POS HI Alarm Analog 6 FaultFuel PRS Fault Inlt TMP FaultENG RPM HI Alarm TOT PWR HI AlarmTOT PWR LO Alarm GEN Freq FaultChck C PHS ROT Fault RLY ActiveUSR Config Chck V PHS ROTWire Signal Description ‹ H-100 Connector PIN DescriptionsAppendix C Miscellaneous H-100 Internal ALARMS/WARNINGS Control Panel Technical Manual Control Panel Technical Manual Generac Power SYSTEMS, INC

H-100 specifications

Generac Power Systems H-100 is an innovative and robust product that has garnered attention for its reliability and performance in power generation. This generator is primarily designed for both residential and commercial applications, providing a seamless backup power solution during outages.

One of the standout features of the H-100 is its powerful engine. Equipped with a state-of-the-art gas engine, this generator can deliver up to 100 kW of power, ensuring that homes, businesses, and critical facilities remain operational even in the most challenging conditions. The engine is engineered for efficiency and longevity, reducing maintenance needs and minimizing fuel consumption.

Another significant aspect of the H-100 is its advanced Smart Management System. This technology ensures optimal power usage by intelligently distributing the electrical load among connected devices. By prioritizing essential circuits, the generator maximizes efficiency and prolongs operational time during power outages.

The H-100 also boasts a remarkable noise reduction feature. Its innovative design includes sound attenuation measures, allowing the generator to operate quietly, which is particularly beneficial in residential areas where noise pollution can be a concern. This focus on quieter operation enhances user comfort and complies with noise regulations.

Durability is a key characteristic of the Generac H-100. Constructed with high-quality materials, it is designed to withstand harsh weather conditions and heavy usage. This generator is built for longevity, providing users with reliable performance and peace of mind.

The H-100 is also equipped with a user-friendly control panel. This intuitive interface allows users to monitor the generator's performance, manage settings, and perform necessary maintenance checks easily. The integration of remote monitoring capabilities enables users to assess the generator's status from anywhere, adding an extra layer of convenience.

Lastly, Generac Power Systems offers comprehensive support and resources for H-100 users. Their commitment to customer service includes accessible informational materials, a reliable warranty program, and a national network of service professionals. This ensures that users receive the assistance they need to maintain their generators optimally.

In summary, the Generac Power Systems H-100 stands out as a reliable, efficient, and user-friendly power generation solution. With its robust engine, smart management system, noise reduction features, and durable construction, it is well-suited to meet the demands of both residential and commercial applications.