Generac Power Systems Understanding Generac Genlink Features in the H-100 Control Panel

Page 16

General Information

H-100 Control Panel Technical Manual

Press the “ENTER” button.

This is a typical System Alarm and Warning page. The n/a indicates there is not an alarm or warning to display on that line. As depicted, this display indi- cates a Fuel Pressure alarm for low pressure. This would be a common alarm for a system that has the gas line turned off. The “Al” indicates it is an alarm. The “*” indicates the alarm has not been acknowl- edged. The “DI2/FUEL PRESS” message indicates it is a fuel pressure alarm (DI2 was included in the text by the user to indicate it is Digital Input #2). The “Lo” indicates the alarm was tripped because the input value fell below a set threshold.

The message format symbols are explained below:

First 2 characters:

Wr – Warning

Al – Non-shutdown alarm

SD – Shutdown alarm

Third Character:

*– Has not been acknowledged Last 2 Characters:

Sn – Sensor failure

Hi – Tripped by being greater than threshold Lo – Tripped by being less than threshold (blank) – Internal alarm or warning

Press the “ENTER” button while the cursor is on "ACK" to acknowledge the alarm.

The “*” is now gone since the alarm has been acknowledged.

Turn the gas line on.

The alarm has cleared since the gas pressure is now adequate.

Move the cursor to the on the bottom line by press- ing the button twice or the button once.

Press the “ENTER” button to see the next page.

Press the “ENTER” button to see the next page.

ENGINE

There are four Engine Parameter pages. In most H- 100 Control Panels, there are spare analog channels available or unused analog channels. They can be displayed on these pages. If they are not configured, they will not be displayed.

Do the following to view the engine parameter pages:

Press the “MENU” button.

14

Image 16
Contents Control Panel Technical Manual  General Hazards  Authorized Service Dealer Location Inside Front CoverFeatures Panel SetupIntroduction ‹ CustomizationMeasurement Engine ‹ Analog Channels‹ Analog Maths Then‹ Analog Alarms Output Functions ‹ Other Analog Options‹ Spare Analog Channels ‹ Analog Sensor Ratings‹ Engine Settings Engine Management‹ Generator Parameters Parameter UnitsStarting and Stopping Sequence Diagrams CLOSED?Voltage Regulator Option Voltage Regulator Option ChartGovernor Speed Regulator Option Trending Governor Speed Regulator Option Chart‹ Remote Trending ILC ‹ Genlink Local Trending Setup‹ Local Trending Front Panel Display ‹ Left Display Pages ‹ Left Display ‹ Right DisplayVolts SwitchAlrm Log Power ‹ AlarmsGraph Hz OtherEngine General Information Status Service Generator Diagnostics General Information EXERCISE/HTS TDN Alarm LOG HomeControl Panel Event LOGAIR/FUEL Ratio Control Option Maintenance SettingsI2T Current Monitoring Option Quiettest Setup Using Genlink Internal Exercise FunctionNormal Exercise Setup Using Genlink Quiettest Setup Using Front Panel General Information General Information Normal Exercise Setup Using Front Panel General Information General Information ‹ Date and Time Setup Using Front Panel ‹ Date and Time Setup Using GenlinkSET Date and Time Adjust Display Contrast ‹ HTS Setup Using Genlink ‹ HTS Setup Using Front PanelGeneral Information NEW Generation Genlink NGG Communications Remote Annunciator Connection OptionAppendix a Analog Functions ThermistorPressure POLY3RD Linear POLY1STPOLY1STN2 Current CalscaleAppendix B H-100 General I/O and Connector Information ‹ H-100 Analog Inputs‹ H-100 Digital Outputs ‹ H-100 Digital Inputs‹ H-100 Digital Output Functions Analog 6 Fault Fuel PRS FaultInlt TMP Fault GOV POS HI AlarmTOT PWR HI Alarm TOT PWR LO AlarmGEN Freq Fault ENG RPM HI AlarmFault RLY Active USR ConfigChck V PHS ROT Chck C PHS ROT‹ H-100 Connector PIN Descriptions Wire Signal DescriptionAppendix C Miscellaneous H-100 Internal ALARMS/WARNINGS Control Panel Technical Manual Control Panel Technical Manual Generac Power SYSTEMS, INC