General Information
This is a typical first Generator Parameter page for a single phase system.
LINE 1: Phase titles for the voltage and current
– voltage title/current title.
LINE 2:
LINE 3: Neutral current and Line currents in Amps RMS.
LINE 4: Generator frequency in Hz followed by the “More” field to allow page selection.
Press the “ENTER” button.
This is a typical third Generator Parameters page. It graphically displays the percent of i2t thermal limit currently attained. If the limit is exceeded, an alarm will be set and the generator will shutdown to protect the alternator. This display will then show % Temp >Over Limit<”. GenLink can provide more informa- tion regarding actual limits exceeded. This page is disabled if the i2t function is disabled.
This is a typical second Generator Parameter page for a three phase system.
LINE 1: Total system real power in kW.
LINE 2: Total system power factor.
LINE 3: Percentage of the system rated power being used.
LINE 4: The “More” field to allow page selection.
This is a typical second Generator Parameter page for a single phase system.
LINE 1: Phase titles for the power and power factor
– Total,
LINE 2: Real power in kW – Total system,
LINE 3: Power Factor – Total system,
LINE 4: The “More” field to allow page selection.
Press the “ENTER” button.
DIAGNOSTICS
There are six System Diagnostic pages. They are digi- tal inputs page, digital outputs page, two analog input pages,
Do the following to view the diagnostics pages:
Press the “MENU” button.
Press the button twice and the button.
Press the “ENTER” button.