Generac Power Systems H-100 technical manual General Information

Page 17

General Information

H-100 Control Panel Technical Manual

This is a typical second engine parameter page. The first two values on this page are not able to be config- ured as other values.

Press the button.

Press the “ENTER” button.

This is a typical first engine parameter page. The three values on this page are not able to be configured as other values.

LINE 1: Oil Temperature (Analog Channel #1) in degrees Fahrenheit.

LINE 2: Oil Pressure (Analog Channel #3) in pounds per square inch.

LINE 3: Coolant Temperature (Analog Channel #2) in degrees Fahrenheit.

LINE 4: “More” field to allow page selection.

If any of these signals are not configured, they will dis- play “n/a” for their value such as the Oil Temperature shown above.

Press the “ENTER” button.

LINE 1: Engine RPM

LINE 2: Battery Voltage in Volts DC.

If any of these signals are not configured, they will display “n/a” for their value.

LINE 3: Normally Battery Charger Current (Analog Channel #9). If it is not configured, the line will be blank.

LINE 4: “More” field to allow page selection.

Press the “ENTER” button.

This is a typical third engine parameter page.

LINE 1: Total number of hours the engine has run.

LINE 2: Coolant Level Sensor (Analog Channel #4) reading in steps 0 - 1023.

LINE 3: Often the Fuel Level Sensor (Analog Channel #5) reading in %. As depicted, Analog Channel #5 is not configured – leaving the line blank.

LINE 4: “More” field to allow page selection.

Press the “ENTER” button.

This is a typical fourth engine parameter page.

LINE 1: Auxiliary Analog Channel input (Analog Channel #6).

LINE 2: Throttle Position Sensor (Analog Channel #7) reading in steps 0 - 1023.

LINE 3: Emissions Sensor (Analog Channel #8) reading. As depicted, Analog Channels #6 and #8 are not configured – leaving the lines blank.

LINE 4: “More” field to allow page selection.

15

Image 17
Contents Control Panel Technical Manual  General Hazards  Inside Front Cover Authorized Service Dealer LocationPanel Setup FeaturesIntroduction ‹ Customization‹ Analog Channels Measurement Engine‹ Analog Maths Then‹ Analog Alarms ‹ Other Analog Options Output Functions‹ Spare Analog Channels ‹ Analog Sensor RatingsEngine Management ‹ Engine Settings‹ Generator Parameters Parameter UnitsCLOSED? Starting and Stopping Sequence DiagramsGovernor Speed Regulator Option Voltage Regulator Option ChartVoltage Regulator Option ‹ Remote Trending Governor Speed Regulator Option ChartTrending ‹ Local Trending ‹ Genlink Local Trending SetupILC ‹ Left Display Pages Front Panel Display‹ Left Display ‹ Right Display Alrm Log Switch Volts ‹ Alarms PowerGraph Hz OtherEngine General Information Status Service Generator Diagnostics General Information EXERCISE/HTS TDN Home Alarm LOGControl Panel Event LOGI2T Current Monitoring Option Maintenance SettingsAIR/FUEL Ratio Control Option Internal Exercise Function Quiettest Setup Using GenlinkNormal Exercise Setup Using Genlink Quiettest Setup Using Front Panel General Information General Information Normal Exercise Setup Using Front Panel General Information General Information SET Date and Time ‹ Date and Time Setup Using Genlink‹ Date and Time Setup Using Front Panel Adjust Display Contrast ‹ HTS Setup Using Front Panel ‹ HTS Setup Using GenlinkGeneral Information Remote Annunciator Connection Option NEW Generation Genlink NGG CommunicationsThermistor Appendix a Analog FunctionsPressure POLY3RD Linear POLY1STCurrent Calscale POLY1STN2‹ H-100 Analog Inputs Appendix B H-100 General I/O and Connector Information‹ H-100 Digital Inputs ‹ H-100 Digital Outputs‹ H-100 Digital Output Functions Fuel PRS Fault Analog 6 FaultInlt TMP Fault GOV POS HI AlarmTOT PWR LO Alarm TOT PWR HI AlarmGEN Freq Fault ENG RPM HI AlarmUSR Config Fault RLY ActiveChck V PHS ROT Chck C PHS ROTWire Signal Description ‹ H-100 Connector PIN DescriptionsAppendix C Miscellaneous H-100 Internal ALARMS/WARNINGS Control Panel Technical Manual Control Panel Technical Manual Generac Power SYSTEMS, INC