Interface module for 20-m local bus (N-V.24)

Description

1LED F (red), signals faults (line protocol faulty, receiver memory overflow)

2 LEDs (green)

D signals ”Data transfer on bus”

M signals ”Interface module has master function” T signals ”Bus processor busy”

B indicates setting of interface module on bus B A indicates setting of interface module on bus A

3 Reset key RS

4 Front plug X3 for connection of a non-Siemens computer via V.24 or 20-mA current loop interface

5 Front plug X4 for connection to the 20-m local bus 6 Jumpers for function and address settings

Fig. 4/4 Interface module for 20-m local bus (N-V.24)

voltage +5 V is loaded with 2.4 A per N-V. 24 module thereby. The number of useable interface modules N-V.24 is therefore restricted.

Possible plug-in slots: Slot for I/O module

In the AS 235 automation system (max. 2 modules N-V.24 per system (basic unit or extension unit)

In the AS 235 K automation system (max. 2 modules N-V.24 per system (basic unit)

In the AS 235 H automation system (max. 1 module N-V.24 per extension unit with 5-V module.)

Use of the N-V.24 interface module in the ES 100 K extension system or in the AS 215 automation system is not allowed.

Interfaces for non-Siemens computer

(alternatively at front plug X3)

V.24 interface

T x D

Transmitted data

 

Information is sent to the peripheral device via this line

R x D

Received data

 

Information is transferred to the system via this line

DSR

Data set ready

 

Input for ”data set ready” message from data circuit

 

terminating equipment

CTS

Clear to send

 

Input for ”clear to send” message from data circuit ter-

 

minating equipment

DTR

Data terminal ready

 

Output for operating status message of N-V.24 module

RTS

Request to send

 

Output signal, switches the transmitter unit of the data

 

circuit terminating equipment

I1,I2

Internal constant-current sources

20-mA current loop interface

R x D Received data

+20 mA: input, -- 20 mA: output T x D Transmitted data

+20 mA: input, -- 20 mA: output

Application

For connection of non-Siemens computers to the CS 275 bus system via a V.24 or 20-mA current loop interface.

The external computer must have a V.24 or 20-mA current loop interface. Coupling software is required in the external computer to handle communication with the interface module N-V.24.

The data transmission rate can be adapted to the requirements between 110 bit/s and 9600 bit/s; for example, 120 measured values/s can be transmitted at a data transfer rate of 9600 bit/s via the serial interface.

The module handles duties specifically connected with data transmission, including occasional control of data transfer.

Design

Compact subassembly, double height, with 1 base plug and 2 front plugs

Front panel width 30.48 mm = 2 standard slots.

The N-V.24 interface module is plugged into an I/O slot. It does not receive its supply voltage via L+ (DC 24 V) but via the sup- ply voltage +5 V of the I/O bus for the logic. The logic supply

Mode of operation

Communication between TELEPERM M systems and

non-Siemens computers

Data transfer between TELEPERM M systems and a non-Siemens computer via the CS 275 bus system is carried out using the same messages which are used for communication between TELEPERM M systems. The defined types of order (format, coding, acknowledgement mode) and the function of the hardware interface (N-V.24) are described in the Instructions for the interface module N-V.24 and in the Manual ”N-V.24, Cou- pling of non-Siemens computers to the CS 275 Bus System”.

Coupling software must be installed in the external computer which matches the computer to the communication conditions of the N-V.24 interface.

Setting of address

In order to differentiate between the individual interface modules in the autonomous bus system, each interface module must be allocated a so-called participant address. In order to differenti- ate between several autonomous buses connected via bus cou- plers, each interface module must be allocated a bus address. These two addresses are set using plug-in jumpers on the front panel of the interface module.

Siemens PLT 130 . 1994

4/5

Image 22
Contents This catalog is out of date, see note on Teleperm M Summary Siemens PLT 130 This catalog is out of date, see note on Mode of operation Data protection Mode of operationTransfer control, data protection and transfer Data transferAddressing Addressing, transmission modesTransmission modes Time synchronization Transmission reliabilityConfiguring of communication This catalog is out of date, see note on Design General notes, local range DesignLocal range Remote range Remote range, bus componentsBus components Bus system with linear structure Teleperm M Remote bus Bus components, technical data Technical dataBus configurations Bus configuration, examplesModules and ordering data Interface modules for 20-m local bus N-AS, 8 bit Interface module for 20-m local bus N-BK Interface module for 20-m local bus N-BK 6DS1 223-8ABInterface module for 20-m local bus N16-M, 16 bit Interface module for 20-m local bus N-V.24 DescriptionTechnical data and ordering data Interface module for 20-m local bus N-S5 Description and ordering data Technical data Interface module for 20-m local bus N-ATBus converter unit UI Connector board AF 13 Redundant remote bus with terminating resistorsRemote bus connection unit FAE Remote bus connection subrack S5 18 Bus coupler BK-FF, subrack configuration Bus coupler20 Bus coupler BK-FF, function diagram Application and ordering data Cable connectors for 20-m local busFront plug for 20-m local bus Front plug with contact points 6DS9 200-8AAOvervoltage protection 23 Coarse overvoltage protection 6DS9 208-8AAConfiguring notes and ordering data Configuring notesRemote bus cable with additional armouring V45466-D21-B65 Remote bus cablesV45466-D21-B55 C45197-A114-C330 Connection of remote bus cablesParts kit for splicing coaxial cables S45056-M125-A1 Cable plug SPN684732-00This catalog is out of date, see note on Appendix SY-TRANS 300 CS gateway Description SY-TRANS 300 CS converter German Description VMS/UNIX user interfaceAppendix Documentation for CS 275 bus system Ordering dataSubject index