Design

Bus components, technical data

Overvoltage protection

The participants connected to the remote bus can be exten- sively protected against destruction by overvoltages by means of the coarse and fine overvoltage protection units.

The coarse protection limits high-voltage signals of high power to the arc voltage. The coarse protection is able to handle brief peaks in the kA range. It is installed where the remote bus cable enters the building. The fine protection reduces the residual voltage which passes the coarse protection down to a value between the internal conductor and the screen of the remote bus cable which is harmless for the amplifier of the inductive coupler in the bus converter. The fine protection is fitted on the connector board AF.

Remote bus cable

Standard coaxial cable is used as the remote bus cable. This may be routed in potentially explosive atmospheres to

DIN 57 165/VDE 0165, Section 5.6.1. It is also suitable for burial in the ground. The max. permissible length is 4000 m.

An in-house cable with smaller outer diameter and smaller per- missible bending radius can be used indoors. The max. permis- sible length is 2000 m.

An increased tensile strength up to 25 000 N is possible using a cable with additional armouring. If protection against damage by rodents and mechanical damage is required, the cable with additional steel-tape armouring should be used.

Connection of remote bus cables

It may be necessary when using remote bus cables to connect sections together. The maximum available length of the in-house cable is 200 m, with all other types of cable 1000 m.

The type of connection depends on the type of cable. Standard and in-house cables are connected by splicing or by using RF plugs. The 2 other types of cable can be connected by splicing.

To provide protection against mechanical damage, the connec- tion should be enclosed in a metal sleeve. The cable armouring can be electrically connected using a copper cable (e. g. as additional overvoltage protection) and secured to prevent ten- sion. The sleeve is filled with sealing compound following as- sembly. All parts required can be obtained as a parts kit for splicing coaxial cables.

Technical data

Number of participants

100, dependent on bus loading

Distance without bus coupler

Max. 4000 m

Data formats

Variable

Bus control

Distributed (token passing principle)

Data protection

Block parity

Hamming distance

d = 4

Noise immunity

IEC Recommendation 255-4

Local bus

 

 

 

 

 

 

Number of participants

Max. 9

 

 

 

 

(bus converter UI counts as

 

 

 

 

participant)

Tranmission rate

250 kbit/s

 

 

 

 

The transmission rate is increased to

 

 

 

 

340 kbit/s with autonomous local bu-

 

 

 

 

ses, i. e. without remote bus coupling

Data transfer rate

Up to 2800 analog values/s or

 

 

 

 

up to 38400 binary values/s or

 

 

 

 

a corresponding combination

Overall cable length between

 

participant interface modules

Max. 20 m

Standard cable

12 x 2 x 0.22 m2

Signal transmission

Unbalanced

Signal level

5 V

Signal form

Unipolar

Coupling

Open collector

Redundant local bus

Standard

Remote bus

 

 

 

 

 

 

Number of converters (UI)

Max. 32

Number of bus couplers

Max. 7,

 

 

 

 

max. 2 between 2 communication

 

 

 

 

subscribers

Transmission rate

250 kbit/s

Standard cable

2YC (mS) CY 1.6/10-75

 

 

 

 

(Z2/5) vs sw

Signal form

Bipolar current signals

Coupling

Inductive, non-reactive

Redundant remote bus

Option

 

 

 

 

 

Siemens PLT 130 . 1994

3/5

Image 16
Contents This catalog is out of date, see note on Teleperm M Summary Siemens PLT 130 This catalog is out of date, see note on Mode of operation Mode of operation Transfer control, data protection and transferData protection Data transferAddressing Addressing, transmission modesTransmission modes Time synchronization Transmission reliabilityConfiguring of communication This catalog is out of date, see note on Design General notes, local range DesignLocal range Remote range Remote range, bus componentsBus components Bus system with linear structure Teleperm M Remote bus Bus components, technical data Technical dataBus configurations Bus configuration, examplesModules and ordering data Interface modules for 20-m local bus N-AS, 8 bit Interface module for 20-m local bus N-BK Interface module for 20-m local bus N-BK 6DS1 223-8ABInterface module for 20-m local bus N16-M, 16 bit Interface module for 20-m local bus N-V.24 DescriptionTechnical data and ordering data Interface module for 20-m local bus N-S5 Description and ordering data Technical data Interface module for 20-m local bus N-ATBus converter unit UI Connector board AF 13 Redundant remote bus with terminating resistorsRemote bus connection unit FAE Remote bus connection subrack S5 18 Bus coupler BK-FF, subrack configuration Bus coupler20 Bus coupler BK-FF, function diagram Cable connectors for 20-m local bus Front plug for 20-m local busApplication and ordering data Front plug with contact points 6DS9 200-8AAOvervoltage protection 23 Coarse overvoltage protection 6DS9 208-8AAConfiguring notes and ordering data Configuring notesRemote bus cable with additional armouring V45466-D21-B65 Remote bus cablesV45466-D21-B55 Connection of remote bus cables Parts kit for splicing coaxial cables S45056-M125-A1C45197-A114-C330 Cable plug SPN684732-00This catalog is out of date, see note on Appendix SY-TRANS 300 CS gateway Description SY-TRANS 300 CS converter German Description VMS/UNIX user interfaceAppendix Documentation for CS 275 bus system Ordering dataSubject index