Mode of operation

Redundant operation mode, transmission reliability, synchronization

Redundant operation mode

The CS 275 bus system can be redundant in order to increase the availability. The interface modules for the local bus are al- ready designed for a redundant local bus line. A bus converter UI and a connector board AF are required for connection of a redundant remote bus per remote bus cable. Different remote bus cable lengths are permissible between bus A and the re- dundant bus B.

The bus system is started up on bus A. Besides this, no prefer- ence is given to either bus. The bus system carries out a cyclic test to see whether a changeover criterion is satisfied. An auto- matic changeover is carried out if this is the case.

Changeover criteria

An image of the local bus is generated through each bus line approx. every 750 ms. If the image of the passive bus con- tains more entries than that of the active bus, the system switches to the passive bus.

If the images on the two bus lines are the same, but the mas- ter detects a transfer request on the passive bus, a change- over also takes place to the passive bus. A slave sends trans- fer requests on the passive bus if transfers are no longer possible for it on the active bus.

If the current master fails because of a fault, the slave with the smallest participant address assumes the master function on the previously passive bus (if one exists).

The bus changeover is signalled to all bus participants.

Time synchronization

The real-time clocks of the particular TELEPERM M subsystems are synchronized by signals from an OS operation and monitor- ing system. This can be synchronized by a radio clock (DCF 77 radio transmitter) or a standard clock.

The subscribers on the CS 275 bus system must be synchro- nized with high accuracy. Because of it, the transit time of the synchronization message is corrected within the milliseconds range by the internal buffers of the local bus interface modules of the automation systems and programmable controllers or by bus couplers.

Date and time transmission program

Remote bus 1

Time receive memory

Intermediate time counter ' t (ms)

Transmission buffer

Remote bus 2

Fig. 2/3 Time generation, time synchronization

Transmission reliability

In addition to data security of the transmission method, the fol- lowing measures ensure high transmission reliability in the physical transmission path:

Noise immunity to IEC 255-4 Triple screened cable, redundant

Coarse overvoltage protection in the building entry (option)

Fine overvoltage protection in the connector board AF (option)

Deflection of noise using braided screens and metal front plugs

Passive line without amplifier

Non--reactive inductive coupling

Appropriate signal coding on the remote bus (bipolar current signals)

Automatic signal equalization independent of location Balanced (to earth) transmission

High signal voltages

Electrical isolation of participants on remote bus Distributed transfer control.

2/4

Siemens PLT 130 . 1994

Image 9
Contents This catalog is out of date, see note on Teleperm M Summary Siemens PLT 130 This catalog is out of date, see note on Mode of operation Transfer control, data protection and transfer Mode of operationData protection Data transferAddressing, transmission modes AddressingTransmission modes Transmission reliability Time synchronizationConfiguring of communication This catalog is out of date, see note on Design Design General notes, local rangeLocal range Remote range, bus components Remote rangeBus components Bus system with linear structure Teleperm M Remote bus Technical data Bus components, technical dataBus configuration, examples Bus configurationsModules and ordering data Interface modules for 20-m local bus N-AS, 8 bit Interface module for 20-m local bus N-BK 6DS1 223-8AB Interface module for 20-m local bus N-BKInterface module for 20-m local bus N16-M, 16 bit Description Interface module for 20-m local bus N-V.24Technical data and ordering data Interface module for 20-m local bus N-S5 Interface module for 20-m local bus N-AT Description and ordering data Technical dataBus converter unit UI 13 Redundant remote bus with terminating resistors Connector board AFRemote bus connection unit FAE Remote bus connection subrack S5 Bus coupler 18 Bus coupler BK-FF, subrack configuration20 Bus coupler BK-FF, function diagram Front plug for 20-m local bus Cable connectors for 20-m local busApplication and ordering data Front plug with contact points 6DS9 200-8AA23 Coarse overvoltage protection 6DS9 208-8AA Overvoltage protectionConfiguring notes Configuring notes and ordering dataRemote bus cables Remote bus cable with additional armouring V45466-D21-B65V45466-D21-B55 Parts kit for splicing coaxial cables S45056-M125-A1 Connection of remote bus cablesC45197-A114-C330 Cable plug SPN684732-00This catalog is out of date, see note on Appendix SY-TRANS 300 CS gateway Description VMS/UNIX user interface Description SY-TRANS 300 CS converter GermanDocumentation for CS 275 bus system Ordering data AppendixSubject index