Siemens CS 275 manual Technical data and ordering data

Page 23

This catalog is out of date, see note on page 2

Interface module for 20-m local bus (N-V.24)

Technical data and ordering data

This circuit cancels the electrical isolation of the N.-V.24 interface

Fig. 4/5 20-mA current loop interface with internal constant-current source for transmitter (left) and receiver (right), connection example

Fig. 4/6 20-mA current loop interface with external current loop for trans- mitter (left) and receiver (right), connection example

Technical data

 

Power supply

 

DC 5 V

 

 

 

Current consumption

 

2.4 A

 

 

 

Interfaces

 

 

 

 

 

- Base plug

 

5-V power supply

 

 

- Front plug X3

 

Serial V.24 or

 

 

 

 

 

 

20-mA current loop interface

 

 

 

 

 

for distances up to 15 or 1000m

 

 

- Front plug X4

 

respectively, 4-wire system

 

 

 

Redundant 20-m local bus output, open

 

 

 

 

 

collector, asymmetric,

 

 

 

 

 

for connection of a cable connector

 

 

 

 

 

with metal front plug and contact parts

 

 

Weight

 

Approx. 0.75 kg

 

 

 

 

 

 

 

 

 

 

 

20-m local bus

V.24- or 20-mA

 

 

 

 

 

 

interface

 

 

 

 

 

 

 

 

Transmission rate

 

340 kbit/s (autonomous)

110 bit/s to

 

 

 

 

250 kbit/s (remote

9600 bit/s,

 

 

 

 

bus connection

can be set on module

 

 

 

 

via inductive converter)

 

 

 

 

 

 

 

 

 

Data protection

 

Horizontal parity (d = 4)

Longitudinal parity

 

 

 

 

 

 

(d = 2)

 

 

 

 

 

 

 

 

Operating mode

 

Half-duplex

Half-duplex,

 

 

 

 

 

 

contention mode

 

 

 

 

 

 

 

 

Character frame

 

Bus transfer element

8bit,code-transparent

 

 

 

 

 

 

 

 

 

Authorization for

 

Token passing principle

DIN 66 020

 

 

data transmission

 

 

 

(V.24)

 

 

 

 

 

 

 

 

Ordering data

 

 

Order No.

Interface module for 20-m local bus (N-V.24)

 

 

with V.24 or 20-mA current loop interface

 

 

¯ with parts kit for front plug and installation

 

6DS1 202-1AB

 

instructions in German

 

 

¯ Without parts kit for front plug

 

6DS1 202-8AB

 

Parts kit for front plug

 

C79458-L437-D1

 

for interface module 6DS1 202-8AB

 

 

with installation instructions in German

 

 

KSN-PC coupling software

 

See Catalog PLT 150

for SICOMP industry-standard PC or

 

 

PG 750/PG 770 programmer

 

 

 

 

 

Instructions

 

 

Interface module for 20-m local bus,

 

Order No.

V.24- or 20-mA current loop interface

 

 

German

 

C79000-B8000-C3

English

 

C79000-B8076-C3

French

 

C79000-B8077-C3

Spanish

 

C79000-B8078-C3

Manuals

 

 

N-V.24: Coupling of non-Siemens

 

 

computers to the CS 275 bus system

 

 

German

 

C79000-G8000-C87

English

 

C79000-G8076-C87

4/6

Siemens PLT 130 . 1994

Image 23
Contents This catalog is out of date, see note on Teleperm M Summary Siemens PLT 130 This catalog is out of date, see note on Mode of operation Data transfer Mode of operationTransfer control, data protection and transfer Data protectionTransmission modes Addressing, transmission modesAddressing Transmission reliability Time synchronizationConfiguring of communication This catalog is out of date, see note on Design Local range DesignGeneral notes, local range Bus components Remote range, bus componentsRemote range Bus system with linear structure Teleperm M Remote bus Technical data Bus components, technical dataBus configuration, examples Bus configurationsModules and ordering data Interface modules for 20-m local bus N-AS, 8 bit Interface module for 20-m local bus N-BK 6DS1 223-8AB Interface module for 20-m local bus N-BKInterface module for 20-m local bus N16-M, 16 bit Description Interface module for 20-m local bus N-V.24Technical data and ordering data Interface module for 20-m local bus N-S5 Interface module for 20-m local bus N-AT Description and ordering data Technical dataBus converter unit UI 13 Redundant remote bus with terminating resistors Connector board AFRemote bus connection unit FAE Remote bus connection subrack S5 Bus coupler 18 Bus coupler BK-FF, subrack configuration20 Bus coupler BK-FF, function diagram Front plug with contact points 6DS9 200-8AA Cable connectors for 20-m local busFront plug for 20-m local bus Application and ordering data23 Coarse overvoltage protection 6DS9 208-8AA Overvoltage protectionConfiguring notes Configuring notes and ordering dataV45466-D21-B55 Remote bus cablesRemote bus cable with additional armouring V45466-D21-B65 Cable plug SPN684732-00 Connection of remote bus cablesParts kit for splicing coaxial cables S45056-M125-A1 C45197-A114-C330This catalog is out of date, see note on Appendix SY-TRANS 300 CS gateway Description VMS/UNIX user interface Description SY-TRANS 300 CS converter GermanDocumentation for CS 275 bus system Ordering data AppendixSubject index