Century Jefferson manual Installation Requirements, Locating The Stove, Clearance Requirements

Page 6

Jefferson Direct Vent/Natural Vent Gas Heater

Installation Requirements

The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition. (EXCEP- TION: Do not derate this appliance for altitude. Main- tain the manifold pressure at 3.5” w.c. for Natural Gas, and 10” w.c. for Propane).

In Canada, installation must be in accordance with the current CSA B-149.1 Installation Codes and/or local

codes.

The installation should be done by a qualified service person, preferably NFI or WETT (Canada) certified who is familiar with the building codes and

installation techniques appropriate for your area to accomplish a safe and effective installation.

Your dealer or your local gas supplier will be able to refer a qualified service person.

WARNING: Due to high temperatures, the HEATER should be located out of traffic and

away from furniture and draperies.

The surface of the Heater Is hot when it is in use. Young children should be watched carefully when they are in the same room when the Heater is in use, and they should be taught to avoid the hot surface. Keep any objects that can burn well away from the Heater, and observe the recommended clearances that follow.

�������

��������������

������������

������������������

�������������

��������������������

���������������

Locating The Stove

In choosing a location for the stove, consider:

The location of outside walls;

Where additional heat is needed:

Where family members gather most often;

The vent system requirements.

NOTE: We do not recommend the use of wallpaper next to this stove. Over time, radiant heat may cause the wallpaper to shrink, or may adversely affect the binders in the wallpaper adhesive.

Direct Vent System Only

A D

B

C

E

A. Flat on corner wall

D. Cross Corner

B. Room Divider

E. Flat on wall

C. Island

ST207a

Fig. 2 Possible stove locations.

Clearance Requirements

Minimum Clearances to Combustible Materials

Measure side clearances as shown in Figures 3 and 4 from the outer edge of the cast iron stove top. Measure rear clearances from the outermost surface of the steel rear skirt.

The Jefferson heater is approved for installation into an alcove constructed of combustible materials to the dimensions and clearances shown on the next page.

The same clearances apply in a standard parallel instal- lation.

WARNING:

• Always maintain required clearances (air spaces) to nearby combustibles

to prevent fire hazard. Do not fill air spaces with insulation. All venting components must maintain a 1” (25 mm) clearance to com- bustible materials. Maintain a 6” (150 mm) clear- ance when using single wall pipe.

The gas appliance and vent system must be vented directly to the outside of the building and never be attached to a chimney serving a separate solid fuel or gas-burning appliance.

Refer to the manufacturer’s instructions includ- ed with the venting system for complete instal- lation procedures.

66

30004177

Image 6
Contents Jefferson Direct Vent/Natural Vent Gas Heater Table of Contents Installation & Operating Instructions Requirements for the Commonwealth of Massachusetts Gas Equipment Venting System not ProvidedJefferson Direct Vent/Natural Vent Stove Dimensions Jefferson dimensionsInstallation Requirements Locating The StoveClearance Requirements Wall Centerline from Floor Wall and Ceiling ClearancesHearth Requirements High Elevations Gas SpecificationsGas Inlet and Manifold Pressures Horizontal Termination Direct Vent onlyRestictor Plate is used on Direct Vent installations only Vertical Termination Direct Vent onlyVent Termination Clearances Location of Vent Termination Canadian Installations1 US Installations2 General Venting Information Termination LocationVenting Requirements Natural Vent Only Termination ClearancesVenting Requirements and Options Direct Vent only Approved Vent System ComponentsTools Required Assembly ProceduresInstall the Optional Fan Unpack the StoveVenting System Assembly Direct Vent General Information Install the Vent Adapter PipeFor Canadian installations The venting system must Attach the Inner Vent Assembly to the stove Attach inner assembly to flue collarSide Wall Termination Assembly Simpson Dura-Vent install outer adapter pipeVent Termination Below Grade Measure the horizontal lengthVertical Through the Roof Vent Assembly Venting System Assembly Natural Vent General InformationInstall the Vent Pipe Install the Log Set Air Shutter Adjustment Air Shutter AdjustmentAir Shutter Adjustment Instructions Connect the Gas Supply LineRemove stove front Install the Stove Front Complete the AssemblyInstall ON/OFF Switch Thermostat Connection optionalOperation Flame & Temperature AdjustmentFlame Characteristics Your First FireLighting and Operating Instructions To Turn Off Gas To HeaterTroubleshooting / Honeywell #8420 Gas Control System Symptom Possible Causes Corrective ActionFuel Conversion Instructions Conversion PrecautionsConversion Procedure Pilot TypeInjector Orifice Size Matrix Conversion to LP Input BTU/hMaintenance Inspect the Vent System Annually Gasket ReplacementStove Disassembly Check the Gas Flame RegularlyWiring Diagrams BLKJefferson Direct Vent/Natural Vent Gas Heater DescriptionDescripción Fuel Conversion KitsFan Kits Optional AccessoriesRemote Controls Decorative Rings3636 Jefferson Direct Vent /Natural Vent Gas Heater 3838 CFM Corporation Toll Free Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency %