Hearth and Home Technologies Cinch Pipe & Termination Cap System Burn Risk

Page 9

E. Install the Heat Shield and Horizontal Termination Cap

WARNING

A 1-1/2 in. minimum overlap MUST be maintained on the telescoping fl ue section of the cap.

WARNING

Fire Risk

Exhaust Fumes Risk

Impaired performance of appliance.

Overlap pipe slip sections at least 2 in.

Use pilot holes for screws.

Screws must not exceed 1 in. long.

Pipe may separate if not properly joined.

on the extended heat shield should rest on the top of the vent (pipe section) to properly space it from the pipe section.

Install the Horizontal Termination Cap

Vent termination must not be recessed in the wall. Siding may be brought to the edge of the cap base.

Caulk the outside edges of the cap.

When installing a horizontal termination cap, follow the cap location guidelines as prescribed by current ANSI Z223.1 and CAN/CGA-B149installation codes.

WARNING

Burn Risk

Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap.

Heat Shield Requirements for Horizontal Termination

For all horizontally vented appliances, a heat shield MUST be placed 1 in. above the top of the vent between the wall shield and the base of the termination cap.

There are two sections of the heat shield. One section at- taches to the wall shield with two screws. The remaining section is attached to the cap in the same manner. See Figure 2.16.

If the wall thickness does not allow the required 1-1/2 in. heat shield overlap, an extended heat shield must be used.

The extended heat shield will need to be cut to the thickness of the wall and be attached to the wall shield. The small leg

Heat Shield or

Rear Vent

Extended

Heat Shield

Heat Shield

1-1/2 in. (38 mm) min.

Wall Shield

overlap

 

Inner Vent

 

Outer Vent

EXTERIOR

INTERIOR

 

SHEATHING

Figure 2.16 Venting through the Wall

WARNING

Do NOT connect a pipe section to a termination cap without using the telescoping fl ue section found on the termination cap.

Note: Where required, an exterior wall fl ashing is available. When penetrating a brick wall, a brick extension kit is available for framing the brick.

Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05

9

Image 9 Contents
Any such action may cause a fire hazard Installation InstructionsNot shown Parts and DescriptionsCool ADD Trap CAP Specification Chart Penetrating a Wall Clearances for the Vent SectionsTop Vented Direct Vent Appliances Rear Vented Direct Vent AppliancesAssemble Vent Sections Attaching Vent to the Firebox AssemblyAssemble Pipe Sections Fire Risk Exhaust Fumes RiskAssemble Slip Sections Assemble Minimum Installation MI SectionsDisassemble Vent Sections Secure the Vent SectionsFire Risk Explosion Risk Asphyxiation Risk Install the Horizontal Termination Cap Install the Heat Shield and Horizontal Termination CapBurn Risk Heat Shield Requirements for Horizontal TerminationInstall Attic Insulation Shield Install the Firestop SpacerVertical Penetration Framing Fire Risk20 Secure with Screws Roof Pitch Min. Ft Install Roof Flashing and Vertical Termination CapCaulk around the top of the storm collar Assemble and Install Storm Collar