Hearth and Home Technologies EL42, EL36 owner manual Clearances to Combustible Materials

Page 19

B. Clearances

Warning! Risk of Fire! You must comply with all minimum air space clearances to combustibles as specified in Fig- ure 6.2. Do NOT pack required air spaces with insulation or other materials.

Storm Collar

Roof Flashing

(attic)

(insulation)

Shaded areas

represent

2 in. (51 mm) min.

air space clearance required around pipe

Attic

Insulation

Shield

(ceiling)

2 in. (51 mm) min.

Offset/Return (secured

with hanger straps)

(ceiling)

Ceiling Firestop

0 in. to level of standoffs

Must have 2 in. (51 mm)

minimum clearance

to header

Combustible Object

48 in. 1219 mm

1/2 in. (13 mm) to back & sides of appliance

0in.

to floor

Figure 6.2 Clearances to Combustible Materials

Note: Chimney air kit is not shown, but is required in Canada.

Heatilator • EL36/EL42 • 4044-132 • Rev AD• 7/12

19

Image 19 Contents
Hot screen/mesh and glass doors will cause burns Wood Burning FireplaceFire Risk Listing Label Information/Location Homeowner Reference InformationInstaller Guide Table of ContentsUser Guide Limited Lifetime Warranty Warranty Hearth & Home Technologies IncThis warranty is void if Warranty ConditionsCombustible Materials Listing and Code ApprovalsAppliance Certification Non-Combustible MaterialsYour Fireplace Operating InstructionsHot glass will cause burns Firescreen Seasoned WoodStarting a Fire GrateClear Space Glass DoorsVented Gas Log Sets & Gas Log Lighters Optional ComponentsWood Fuel Creosote Formation and Need for Removal Maintenance and ServiceChimney Inspection/Cleaning Disposal of AshesFrequency As desired Glass CleaningCheck Firebox Refractory Inspect GrateStart Fire Problems Possible Cause Solution Troubleshooting GuideTypical Fireplace System Getting Started Draft Design and Installation Considerations Negative Pressure Recommended Chimney Locations Locating Fireplace & ChimneyFireplace System Requirements Tools and Supplies NeededInspect Fireplace and Components Select Fireplace Location Framing & ClearancesClearances to Combustible Materials ClearancesModel # Sidewalls/SurroundsFrame the Fireplace OutsidePlace Protective Metal Hearth Strips Installation of FireplaceThings to Consider Position the FireplaceFt min. from top of uppermost chimney section to air inlet Outside Air Installation Install Outside Air KitChimney Assembly Chimney Requirements Chimney RequirementsSL306 SL312 SL318 SL324 SL336 SL348 Using Offsets/ReturnsExample DegreeAssemble Chimney Sections Install Chimney Air KitInstalling the Ceiling Firestop Install Ceiling FirestopsPrepare Attic Insulation Shield Install Attic Insulation ShieldCut out Hole in Roof Complete InstallationInstall Flashing Following steps should be skipped if using a chaseMultiple Chimney Locations Chimney Termination RequirementsConstruct the Chase Chase InstallationsInstall Chase Top Install Fireplace & ChimneyCap Install Termination CapTS345/TS345P Square Termination Cap Open Top Shroud TR342 caps require radiation shield ShroudsRadiation Shield Field Constructed ShroudsTR342/344 Mailbox Style Shroud radiation shield requiredRoofed Style Shroud radiation shield required TS345 TR342Material Finishing= 1/k x inches of thickness Hearth Extension MinimumModel # Raised Hearth Extension FramingRaised Platform Hearth Extension-Finishing Materi- als Non-combustible SealantDecorative Facing Finishing MaterialClearances to Mantels or other Combustibles above Fireplace Combustible Mantel4 in mm Gas Code, Ansi Z223.1 AccessoriesGas Log/Lighter Provision Wood Burning InsertsReference Materials Fireplace DimensionsAK24 In. HX3 Hearth Extension 13 mmMm HX4 Hearth Extension Bifold Glass Doors DM1036, DM1042Catalog # Chimney ComponentsST375 Square Termination Cap JB877 Chimney Joint BandCeiling Firestop CB876 Chimney Joint BandCT35 Chase Top TCT375 Terra Cotta CapTS345/TS345P Square Termination Cap Damper Kit Air Handle Part number list on followingStocked Service PartsAt Depot Piece Rod EL42EL42 Contact Information