Hearth and Home Technologies EL42, EL36 owner manual Raised Hearth Extension Framing, Model #

Page 39

Model #

A

B

C

D

EL36

in.

36

52

8

16

mm

914

1321

203

406

 

EL42

in.

42

66

12

20

mm

107

1676

305

508

 

Raised Hearth Extension Framing

Warning! Risk of Fire. A raised hearth extension built flush with the fireplace opening (Figure 11.3) or less than 4 in. (102 mm) below the fireplace opening requires the fireplace be installed on a non-combustible surface.

The hearth framing must be constructed of non-combus- tible materials (Figure 11.2) and placed on 1/2 in. Micore, or equivalent material (Figure 11.4). When creating the platform, allow for the thickness of the non-combustible finishing materials (Figure 11.5).

4 in. (102 mm)

 

minimum between

 

bottom of fireplace opening

 

and finished surface of hearth extension

C

 

A

 

B

C

 

 

D

Figure 11.1 Hearth Extension Dimensions

 

Continuous, non-

Fireplace

combustible sealant

Opening

1/2 in. Micore Hearth

Tile, stone or other

 

Extension (or

non-combustible material

4 in.

equivalent insulation)

 

 

(102 mm) min.

See Table 11.2.

 

 

 

Floor constructed of wood or

2 in. (51 mm) of the Protective

Metal Hearth Strip is required

other combustible material

under the front of the fireplace

Figure 11.2 Hearth Extension Construction

IMPORTANT! Hearth extension design must be determined before installation of fireplace.

Non-combustible

Material

Non-combustible

Finishing Material

Non-combustible

Framing Material

1/2 in. Micore

 

 

 

 

 

 

 

 

Protective Metal

Floor

or equivalent

Hearth Strips

 

 

insulation

 

 

 

 

 

 

Figure 11.3 Raised Platform Hearth Extension Detail

Non-combustible

Framing Material1/2 in. Micore or equivalent insulation

Figure 11.4 Raised Platform Hearth Extension-Framing Materials

Heatilator • EL36/EL42 • 4044-132 • Rev AD• 7/12

39

Image 39
Contents Wood Burning Fireplace Hot screen/mesh and glass doors will cause burnsFire Risk Listing Label Information/Location Homeowner Reference InformationTable of Contents Installer GuideUser Guide Limited Lifetime Warranty Warranty Hearth & Home Technologies IncThis warranty is void if Warranty ConditionsCombustible Materials Listing and Code ApprovalsAppliance Certification Non-Combustible MaterialsOperating Instructions Your FireplaceHot glass will cause burns Firescreen Seasoned WoodStarting a Fire GrateClear Space Glass DoorsVented Gas Log Sets & Gas Log Lighters Optional ComponentsWood Fuel Creosote Formation and Need for Removal Maintenance and ServiceChimney Inspection/Cleaning Disposal of AshesFrequency As desired Glass CleaningCheck Firebox Refractory Inspect GrateStart Fire Problems Possible Cause Solution Troubleshooting GuideTypical Fireplace System Getting StartedDesign and Installation Considerations DraftNegative Pressure Recommended Chimney Locations Locating Fireplace & ChimneyTools and Supplies Needed Fireplace System RequirementsInspect Fireplace and Components Select Fireplace Location Framing & ClearancesClearances to Combustible Materials ClearancesModel # Sidewalls/SurroundsFrame the Fireplace OutsidePlace Protective Metal Hearth Strips Installation of FireplaceThings to Consider Position the FireplaceFt min. from top of uppermost chimney section to air inlet Outside Air Installation Install Outside Air KitChimney Assembly Chimney Requirements Chimney RequirementsSL306 SL312 SL318 SL324 SL336 SL348 Using Offsets/ReturnsExample DegreeAssemble Chimney Sections Install Chimney Air KitInstalling the Ceiling Firestop Install Ceiling FirestopsPrepare Attic Insulation Shield Install Attic Insulation ShieldCut out Hole in Roof Complete InstallationInstall Flashing Following steps should be skipped if using a chaseMultiple Chimney Locations Chimney Termination RequirementsConstruct the Chase Chase InstallationsInstall Chase Top Install Fireplace & ChimneyCap Install Termination CapTS345/TS345P Square Termination Cap Open Top Shroud TR342 caps require radiation shield ShroudsRadiation Shield Field Constructed ShroudsTR342/344 Mailbox Style Shroud radiation shield requiredRoofed Style Shroud radiation shield required TS345 TR342Material Finishing= 1/k x inches of thickness Hearth Extension MinimumModel # Raised Hearth Extension FramingRaised Platform Hearth Extension-Finishing Materi- als Non-combustible SealantDecorative Facing Finishing MaterialClearances to Mantels or other Combustibles above Fireplace Combustible Mantel4 in mm Gas Code, Ansi Z223.1 AccessoriesGas Log/Lighter Provision Wood Burning InsertsReference Materials Fireplace DimensionsAK24 In. HX3 Hearth Extension 13 mmMm HX4 Hearth Extension Bifold Glass Doors DM1036, DM1042Catalog # Chimney ComponentsST375 Square Termination Cap JB877 Chimney Joint BandCeiling Firestop CB876 Chimney Joint BandTCT375 Terra Cotta Cap CT35 Chase TopTS345/TS345P Square Termination Cap Damper Kit Air Handle Part number list on followingService Parts StockedAt Depot Piece Rod EL42EL42 Contact Information